humidityEntry
EATON-EPDU-MIB ·
.1.3.6.1.4.1.534.6.6.7.7.2.1
Object
row
An entry for a humidity measurement.
Context
- MIB
- EATON-EPDU-MIB
- OID
.1.3.6.1.4.1.534.6.6.7.7.2.1- Type
- row
- Status
- current
- Parent
- humidityTable
- Table
- humidityTable
- Children
- 9
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| humidityIndex A unique value for each humidity probe measurement. Its value
ranges from 1 to humidityCount. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.1 |
| humidityName A descriptive name for the humidity probe. | column | OctetString | .1.3.6.1.4.1.534.6.6.7.7.2.1.2 |
| humidityProbeStatus Indicates whether a probe is connected or not. | column | Enumeration | .1.3.6.1.4.1.534.6.6.7.7.2.1.3 |
| humidityValue Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.4 |
| humidityThStatus Status of the measured humidity relative to the configured
thresholds. | column | Enumeration | .1.3.6.1.4.1.534.6.6.7.7.2.1.5 |
| humidityThLowerWarning Lower warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.6 |
| humidityThLowerCritical Lower critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.7 |
| humidityThUpperWarning Upper warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.8 |
| humidityThUpperCritical Upper critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| strappingIndex For units that support 'strapping' functionality, this will be a unique
value for each unit. If units do not support 'strapping', this will
always be '0'. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.1.2.1.1 |
| humidityIndex A unique value for each humidity probe measurement. Its value
ranges from 1 to humidityCount. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.7.2.1.1 |