outletControlOnCmd

EATON-EPDU-MIB · .1.3.6.1.4.1.534.6.6.7.6.6.1.4

Object

column r/w Integer32
Outlet control command.
              
Once the command is issued, the outlet will turn On immediately.
0-n : Time in seconds until the outlet command is issued
-1 : Cancel a pending outlet On command 
              
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
                        
          Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
          commands.  These will respond with an error if a command value of > 0 is written to this object.

Context

MIB
EATON-EPDU-MIB
OID
.1.3.6.1.4.1.534.6.6.7.6.6.1.4
Type
column
Access
readwrite
Status
current
Parent
outletControlEntry
Table
outletControlTable
Siblings
8

Syntax

Integer32

Values & Constraints

Object Constraints
range: -1-99999

Related Objects