outletVoltageEntry
EATON-EPDU-MIB ·
.1.3.6.1.4.1.534.6.6.7.6.3.1
Object
row
An entry for an outlet voltage measurement.
Context
- MIB
- EATON-EPDU-MIB
- OID
.1.3.6.1.4.1.534.6.6.7.6.3.1- Type
- row
- Status
- current
- Parent
- outletVoltageTable
- Table
- outletVoltageTable
- Children
- 6
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| outletVoltage Units are millivolts. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.6.7.6.3.1.2 |
| outletVoltageThStatus Status of the measured outlet voltage relative to the configured thresholds. | column | Enumeration | .1.3.6.1.4.1.534.6.6.7.6.3.1.3 |
| outletVoltageThLowerWarning Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.3.1.4 |
| outletVoltageThLowerCritical Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.3.1.5 |
| outletVoltageThUpperWarning Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.3.1.6 |
| outletVoltageThUpperCritical Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.3.1.7 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| strappingIndex For units that support 'strapping' functionality, this will be a unique
value for each unit. If units do not support 'strapping', this will
always be '0'. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.1.2.1.1 |
| outletIndex A unique value for each outlet. its value ranges from 1 to outletCount. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.6.1.1.1 |