groupControlRebootCmd
EATON-EPDU-MIB ·
.1.3.6.1.4.1.534.6.6.7.5.6.1.5
Object
column
r/w
Integer32
Group-level outlet control command.
For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is
issued, remain Off for outletControlRebootOffTime seconds, and then turn back On.
For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime
seconds from when the command is issued.
0-n : Time in seconds until the Reboot command is issued
-1 : Cancel a pending group-level Reboot command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object.
Context
- MIB
- EATON-EPDU-MIB
- OID
.1.3.6.1.4.1.534.6.6.7.5.6.1.5- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- groupControlEntry
- Table
- groupControlTable
- Siblings
- 3
Syntax
Integer32
Values & Constraints
Object Constraints
range: -1-0
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| groupControlStatus Current state of a controlled group. A value of 'mixed' means that
that the outlets within the group have differing states. | column | Enumeration | .1.3.6.1.4.1.534.6.6.7.5.6.1.2 |
| groupControlOffCmd Group-level outlet control command.
Once the command is issued, the outlets in the group will turn Off immediately.
0-n : Time in seconds until the group command is… | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.5.6.1.3 |
| groupControlOnCmd Group-level outlet control command.
Once the command is issued, the outlets in the group will turn On immediately.
0-n : Time in seconds until the group command is … | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.5.6.1.4 |