dcAirconSubStatus
ORION-BASE-MIB ·
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.5
Object
column
Enumeration
Aircon module sub status
Context
- MIB
- ORION-BASE-MIB
- OID
.1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.5- Type
- column
- Access
- readonly
- Status
- current
- Parent
- dcAirconEntry
- Table
- dcAirconTable
- Siblings
- 16
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | na |
2 | unknown |
3 | cooling |
4 | silentCooling |
5 | selfTest |
6 | heating |
7 | targetTemperatureReached |
8 | localOff |
9 | forceVentilation |
10 | systemProtection |
11 | temperatureAbnormal |
12 | temperatureSensorFault |
13 | fanFault |
14 | controlDeviceFault |
15 | environmentalAbnormalAlarm |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dcAirconIndex Table index. | column | Integer32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.1 |
| dcCoolingPlanPriority Cooling plan priority | column | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.10 |
| dcCoolingPlanStatus Cooling plan status | column | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.11 |
| dcCoolingPlanTargetTemp Cooling plan target temperature. The range is 25°C ... 40°C(77°F ... 104°F). | column | 0.1 degree Integer32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.12 |
| dcCoolingPlanOperatingMode Cooling plan operating mode | column | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.13 |
| dcCoolingPlanStandbyFanSpeed Cooling plan standby fan speed | column | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.14 |
| dcCoolingPlanHeaterStartTemp Cooling plan heater start temperature. The range is -10°C ... 15°C(14°F ... 59°F). | column | 0.1 degree Integer32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.15 |
| dcCoolingPlanHeaterHyst Cooling plan heater start temperature hysteresis. The range is 1°C ... 10°C(1.8°F ... 18°F). | column | 0.1 degree Integer32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.16 |
| dcCoolingPlanHeaterControl Cooling plan heater control mode | column | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.17 |
| dcCoolingPlanIndex Cooling plan index | column | Integer32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.2 |
| dcAirconName Aircon module name | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.3 |
| dcAirconMainStatus Aircon module main status | column | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.4 |
| dcAirconConfiguration Module configuration status | column | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.6 |
| dcAirconPlanName The name of cooling plan | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.7 |
| dcAirconRoomTemp Room temperature | column | 0.1 degree SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.8 |
| dcCoolingPlanActivationInput The input event for activate cooling plan | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.9 |