POWER-ATTRIBUTES-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
3
Rows
3
Columns
24
.1.3.6.1.2.1.230.1.1 · 1 row entry · 12 columns
This table contains power attributes measurements for
supported entPhysicalIndex entities.  It is a sparse
extension of the eoPowerTable.
eoACPwrAttributesEntry entry .1.3.6.1.2.1.230.1.1.1
This is a sparse extension of the eoPowerTable with
entries for power attributes measurements or
configuration. Each measured value corresponds to an
attribute in IEC 61850-7-4 for non-phase measurements
within the obj…
Indexes
ENTITY-MIBentPhysicalIndex
Column Syntax OID
eoACPwrAttributesConfiguration
Configuration describes the physical configurations of
the power supply lines:

* alternating current, single phase (SNGL)
* alternating current, three-phase delta (DEL)
* alternating current, thr…
Enumeration
Enumerated Values:
1sngl
2del
3wye
.1.3.6.1.2.1.230.1.1.1.1
eoACPwrAttributesAvgVoltage
A measured value for average of the voltage measured
over an integral number of AC cycles. For a three-phase
system, this is the average voltage (V1+V2+V3)/3. IEC
61850-7-4 measured value attribute 'Vol'.
0.1 Volt ACSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.2.1.230.1.1.1.2
eoACPwrAttributesAvgCurrent
A measured value for average of the current measured
over an integral number of AC cycles. For a three-phase
system, this is the average current (I1+I2+I3)/3. IEC
61850-7-4 attribute 'Amp'.
amperesSNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.2.1.230.1.1.1.3
eoACPwrAttributesFrequency
A measured value for the basic frequency of the AC
circuit. IEC 61850-7-4 attribute 'Hz'.
0.01 hertzInteger32
Constraints:
range: 4500-6500
.1.3.6.1.2.1.230.1.1.1.4
eoACPwrAttributesPowerUnitMultiplier
The magnitude of watts for the usage value in
eoACPwrAttributesTotalActivePower,
eoACPwrAttributesTotalReactivePower,
and eoACPwrAttributesTotalApparentPower measurements.
For three-phase power systems, this will also i…
ENERGY-OBJECT-MIBUnitMultiplier
Textual Convention: ENERGY-OBJECT-MIBUnitMultiplier Enumeration
Type Values:
-24yocto
-21zepto
-18atto
-15femto
-12pico
-9nano
-6micro
-3milli
0units
3kilo
6mega
9giga
12tera
15peta
18exa
21zetta
24yotta
.1.3.6.1.2.1.230.1.1.1.5
eoACPwrAttributesPowerAccuracy
This object indicates a percentage value, in hundredths of a
percent, representing the presumed accuracy of active,
reactive, and apparent power usage reporting. For
example, 1010 means the reported usage is accurate t…
hundredths of percentInteger32
Constraints:
range: 0-10000
.1.3.6.1.2.1.230.1.1.1.6
eoACPwrAttributesTotalActivePower
A measured value of the actual power delivered to or
consumed by the load. IEC 61850-7-4 attribute 'TotW'.
wattsSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.2.1.230.1.1.1.7
eoACPwrAttributesTotalReactivePower
A measured value of the reactive portion of the apparent
power. IEC 61850-7-4 attribute 'TotVAr'.
volt-amperes reactiveSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.2.1.230.1.1.1.8
eoACPwrAttributesTotalApparentPower
A measured value of the voltage and current that
determines the apparent power. The apparent power is the
vector sum of real and reactive power.

Note: watts and volt-amperes are equivalent units and may
volt-amperesSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.2.1.230.1.1.1.9
eoACPwrAttributesTotalPowerFactor
A measured value ratio of the real power flowing to the
load versus the apparent power. It is dimensionless and
expressed here as a percentage value in hundredths. A power
factor of 100% indicates there is no inductan…
hundredthsInteger32
Constraints:
range: -10000-10000
.1.3.6.1.2.1.230.1.1.1.10
eoACPwrAttributesThdCurrent
A calculated value for the current total harmonic
distortion (THD). Method of calculation is not
specified. IEC 61850-7-4 attribute 'ThdAmp'.
hundredths of percentInteger32
Constraints:
range: 0-10000
.1.3.6.1.2.1.230.1.1.1.11
eoACPwrAttributesThdVoltage
A calculated value for the voltage total harmonic
distortion (THD). The method of calculation is not
specified. IEC 61850-7-4 attribute 'ThdVol'.
hundredths of percentInteger32
Constraints:
range: 0-10000
.1.3.6.1.2.1.230.1.1.1.12
.1.3.6.1.2.1.230.1.2 · 1 row entry · 3 columns
This optional table describes three-phase power attributes
measurements in a DEL configuration with phase-to-phase
          
power attributes measurements.  Entities having single
phase power shall not have any entities.  This is a
sparse extension of the eoACPwrAttributesTable.
          
These attributes correspond to measurements related to
the IEC 61850-7.4 MMXU phase and measured harmonic or
interharmonics related to the MHAI phase.
eoACPwrAttributesDelPhaseEntry entry .1.3.6.1.2.1.230.1.2.1
An entry describes power measurements of a phase in a
DEL three-phase power. Three entries are required for each
supported entPhysicalIndex entry. Voltage measurements
are provided relative to each other.
Indexes
ENTITY-MIBentPhysicalIndex eoACPwrAttributesDelPhaseIndex
Column Syntax OID
eoACPwrAttributesDelPhaseIndex
A phase angle typically corresponding to 0, 120, 240.
Integer32
Constraints:
range: 0-359
.1.3.6.1.2.1.230.1.2.1.1
eoACPwrAttributesDelPhaseToNextPhaseVoltage
A measured value of phase to next phase voltages, where
the next phase is IEC 61850-7-4 attribute 'PPV'.
0.1 Volt ACSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.2.1.230.1.2.1.2
eoACPwrAttributesDelThdPhaseToNextPhaseVoltage
A calculated value for the voltage total harmonic
distortion for phase to next phase. Method of calculation
is not specified. IEC 61850-7-4 attribute 'ThdPPV'.
hundredths of percentInteger32
Constraints:
range: 0-10000
.1.3.6.1.2.1.230.1.2.1.3
.1.3.6.1.2.1.230.1.3 · 1 row entry · 9 columns
This optional table describes three-phase power attributes
measurements in a WYE configuration with phase-to-neutral
power attributes measurements.  Entities having single
phase power shall not have any entities.  This is a sparse
extension of the eoACPwrAttributesTable.
          
These attributes correspond to measurements related to
the IEC 61850-7.4 MMXU phase and measured harmonic or
interharmonics related to the MHAI phase.
eoACPwrAttributesWyePhaseEntry entry .1.3.6.1.2.1.230.1.3.1
This table describes measurements of a phase in a WYE
three-phase power system. Three entries are required for
each supported entPhysicalIndex entry. Voltage
measurements are relative to neutral.

Each ent…
Indexes
ENTITY-MIBentPhysicalIndex eoACPwrAttributesWyePhaseIndex
Column Syntax OID
eoACPwrAttributesWyePhaseIndex
A phase angle typically corresponding to 0, 120, 240.
Integer32
Constraints:
range: 0-359
.1.3.6.1.2.1.230.1.3.1.1
eoACPwrAttributesWyePhaseToNeutralVoltage
A measured value of phase to neutral voltage. IEC
61850-7-4 attribute 'PNV'.
0.1 Volt ACSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.2.1.230.1.3.1.2
eoACPwrAttributesWyeCurrent
A measured value of phase currents. IEC 61850-7-4
attribute 'A'.
0.1 amperes ACSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.2.1.230.1.3.1.3
eoACPwrAttributesWyeActivePower
A measured value of the actual power delivered to or
consumed by the load with the magnitude indicated
separately in eoPowerUnitMultiplier. IEC 61850-7-4
attribute 'W'.
wattsSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.2.1.230.1.3.1.4
eoACPwrAttributesWyeReactivePower
A measured value of the reactive portion of the apparent
power with the magnitude of indicated separately in
eoPowerUnitMultiplier. IEC 61850-7-4 attribute 'VAr'.
volt-amperes reactiveSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.2.1.230.1.3.1.5
eoACPwrAttributesWyeApparentPower
A measured value of the voltage and current determines
the apparent power with the indicated separately in
eoPowerUnitMultiplier. Active plus reactive power equals
the total apparent power.

Note: Watts a…
volt-amperesSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.2.1.230.1.3.1.6
eoACPwrAttributesWyePowerFactor
A measured value ratio of the real power flowing to the
load versus the apparent power for this phase. IEC
61850-7-4 attribute 'PF'. Power Factor can be positive or
negative where the sign should be in lead/lag (IEEE)…
hundredthsInteger32
Constraints:
range: -10000-10000
.1.3.6.1.2.1.230.1.3.1.7
eoACPwrAttributesWyeThdCurrent
A calculated value for the voltage total harmonic
distortion (THD) for phase to phase. Method of
calculation is not specified.
IEC 61850-7-4 attribute 'ThdA'.
hundredths of percentInteger32
Constraints:
range: 0-10000
.1.3.6.1.2.1.230.1.3.1.8
eoACPwrAttributesWyeThdPhaseToNeutralVoltage
A calculated value of the voltage total harmonic
distortion (THD) for phase to neutral. IEC 61850-7-4
attribute 'ThdPhV'.
hundredths of percentInteger32
Constraints:
range: 0-10000
.1.3.6.1.2.1.230.1.3.1.9