.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1 · 1 row entry · 3 columns
Controller's event history table that shows the content of the
default log file.
dcEventHistoryEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1
A particular Event History entry.
Indexes
dcEventHistoryIndex
Column Syntax OID
dcEventHistoryIndex
Table index.
Integer32
Constraints:
range: 1-10000
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1
dcEventHistoryTimestamp
ISO8601 timestamp representation of a particular entry
in the form YYYY-MM-DDThh:mm:ss.
OctetString
Constraints:
range: 19-19
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2
dcEventHistoryMessage
Event message of a particular entry.
OctetString
Constraints:
range: 1-255
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2 · 1 row entry · 5 columns
Table that shows all active sent Traps.
dcAlarmEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1
A particular active alarm source entry.
Indexes
dcAlarmIndex
Column Syntax OID
dcAlarmIndex
Table index.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1
dcAlarmEventCategory
Specifies the type of alarm source.
Enumeration
Enumerated Values:
1unknown
2urgent
3nonUrgent
4critical
5allAlarm
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2
dcAlarmEventName
Name of a particular alarm source entry.
OctetString
Constraints:
range: 1-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3
dcAlarmEventIdentifier
Unique alarm event identifier.
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4
dcAlarmEventValue
Event status that corresponds to alarm event identifier.
Enumeration
Enumerated Values:
1false
3true
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12 · 1 row entry · 4 columns
Table that shows ten alarm event assignments that can be 
configured via WEB interface.
dcGenericAlarmEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1
A particular generic alarm entry.
Indexes
dcGenericAlarmIndex
Column Syntax OID
dcGenericAlarmIndex
Table index.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1
dcGenericAlarmEventName
Plain text name of the assigned alarm event. Empty if not
configured.
OctetString
Constraints:
range: 0-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2
dcGenericAlarmEventIdentifier
Unique numeric identifier of the assigned alarm event. Zero
if not configured.
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3
dcGenericAlarmEventValue
Current value of the assigned alarm event. Value is false if
not configured.
Enumeration
Enumerated Values:
1false
2true
.1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4 · 1 row entry · 7 columns
Table that shows all currently active rectifier modules.
dcRectifierEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1
A particular rectifier entry.
Indexes
dcRectifierIndex
Column Syntax OID
dcRectifierIndex
Table index.
Integer32
Constraints:
range: 1-128
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1
dcRectifierIdentifier
Unique rectifier identifier. If positioning active the
position number scheme is used otherwise the rectifier
instance is used to identify a rectifier.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2
dcRectifierSlotState
Specifies state of slots.
Enumeration
Enumerated Values:
1noPos
2empty
3lost
4new
5off
6on
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3
dcRectifierMainStatus
Specifies status of rectifiers.
Enumeration
Enumerated Values:
1unknown
2on
3remoteOff
4off
5temporaryInternalOff
6latchedInternalOff
7error
8notAuthenticated
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.4
dcRectifierConfiguration
Specifies configuration of rectifiers.
Enumeration
Enumerated Values:
1unknown
2ok
3default
4error
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.5
dcRectifierIout
The measured rectifier output current. The max. value 2147483647
is used to indicate an invalid value.
100 mASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.6
dcRectifierPout
The measured rectifier output power. The max. value 2147483647
is used to indicate an invalid value.
WSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.7
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5 · 1 row entry · 15 columns
Table that shows all available rectifier groups.
dcRectifierGroupEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1
A particular rectifier group entry.
Indexes
dcRectifierGroupIndex
Column Syntax OID
dcRectifierGroupIndex
Table index.
Integer32
Constraints:
range: 1-1
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.1
dcRectifierGroupName
Rectifier group name to identify an individual device
parameter set.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.2
dcRectifierGroupRectifierType
Rectifier type defined for this group.
Enumeration
Enumerated Values:
1unknown48V
2fR48V2000W
3dPR1200B48
4dPR1500B48
5dPR600B48
6dPR7200B48
7fR48to60V2000W
8unknown24V
9unknown60V
10dPR600B60
11dPR3500B48
12dPR3500B24
13dPR300B48
14dPR1600B48
15dPR2700B48
16dPR2400B48
17dPR4000B48
18dPR2900B48
19dPR4000B48to60
20dPR850B48
21dPR2000B48
22dPR6000B48A1
23dPR6000B48B1
24dPR4815B
25dPR24100B
26dPR3000
27eSR4856FF
28dPR2900F48A1
29dPR4000B48A5
30dPR6000B48A1forChineseMarket
31dPR2500F48A1
32dPR3000B48
33dPR1000B48
34dPR12000240
35dPR12000336
36dPR3000B48A4
37dPR1800B48A1
38dPR1800B48A2
39dPR6000B48A2
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.3
dcRectifierGroupDefaultVoltage
This default voltage is used by rectifiers when there
is no connection to ORION.
10 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.4
dcRectifierGroupDefaultCurrentLimit
This default current limit is used by rectifiers when there
is no connection to ORION.
100 mASNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.5
dcRectifierGroupDefaultPowerLimit
This default power limit is used by rectifiers when there
is no connection to ORION.
1 WSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.6
dcRectifierGroupInputLowOff
Threshold for low AC input voltage. It can is used to
adjust the behaviour of the power system to the available
AC network limitation.
100 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.7
dcRectifierGroupInputLowOn
For details see dcRectifierGroupInputLowOff.
100 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.8
dcRectifierGroupStartupVoltage
Startup parameters are the values that rectifiers use
during the start-up phase. These parameters allow starting
the system smoothly after a mains failure even on a
discharged battery and even without ORION.
10 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.9
dcRectifierGroupStartupCurrentLimit
For details see dcRectifierGroupStartupVoltage.
100 mASNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.10
dcRectifierGroupStartupPowerLimit
For details see dcRectifierGroupStartupVoltage.
1 WSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.11
dcRectifierGroupStartupLimitTime
For details see dcRectifierGroupStartupVoltage.
10 msSNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.12
dcRectifierGroupPowerupDelay
This parameter is used after a mains failure to
delay the start-up of all rectifiers.
10 msSNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.13
dcRectifierGroupPowerupTime
This parameter used after a mains failure and allows
defining a time within all rectifiers needs to start-up
one after another.
10 msSNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.14
dcRectifierGroupUmaxOff
Overvoltage protection value.
10 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.15
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1 · 1 row entry · 6 columns
Table that shows parameters of the available power limitation
functions.
dcPowerLimitationEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1
A particular power limitation entry.
Indexes
dcPowerLimitationIndex
Column Syntax OID
dcPowerLimitationIndex
Table index.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.1
dcPowerLimitationEventName
Name of the power limitation event.
OctetString
Constraints:
range: 1-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.2
dcPowerLimitationStatus
Status of power limitation.
Enumeration
Enumerated Values:
1disabled
2inactive
3powerLimit
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.3
dcPowerLimitationType
Power limitation type.
Enumeration
Enumerated Values:
1dynamic
2fixedLimit
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.4
dcMaxTotalRectifierPower
Limit used for power limitation.
1 WSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.5
dcPowerLimitationNoBatteryDischarge
Enable/disable no battery discharge during power limitation.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.6
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7 · 1 row entry · 19 columns
Lists all the configured Battery Tests elements.
dcBatteryTestTableEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1
Indexes
dcBatteryTestTableIndex
Column Syntax OID
dcBatteryTestTableIndex
Table index.
Integer32
Constraints:
range: 1-10000
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.1
dcBatteryTestTablePriority
Priority of the battery test. Used as index for this table.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.2
dcBatteryTestTableName
Battery test name.
OctetString
Constraints:
range: 32-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.3
dcBatteryTestTableType
Battery test type used.
Enumerationr/w
Enumerated Values:
1none
2constantCurrent
3realLoad
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.4
dcBatteryTestTableStatus
Current status of battery test.
Enumeration
Enumerated Values:
1inactive
2starting
3stopping
4constantCurrent
5recovery
6realLoad
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.5
dcBatteryTestTableUsupport
Support charge voltage for the battery.
10 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.6
dcBatteryTestTableDuration
Battery test duration. Zero indicates that this value is not set.
minuteSNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.7
dcBatteryTestTableInterval
Minimal time between programmed battery tests as start
condition.
daysSNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.8
dcBatteryTestTableDischargeCurrent
Battery discharge current. The maximum value 2147483647
is used to indicate an invalid value.
100 mASNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.9
dcBatteryTestTableMinDuration
Minimum battery test duration during which time a battery test
is not stopped in case of a voltage below the support voltage or
a current difference higher than the specified value defined in
Idiff measurement is det…
minutesSNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.10
dcBatteryTestTableVoltageWithinUfloat
Battery voltage must be within Ufloat +/- set voltage for a given time (see also dcBatteryTestTableVoltageWithinUfloatPeriod) in order to start a battery test.
10 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.11
dcBatteryTestTableVoltageWithinUfloatPeriod
For details see dcBatteryTestTableVoltageWithinUfloat parameter.
daysSNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.12
dcBatteryTestTableTempFrom
Battery temperature must be within temperature range given by dcBatteryTestTableTempFrom and dcBatteryTestTableTempTo, so that a battery test can be started.
0.1 degreeSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.13
dcBatteryTestTableTempTo
For details see dcBatteryTestTableTempFrom parameter.
0.1 degreeSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.14
dcBatteryTestTableIntervalEnabled
Enable/disable interval. For more details see dcBatteryTestTableInterval.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.15
dcBatteryTestTableStartTimeFrom
Defines start time window for battery test. The possible time window is defined as the range between dcBatteryTestTableStartTimeFrom and dcBatteryTestTableStartTimeTo. The value is in the format 'hh:mm:ss'.
OctetStringr/w
Constraints:
range: 8-8
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.16
dcBatteryTestTableStartTimeTo
For details see dcBatteryTestTableStartTimeFrom.
OctetStringr/w
Constraints:
range: 8-8
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.17
dcBatteryTestTableControl
Manual Start/stop of battery test.
Enumerationr/w
Enumerated Values:
1start
2stop
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.18
dcBatteryTestTableFailureEvent
Reset the battery test failure event.
Enumerationr/w
Enumerated Values:
1reset
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.19
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8 · 1 row entry · 6 columns
Lists the results for all configured Battery Test elements.
dcBatteryTestResultTableEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1
Indexes
dcBatteryTestResultTableIndex
Column Syntax OID
dcBatteryTestResultTableIndex
Table index.
Integer32
Constraints:
range: 1-10000
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.1
dcBatteryTestResultTablePriority
Priority of the battery test. Used as index for this table.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.2
dcBatteryTestResultTableName
Battery test name.
OctetString
Constraints:
range: 32-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.3
dcBatteryTestResultTableDateTime
ISO 8601 representation of the last performed battery test. The value is in the format YYYY-MM-DDThh:mm:ss. This parameter is valid only if there is a test result available.
OctetString
Constraints:
range: 19-19
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.4
dcBatteryTestResultTableResult
Result of last performed battery test.
Enumeration
Enumerated Values:
1none
2failed
3aborted
4loadFailure
5okay
6abortedManual
7abortedEvCtrlCharge
8abortedInhibitEv
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.5
dcBatteryTestResultTableEndVoltage
System voltage at the end of the last performed battery test.
The maximum value 2147483647 is used to indicate an invalid
value.
10 mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.6
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2 · 1 row entry · 4 columns
Table that shows parameters of the available battery strings.
dcBatteryStringEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1
A particular battery string entry.
Indexes
dcBatteryStringIndex
Column Syntax OID
dcBatteryStringIndex
Table index.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.1
dcBatteryStringName
Name of the battery string.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.2
dcBatteryStringMaxIBatt
Maximum battery charging current for this string. This
parameter can be set individually for each battery.
ORION then regulates the system voltage such that the maximum
battery charging current of each battery is res…
100 mASNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.3
dcBatteryStringCapacity
Capacity of battery can be defined individually. It is used
to calculate the expected backup time of the system.
100 mAhSNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.4
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4 · 1 row entry · 8 columns
Table that shows parameters of the available Lithium batteries.
dcBatteryLithiumEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1
A particular Lithium battery entry.
Indexes
dcBatteryLithiumIndex
Column Syntax OID
dcBatteryLithiumIndex
Table index.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.1
dcBatteryLithiumName
Name of the Lithium battery.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.2
dcBatteryLithiumMainState
Lithium Battery Main State.
Enumeration
Enumerated Values:
0invalid
1unknown
2missing
3ok
4warning
5alarm
6error
7remoteOff
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.3
dcBatteryLithiumSubState
Lithium Battery Sub-State.
Enumeration
Enumerated Values:
0invalid
1na
2unknown
3float
4charge
5discharge
6highvoltage
7lowvoltage
8temperature
9highcurrent
10internalfailure
11lowSoC
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.4
dcBatteryLithiumCurrent
Lithium battery current
100 mASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.5
dcBatteryLithiumStateOfCharge
Lithium battery state of charge
%SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.6
dcBatteryLithiumInstallationDate
Installation Date of the Lithium battery.
OctetString
Constraints:
range: 1-11
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.7
dcBatteryLithiumSoH
Lithium battery state of health.
%SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.8
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.5 · 1 row entry · 5 columns
Table that shows parameters of life prediction.
dcBatteryLifePredictionEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.5.1
A particular life prediction entry.
Indexes
dcBatteryLifePredictionIndex
Column Syntax OID
dcBatteryLifePredictionIndex
Table index.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.5.1.1
dcBatteryLifePredictionName
Name of the battery.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.5.1.2
dcBatteryLifePredictionRemainingDays
Remaining days of battery.
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.5.1.3
dcBatteryLifePredictionInstallationDate
Installation date of battery.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.5.1.4
dcBatteryLifePredictionSoH
Battery state of health.
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.5.1.5
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4 · 1 row entry · 9 columns
Lists all the configured Event Controlled Charges elements.
dcEventControlledChargeTableEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1
Indexes
dcEventControlledChargeTableIndex
Column Syntax OID
dcEventControlledChargeTableIndex
Table index.
Integer32
Constraints:
range: 1-10000
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.1
dcEventControlledChargeTablePriority
Priority of the event controlled charge instance. Used as index for this table.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.2
dcEventControlledChargeTableName
Event control charge name.
OctetString
Constraints:
range: 32-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.3
dcEventControlledChargeTableActivationInput
Event used to activate the controlled charge.
OctetString
Constraints:
range: 32-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.4
dcEventControlledChargeTableStatus
Event control charge current status.
Enumeration
Enumerated Values:
1inactive
2voltageControlled
3noBatteryCharge
4currentLimitation
5suppressed
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.5
dcEventControlledChargeTableType
Selected event control charge type.
Enumerationr/w
Enumerated Values:
1voltageControlled
2noBatteryCharge
3currentLimitation
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.6
dcEventControlledChargeTableVoltage
Voltage used for event control charge.
10mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.7
dcEventControlledChargeTableMaxIBatt
Max. IBatt used for event control charge.
100mASNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.8
dcEventControlledChargeTableTempCompEnabled
Enable/disable temperature compensation during event control charge.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.9
.1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1 · 1 row entry · 4 columns
Table that shows ten output event assignments that can be 
configured via WEB interface.
dcControlEventEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1
A particular generic output entry.
Indexes
dcControlEventIndex
Column Syntax OID
dcControlEventIndex
Table index.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1
dcControlEventName
Plain text name of the assigned control event. Empty if not
configure.
OctetString
Constraints:
range: 0-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2
dcControlEventIdentifier
Unique numeric identifier of the assigned control event. Zero
if not configured.
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3
dcControlEventValue
Current value of the assigned control event. Value is false if
not configured.
Enumerationr/w
Enumerated Values:
1false
2true
.1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4
.1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1 · 1 row entry · 4 columns
Trap table that shows all configured trap destinations.
dcTrapDestinationEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1
A particular trap destination entry.
Indexes
dcTrapDestinationIndex
Column Syntax OID
dcTrapDestinationIndex obsolete
Table index.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1
dcTrapDestinationIp obsolete
IP address of the trap destination. Value is 0.0.0.0 if IP
address is not configured.
SNMPv2-SMIIpAddressr/w
Textual Convention: SNMPv2-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2
dcTrapDestinationPort obsolete
Port number of the trap destination. By default port 162
is used.
SNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3
dcTrapDestinationUser obsolete
User of the trap destination.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.4
.1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6 · 1 row entry · 4 columns
Trap table that shows all configured trap destinations.
dcTrapDestinationv2Entry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6.1
A specific trap destination entry.
Indexes
dcTrapDestinationv2Index
Column Syntax OID
dcTrapDestinationv2Index
Table index.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6.1.1
dcTrapDestinationv2
Address of the trap destination.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6.1.2
dcTrapDestinationv2Port
Port number of the trap destination.
SNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6.1.3
dcTrapDestinationv2User
User of the trap destination.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6.1.4
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1 · 1 row entry · 3 columns
Event config table for default log.
dcDefaultLogEventEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1
A particular event entry.
Indexes
dcDefaultLogEventIndex
Column Syntax OID
dcDefaultLogEventIndex
Table index.
Integer32
Constraints:
range: 0-1000
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.1
dcDefaultLogEventName
Plain text name of the event that can be logged.
OctetString
Constraints:
range: 1-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.2
dcDefaultLogEventLogged
If yes then this event is logged otherwise not.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.3
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2 · 1 row entry · 4 columns
Event config table for event ORs.
dcEventProcessingEventEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1
A particular event entry.
Indexes
dcEventProcessingEventIndex
Column Syntax OID
dcEventProcessingEventIndex
Table index.
Integer32
Constraints:
range: 0-1000
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.1
dcEventProcessingEventName
Plain text name of the input event.
OctetString
Constraints:
range: 1-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.2
dcEventProcessingEventAssigned
If yes then the input event is assigned to the selected
event. Please note, that it is only possible to change
assignment of event ORs.
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.3
dcEventProcessingEventType
Type of the input event.
Enumeration
Enumerated Values:
1unknown
2eventOR
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.4
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4 · 1 row entry · 8 columns
Table lists all available LVDs.
dcLvdEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1
A particular LVD entry.
Indexes
dcLvdIndex
Column Syntax OID
dcLvdIndex
Table index.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.1
dcLvdName
Name of the LVD.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.2
dcLvdDisconnectDelay
Time delay from the activation of the source event, after
which the LVD event is switched. The value is in the format
'hh:mm:ss'.
OctetStringr/w
Constraints:
range: 8-8
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.3
dcLvdType
Type of the LVD.
Enumeration
Enumerated Values:
1eventControlled
2utControlled
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.4
dcLvdVoltageThreshold
Voltage threshold for U and t controlled type LVD. Only available in U and t Controlled Type LVDs.
10 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.5
dcLvdVoltageHysteresis
Voltage Hysteresis for U and t controlled type LVD. Only available in U and t Controlled Type LVDs.
10 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.6
dcLvdControlEvent
Control (previously named Source) Event for the LVD action. Only available in Event Controlled Type LVDs.
OctetString
Constraints:
range: 0-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.7
dcLvdMonitoringEvent
Monitoring Event. Only available in Event Controlled Type LVDs.
OctetString
Constraints:
range: 0-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.8
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5 · 1 row entry · 5 columns
Table that shows twenty threshold event assignments that can be 
configured via WEB interface.
dcEventDefinitionEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1
A particular generic EventDefinition entry.
Indexes
dcEventIndex
Column Syntax OID
dcEventIndex
Table index.
Integer32
Constraints:
range: 1-20
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.1
dcEventName
Name of the threshold.
OctetString
Constraints:
range: 0-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.2
dcThreshold
Value of the threshold.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.3
dcThresholdHysteresis
Hysteresis of the threshold.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.4
dcUnit
Unit of the threshold
Enumeration
Enumerated Values:
1unitUnknown
2unitNone
3unit10mVdc
4unit10mVac
5unit100mA
6unit100mAh
7unit100mDegree
8unit100mDegreeCoefficient
9unitWatt
10unitWattHour
11unitKilowattHour
12unitSeconds
13unitPercent
14unitHertz
15unitVoltAmpere
16unitVoltAmpereReactive
17unitVoltAmpereReactiveHour
18unitVoltAmpereHour
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.5
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.6 · 1 row entry · 4 columns
Table that shows twenty filter event assignments that can be 
configured via WEB interface.
dcFilterEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.8.6.1
A particular generic Filter entry.
Indexes
dcFilterIndex
Column Syntax OID
dcFilterIndex
Table index.
Integer32
Constraints:
range: 1-20
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.6.1.1
dcFilterName
Name of the Filter.
OctetString
Constraints:
range: 0-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.6.1.2
dcTrueForMin
True for Min.
OctetStringr/w
Constraints:
range: 0-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.6.1.3
dcFalseForMin
False for Min.
OctetStringr/w
Constraints:
range: 0-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.6.1.4
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7 · 1 row entry · 18 columns
Table that shows twenty timer event assignments that can be 
configured via WEB interface.
dcTimerEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1
A particular generic Timer entry.
Indexes
dcTimerIndex
Column Syntax OID
dcTimerIndex
Table index.
Integer32
Constraints:
range: 1-20
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.1
dcTimerName
Name of the Timer.
OctetString
Constraints:
range: 0-35
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.2
dcStartTime
Start Time(hh:mm).
OctetStringr/w
Constraints:
range: 0-10
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.3
dcStartDaySu
Is Sunday Start Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.4
dcStartDayMo
Is Monday Start Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.5
dcStartDayTu
Is Tuesday Start Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.6
dcStartDayWe
Is Wednesday Start Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.7
dcStartDayTh
Is Thursday Start Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.8
dcStartDayFr
Is Friday Start Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.9
dcStartDaySa
Is Saturday Start Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.10
dcEndTime
End Time(hh:mm).
OctetStringr/w
Constraints:
range: 0-10
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.11
dcEndDaySu
Is Sunday End Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.12
dcEndDayMo
Is Monday End Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.13
dcEndDayTu
Is Tuesday End Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.14
dcEndDayWe
Is Wednesday End Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.15
dcEndDayTh
Is Thursday End Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.16
dcEndDayFr
Is Friday End Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.17
dcEndDaySa
Is Saturday End Day?
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.18
.1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1 · 1 row entry · 5 columns
Table lists all available measurements.
dcMeasurementEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1
A particular measurement entry.
Indexes
dcMeasurementIndex
Column Syntax OID
dcMeasurementIndex
Table index.
Integer32
Constraints:
range: 1-500
.1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.1
dcMeasurementName
Name of the measurement.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.2
dcMeasurementValue
Unscaled calibrated value of the measurement.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.3
dcMeasurementScaleFactor
Scale factor as power of 10 to be multiplied with measurement value.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.4
dcMeasurementUnit
Unit of the measurement.
Enumeration
Enumerated Values:
1unknown
2none
3voltDC
4voltAC
5ampere
6ampereHour
7temperature
8temperatureCoefficient
9watt
10wattHour
11seconds
12percent
13hertz
14voltAmpere
15voltAmpereReactive
16voltAmpereReactiveHour
17voltAmpereHour
.1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.5
.1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1 · 1 row entry · 4 columns
Table lists all available meter panel events.
dcMeterPanelEventEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1
A particular meter panel event entry.
Indexes
dcMeterPanelEventIndex
Column Syntax OID
dcMeterPanelEventIndex
Table index.
Integer32
Constraints:
range: 1-128
.1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.1
dcMeterPanelEventName
Name of the event.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.2
dcMeterPanelEventValue
Value of the event.
Enumeration
Enumerated Values:
1false
2indeterminate
3true
.1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.3
dcMeterPanelEventHourMeterValue
Value of the hour meter event.
secondsSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.4
.1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2 · 1 row entry · 4 columns
Table lists all available meter panel Measurements.
dcMeterPanelMeasurementEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2.1
A particular meter panel Measurement entry.
Indexes
dcMeterPanelMeasurementIndex
Column Syntax OID
dcMeterPanelMeasurementIndex
Table index.
Integer32
Constraints:
range: 1-128
.1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2.1.1
dcMeterPanelMeasurementName
Name of the Measurement.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2.1.2
dcMeterPanelMeasurementValue
Value of the Measurement.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2.1.3
dcMeterPanelMeasurementUnit
Unit of the measurement.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2.1.4
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4 · 1 row entry · 10 columns
Table that shows all currently active PVC modules.
dcPVCEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1
A particular PVC entry.
Indexes
dcPVCIndex
Column Syntax OID
dcPVCIndex
Table index.
Integer32
Constraints:
range: 1-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.1
dcPVCIdentifier
Unique PVC identifier. If positioning active the
position number scheme is used otherwise the PVC
instance is used to identify a PVC.
OctetString
Constraints:
range: 1-16
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.2
dcPVCSlotState
Specifies state of slots.
Enumeration
Enumerated Values:
1noPos
2empty
3lost
4new
5off
6on
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.3
dcPVCMainStatus
Specifies status of PVCs.
Enumeration
Enumerated Values:
1unknown
2on
3remoteOff
4off
5temporaryInternalOff
6latchedInternalOff
7error
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.4
dcPVCSubStatus
Specifies sub-status of PVCs.
Enumeration
Enumerated Values:
1unknown
2notAvailable
3mppt
4voltageMode
5outputCurrentLimit
6outputPowerLimit
7inputCurrentLimit
8inputPowerLimit
9inputVoltageOutsideRange
10sunset
11breakerOpen
12startUpDelay
13otp
14ovp
15fanFailure
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.5
dcPVCConfiguration
Specifies configuration of PVCs.
Enumeration
Enumerated Values:
1unknown
2ok
3default
4outsideLimts
5invalid
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.6
dcPVCIout
The measured PVC output current. The max. value 2147483647
is used to indicate an invalid value.
100 mASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.7
dcPVCUout
The measured PVC output voltage. The max. value 2147483647
is used to indicate an invalid value.
10 mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.8
dcPVCIin
The measured PVC input current. The max. value 2147483647
is used to indicate an invalid value.
100 mASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.9
dcPVCUin
The measured PVC input voltage. The max. value 2147483647
is used to indicate an invalid value.
100 mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.10
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5 · 1 row entry · 9 columns
Table that shows all available PVC groups.
dcPVCGroupEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1
A particular PVC group entry.
Indexes
dcPVCGroupIndex
Column Syntax OID
dcPVCGroupIndex
Table index.
Integer32
Constraints:
range: 1-1
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.1
dcPVCGroupPVCType
PVC type defined for this group.
Enumeration
Enumerated Values:
1unknown48V
2pvc2200B48
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.2
dcPVCGroupVoltage
This default voltage is used by PVCs when there
is no connection to ORION.
10 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.3
dcPVCGroupVPGM
This is offset voltage used by PVCs.
10 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.4
dcPVCGroupInputLowOff
Threshold for low input voltage.
100 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.5
dcPVCGroupInputLowOn
Threshold for low input voltage.
100 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.6
dcPVCGroupStartUpDelay
This parameter is power up time of PVC that can be defined.
secondsSNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.7
dcPVCGroupOvpLimit
This voltage defines the maximum allowed DC-voltage.
10 mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.8
dcPVCGroupAlarmDelay
This parameter can be used for suppressing alarms during night time.
secondsSNMPv2-SMIGauge32r/w
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.9
.1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1 · 1 row entry · 8 columns
Controller's inventory table that shows all inventory information.
dcInventoryEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1
A particular inventory entry.
Indexes
dcInventoryIndex
Column Syntax OID
dcInventoryIndex
Table index.
Integer32
Constraints:
range: 1-10000
.1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.1
dcInventoryType
Module type
OctetString
Constraints:
range: 1-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.2
dcInventoryName
Module name
OctetString
Constraints:
range: 1-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.3
dcInventorySwVersion
Module software vision
OctetString
Constraints:
range: 1-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.4
dcInventoryBuildVersion
Module software build vision
OctetString
Constraints:
range: 1-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.5
dcInventoryPartNb
Module part number
OctetString
Constraints:
range: 1-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.6
dcInventorySerialNb
Module serial number
OctetString
Constraints:
range: 1-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.7
dcInventoryTopLevel
Module top level
OctetString
Constraints:
range: 1-32
.1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.8
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1 · 1 row entry · 17 columns
Aircon table that shows all Aircon and cooling plan information.
dcAirconEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1
A particular Aircon entry.
Indexes
dcAirconIndex dcCoolingPlanIndex
Column Syntax OID
dcAirconIndex
Table index.
Integer32
Constraints:
range: 1-10000
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.1
dcCoolingPlanIndex
Cooling plan index
Integer32
Constraints:
range: 1-10000
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.2
dcAirconName
Aircon module name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.3
dcAirconMainStatus
Aircon module main status
Enumeration
Enumerated Values:
1unknown
2on
3remoteOff
4standby
5warning
6temporaryInternalOff
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.4
dcAirconSubStatus
Aircon module sub status
Enumeration
Enumerated Values:
1na
2unknown
3cooling
4silentCooling
5selfTest
6heating
7targetTemperatureReached
8localOff
9forceVentilation
10systemProtection
11temperatureAbnormal
12temperatureSensorFault
13fanFault
14controlDeviceFault
15environmentalAbnormalAlarm
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.5
dcAirconConfiguration
Module configuration status
Enumeration
Enumerated Values:
1ok
2default
3outsideLimit
4invalid
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.6
dcAirconPlanName
The name of cooling plan
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.7
dcAirconRoomTemp
Room temperature
0.1 degreeSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.8
dcCoolingPlanActivationInput
The input event for activate cooling plan
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.9
dcCoolingPlanPriority
Cooling plan priority
Enumeration
Enumerated Values:
1priority1
2priority2
3priority3
4priority4
5priority5
6lowest
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.10
dcCoolingPlanStatus
Cooling plan status
Enumeration
Enumerated Values:
1inactive
2active
3suppressed
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.11
dcCoolingPlanTargetTemp
Cooling plan target temperature. The range is 25°C ... 40°C(77°F ... 104°F).
0.1 degreeInteger32r/w
Constraints:
range: 250-1040
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.12
dcCoolingPlanOperatingMode
Cooling plan operating mode
Enumerationr/w
Enumerated Values:
1normal
2silent
3off
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.13
dcCoolingPlanStandbyFanSpeed
Cooling plan standby fan speed
Enumerationr/w
Enumerated Values:
2low
3high
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.14
dcCoolingPlanHeaterStartTemp
Cooling plan heater start temperature. The range is -10°C ... 15°C(14°F ... 59°F).
0.1 degreeInteger32r/w
Constraints:
range: -100-590
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.15
dcCoolingPlanHeaterHyst
Cooling plan heater start temperature hysteresis. The range is 1°C ... 10°C(1.8°F ... 18°F).
0.1 degreeInteger32r/w
Constraints:
range: 10-180
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.16
dcCoolingPlanHeaterControl
Cooling plan heater control mode
Enumerationr/w
Enumerated Values:
1auto
2manual
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.17
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1 · 1 row entry · 22 columns
Table that shows all available Inverter groups.
dcInverterGroupEntry entry .1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1
A particular Inverter group entry.
Indexes
dcInverterGroupIndex
Column Syntax OID
dcInverterGroupIndex
Table index.
Integer32
Constraints:
range: 1-1
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.1
dcInverterGroupState
This is the alarm state of the inverter system.
Enumeration
Enumerated Values:
1invalid
2noAlarm
3nonUrgentAlarm
4urgentAlarm
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.2
dcInverterGroupLoadPosition
Shows where is the load positioned in the system.
Enumeration
Enumerated Values:
1invalid
2ac
3dc
4mixed
5unknown
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.3
dcInverterGroupNbrOfConfigInverters
The system is configure to operate this number of inverters at maximum.
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.4
dcInverterGroupNbrOfPresentInverters
Number of inverters actually present in the system.
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.5
dcInverterGroupPhase
This is the alarm state of the inverter system.
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.6
dcInverterGroupDcVoltage
Input DC voltage
10 mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.7
dcInverterGroupInputDcPower
Input DC Power
1 WSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.8
dcInverterGroupInputVoltage1
Input voltage line 1
100 mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.9
dcInverterGroupInputVoltage2
Input voltage line 2 - in three phase system only
100 mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.10
dcInverterGroupInputVoltage3
Input voltage line 3 - in three phase system only
100 mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.11
dcInverterGroupInputApparentPower1
Input power line 1
1 VASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.12
dcInverterGroupInputApparentPower2
Input power line 2 - in three phase system only
1 VASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.13
dcInverterGroupInputApparentPower3
Input power line 3 - in three phase system only
1 VASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.14
dcInverterGroupInputFrequency
Input frequency
10 mHzSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.15
dcInverterGroupOutputVoltage1
Output voltage line 1
100 mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.16
dcInverterGroupOutputVoltage2
Output voltage line 2 - in three phase system only
100 mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.17
dcInverterGroupOutputVoltage3
Output voltage line 3 - in three phase system only
100 mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.18
dcInverterGroupOutputApparentPower1
Output apparent power line 1
1 VASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.19
dcInverterGroupOutputApparentPower2
Output apparent power line 2 - in three phase system only
1 VASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.20
dcInverterGroupOutputApparentPower3
Output apparent power line 3 - in three phase system only
1 VASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.21
dcInverterGroupOutputFrequency
Output frequency
10 mHzSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.22