outletControlEntry
EATON-EPDU-MIB ·
.1.3.6.1.4.1.534.6.6.7.6.6.1
Object
row
An entry for a controllable outlet.
Context
- MIB
- EATON-EPDU-MIB
- OID
.1.3.6.1.4.1.534.6.6.7.6.6.1- Type
- row
- Status
- current
- Parent
- outletControlTable
- Table
- outletControlTable
- Children
- 9
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| outletControlShutoffDelay Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first
then wri… | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.6.1.10 |
| outletControlStatus Current state of a controlled outlet. | column | Enumeration | .1.3.6.1.4.1.534.6.6.7.6.6.1.2 |
| outletControlOffCmd Outlet control command.
Once the command is issued, the outlet will turn Off immediately.
0-n : Time in seconds until the outlet command is issued
-1 : Cancel a pen… | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.6.1.3 |
| outletControlOnCmd Outlet control command.
Once the command is issued, the outlet will turn On immediately.
0-n : Time in seconds until the outlet command is issued
-1 : Cancel a pend… | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.6.1.4 |
| outletControlRebootCmd Outlet control command.
For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is
issued, remain Off for outletCont… | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.6.1.5 |
| outletControlPowerOnState Determines the outlet state when power is applied to the unit.
0 : not restart at device startup
1 : should sequence back ON in line with outletControlSequenceTime
2 : should take… | column | Enumeration | .1.3.6.1.4.1.534.6.6.7.6.6.1.6 |
| outletControlSequenceDelay Time delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on
delay. Set to -1 to e… | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.6.1.7 |
| outletControlRebootOffTime Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.6.1.8 |
| outletControlSwitchable Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled
2 : control On/Off disabled. | column | Enumeration | .1.3.6.1.4.1.534.6.6.7.6.6.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| strappingIndex For units that support 'strapping' functionality, this will be a unique
value for each unit. If units do not support 'strapping', this will
always be '0'. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.1.2.1.1 |
| outletIndex A unique value for each outlet. its value ranges from 1 to outletCount. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.1.1.1 |