humidityProbeStatus
EATON-EPDU-MIB ·
.1.3.6.1.4.1.534.6.6.7.7.2.1.3
Object
column
Enumeration
Indicates whether a probe is connected or not.
Context
- MIB
- EATON-EPDU-MIB
- OID
.1.3.6.1.4.1.534.6.6.7.7.2.1.3- Type
- column
- Access
- readonly
- Status
- current
- Parent
- humidityEntry
- Table
- humidityTable
- Siblings
- 8
Syntax
Enumeration
Values & Constraints
Enumerated Values
-1 | bad |
0 | disconnected |
1 | connected |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| humidityIndex A unique value for each humidity probe measurement. Its value
ranges from 1 to humidityCount. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.1 |
| humidityName A descriptive name for the humidity probe. | column | OctetString | .1.3.6.1.4.1.534.6.6.7.7.2.1.2 |
| humidityValue Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.4 |
| humidityThStatus Status of the measured humidity relative to the configured
thresholds. | column | Enumeration | .1.3.6.1.4.1.534.6.6.7.7.2.1.5 |
| humidityThLowerWarning Lower warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.6 |
| humidityThLowerCritical Lower critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.7 |
| humidityThUpperWarning Upper warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.8 |
| humidityThUpperCritical Upper critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.9 |