Sentry3-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
7
Rows
7
Columns
101
.1.3.6.1.4.1.1718.3.2.1 · 1 row entry · 15 columns
A table of towers.
towerEntry entry .1.3.6.1.4.1.1718.3.2.1.1
Row definition for the tower table.
Indexes
towerIndex
Column Syntax OID
towerIndex
Index for the tower table.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.3.2.1.1.1
towerID
The ID of the tower.
OctetString
Constraints:
range: 1-1
.1.3.6.1.4.1.1718.3.2.1.1.2
towerName
The name of the tower.
OctetStringr/w
Constraints:
range: 0-24
.1.3.6.1.4.1.1718.3.2.1.1.3
towerStatus
The operational status of the tower.
Enumeration
Enumerated Values:
0normal
1noComm
2fanFail
3overTemp
4nvmFail
5outOfBalance
Constraints:
range: 4-4
.1.3.6.1.4.1.1718.3.2.1.1.4
towerInfeedCount
The number of input feeds on the tower.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.3.2.1.1.5
towerProductSN
The product serial number of the tower.
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.1718.3.2.1.1.6
towerModelNumber
The model number of the tower.
OctetString
Constraints:
range: 0-24
.1.3.6.1.4.1.1718.3.2.1.1.7
towerCapabilities
The capabilities of the tower.
Bits
Enumerated Values:
0failSafe
1fuseSense
2directCurrent
3threePhase
4fanSense
5tempSense
.1.3.6.1.4.1.1718.3.2.1.1.8
towerVACapacity
The total apparent power capacity of the tower circuit.
A non-negative value indicates the maximum total apparent
power in Volt-Amps. A negative value indicates that the
total apparent power capacity was not available.
Volt-AmpsInteger32
Constraints:
range: -1-50000
.1.3.6.1.4.1.1718.3.2.1.1.9
towerVACapacityUsed
The used percentage of the tower circuit total apparent power
capacity (towerApparentPower / towerVACapacity x 100). A
non-negative value indicates the percentage of capacity used
in tenths. A negative value indicates…
tenth percentageInteger32
Constraints:
range: -1-1500
.1.3.6.1.4.1.1718.3.2.1.1.10
towerActivePower
The total active power consumption of the tower circuit.
A non-negative value indicates the total active power
consumption in Watts. A negative value indicates that the
total active power consumption was not available.
WattsInteger32
Constraints:
range: -1-50000
.1.3.6.1.4.1.1718.3.2.1.1.11
towerApparentPower
The total apparent power consumption of the tower circuit.
A non-negative value indicates the total apparent power
consumption in Volt-Amps. A negative value indicates that
the total apparent power consumption was not …
Volt-AmpsInteger32
Constraints:
range: -1-50000
range: 0-255
.1.3.6.1.4.1.1718.3.2.1.1.12
towerPowerFactor
The overall power factor of the tower circuit. A non-
negative value indicates the overall power factor in
hundredths. A negative value indicates that the overall
power factor was not able to be measured.
hundredthsInteger32
Constraints:
range: -1-100
range: 0-255
.1.3.6.1.4.1.1718.3.2.1.1.13
towerEnergy
The total energy consumption of the tower circuit. A non-
negative value indicates the total energy consumption in
Kilowatt-Hours. A negative value indicates that the total
energy consumption was not available.
Kilowatt-HoursInteger32
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.1718.3.2.1.1.14
towerLineFrequency
The frequency of the input feed line voltage. A non-
negative value indicates the frequency in Hertz. A negative
value indicates that the frequency was not available.
HertzInteger32
Constraints:
range: -1-60
.1.3.6.1.4.1.1718.3.2.1.1.15
.1.3.6.1.4.1.1718.3.2.2 · 1 row entry · 25 columns
A table of input feeds.
infeedEntry entry .1.3.6.1.4.1.1718.3.2.2.1
Row definition for the input feed table.
Indexes
towerIndex infeedIndex
Column Syntax OID
infeedIndex
Index for the input feed table.
Integer32
Constraints:
range: 0-4
range: 0-16777215
.1.3.6.1.4.1.1718.3.2.2.1.1
infeedID
The ID of the input feed.
OctetString
Constraints:
range: 2-2
range: 0-255
.1.3.6.1.4.1.1718.3.2.2.1.2
infeedName
The name of the input feed.
OctetStringr/w
Constraints:
range: 0-24
.1.3.6.1.4.1.1718.3.2.2.1.3
infeedCapabilities
The capabilities of the input feed.
Bits
Enumerated Values:
0onSense
1loadSense
2powerControl
3failSafe
4defaultOff
5voltageSense
6powerSense
7branchOnSense
8branchLoadSense
Constraints:
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.4
infeedStatus
The status of the input feed line. If the infeedCapabilities
'onSense' bit is TRUE, then all of the states are supported
and indicate the sensed state of the input feed. If the
infeedCapabilities 'onSense' bit is FALS…
Enumeration
Enumerated Values:
0off
1on
2offWait
3onWait
4offError
5onError
6noComm
7reading
8offFuse
9onFuse
Constraints:
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.5
infeedLoadStatus
The status of the load measured on the input feed line. If
the infeedCapabilities 'loadSense' bit is TRUE, then all of
the states are supported. If the infeedCapabilities
'loadSense' bit is FALSE, then only the 'norma…
Enumeration
Enumerated Values:
0normal
1notOn
2reading
3loadLow
4loadHigh
5overLoad
6readError
7noComm
Constraints:
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.6
infeedLoadValue
The load measured on the input feed line. A non-negative
value indicates the measured load in hundredths of Amps. A
negative value indicates that a load value was not able to
be measured.
hundredth AmpsInteger32
Constraints:
range: -1-60000
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.7
infeedLoadHighThresh
The load high threshold value of the input feed line in Amps.
AmpsInteger32r/w
Constraints:
range: 0-600
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.8
infeedOutletCount
The number of controlled and/or monitored outlets on the
input feed.
Integer32
Constraints:
range: 0-64
range: 0-16777215
.1.3.6.1.4.1.1718.3.2.2.1.9
infeedCapacity
The load capacity of the input feed line. A non-negative
value indicates the maximum load in Amps. A negative
value indicates that the capacity was not available.
AmpsInteger32
Constraints:
range: -1-600
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.10
infeedVoltage
The line-to-line voltage of the input feed. A non-negative
value indicates the voltage in tenths of Volts. A negative
value indicates that the voltage was not available.
tenth VoltsInteger32
Constraints:
range: -1-4800
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.11
infeedPower
The active power consumption of the input feed phase. A non-
negative value indicates the active power consumption in
Watts. A negative value indicates that the active power
consumption was not available.
WattsInteger32
Constraints:
range: -1-25000
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.12
infeedApparentPower
The apparent power consumption of the input feed phase. A
non-negative value indicates the apparent power consumption
in Volt-Amps. A negative value indicates that the apparent
power consumption was not available.
Volt-AmpsInteger32
Constraints:
range: -1-25000
range: 0-16777215
.1.3.6.1.4.1.1718.3.2.2.1.13
infeedPowerFactor
The power factor of the input feed phase. A non-negative
value indicates the power factor in hundredths. A negative
value indicates that the power factor was not able to be
measured.
hundredthsInteger32
Constraints:
range: -1-100
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.14
infeedCrestFactor
The crest factor for the load of the input feed phase. A
non-negative value indicates the crest factor in tenths. A
negative value indicates that the crest factor was not able
to be measured.
tenthsInteger32
Constraints:
range: -1-1000
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.15
infeedEnergy
The energy consumption of the input feed phase. A non-
negative value indicates the energy consumption in tenths of
Kilowatt-Hours. A negative value indicates that the energy
consumption was not available.
tenth Kilowatt-HoursInteger32
Constraints:
range: -1-2147483647
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.16
infeedReactance
The characterization of the phase relation between the
voltage and current of the input feed phase.
Enumeration
Enumerated Values:
0unknown
1capacitive
2inductive
3resistive
.1.3.6.1.4.1.1718.3.2.2.1.17
infeedPhaseVoltage
The voltage measured for the input feed phase. A non-
negative value indicates the voltage in tenths of Volts. A
negative value indicates that the voltage was not available.
tenth VoltsInteger32
Constraints:
range: -1-2640
range: 0-255
.1.3.6.1.4.1.1718.3.2.2.1.18
infeedPhaseCurrent
The current measured for the input feed phase. A non-
negative value indicates the measured load in hundredths of
Amps. A negative value indicates that a load value was not
able to be measured.
hundredth AmpsInteger32
Constraints:
range: -1-25500
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.19
infeedCapacityUsed
The used percentage of the input feed line load capacity
(infeedLoadValue / infeedCapacity x 100). A non-negative
value indicates the percentage of capacity used in tenths.
A negative value indicates that the percentag…
tenth percentageInteger32
Constraints:
range: -1-1500
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.20
infeedLineID
The ID of the input feed line.
OctetString
Constraints:
range: 0-4
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.21
infeedLineToLineID
The line-to-line ID of the input feed.
OctetString
Constraints:
range: 0-7
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.22
infeedPhaseID
The ID of the input feed phase.
OctetString
Constraints:
range: 0-6
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.23
infeedVACapacity
The apparent power capacity of the input feed circuit. A
non-negative value indicates the maximum apparent power in
Volt-Amps. A negative value indicates that the apparent
power capacity was not available.
Volt-AmpsInteger32
Constraints:
range: -1-25000
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.24
infeedVACapacityUsed
The used percentage of the input feed circuit apparent power
capacity (infeedApparentPower / infeedVACapacity x 100). A
non-negative value indicates the percentage of capacity used
in tenths. A negative value indicate…
tenth percentageInteger32
Constraints:
range: -1-1500
range: 4-4
.1.3.6.1.4.1.1718.3.2.2.1.25
.1.3.6.1.4.1.1718.3.2.3 · 1 row entry · 20 columns
A table of outlets.
outletEntry entry .1.3.6.1.4.1.1718.3.2.3.1
Row definition for the outlet table.
Indexes
towerIndex infeedIndex outletIndex
Column Syntax OID
outletIndex
Index for the outlet table.
Integer32
Constraints:
range: 0-64
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.1
outletID
The ID of the outlet.
OctetString
Constraints:
range: 2-4
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.2
outletName
The name of the outlet.
OctetStringr/w
Constraints:
range: 0-24
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.3
outletCapabilities
The capabilities of the outlet.
Bits
Enumerated Values:
0onSense
1loadSense
2powerControl
3shutdown
4defaultOn
5ownInfeed
6fusedBranch
7voltageSense
8powerSense
Constraints:
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.4
outletStatus
The status of the outlet. If the outletCapabilities
'onSense' bit is TRUE, then the state indicates the sensed
state of the outlet, not a derived state, and 'offError'
and 'onError' are supported to indicate a mismatch…
Enumeration
Enumerated Values:
0off
1on
2offWait
3onWait
4offError
5onError
6noComm
7reading
8offFuse
9onFuse
Constraints:
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.5
outletLoadStatus
The status of the load measured on the outlet. If the
outletCapabilities 'loadSense' bit is TRUE, then all of the
states are supported. If the outletCapabilities 'loadSense'
bit is FALSE, then only the 'normal' and '…
Enumeration
Enumerated Values:
0normal
1notOn
2reading
3loadLow
4loadHigh
5overLoad
6readError
7noComm
Constraints:
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.6
outletLoadValue
The load measured on the outlet. A non-negative value
indicates the measured load in hundredths of Amps. A
negative value indicates that a load value was not able to
be measured.
hundredth AmpsInteger32
Constraints:
range: -1-25500
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.7
outletLoadLowThresh
The load low threshold value of the outlet in Amps.
AmpsInteger32r/w
Constraints:
range: 0-255
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.8
outletLoadHighThresh
The load high threshold value of the outlet in Amps.
AmpsInteger32r/w
Constraints:
range: 0-255
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.9
outletControlState
The control state of the outlet. The supported states are
dependent upon the outletCapabilities 'powerControl' and
'shutdown' bits, as well as the supported features of the
firmware version.
Enumeration
Enumerated Values:
0idleOff
1idleOn
2wakeOff
3wakeOn
4off
5on
6lockedOff
7lockedOn
8reboot
9shutdown
10pendOn
11pendOff
12minimumOff
13minimumOn
14eventOff
15eventOn
16eventReboot
17eventShutdown
Constraints:
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.10
outletControlAction
An action to change the control state of the outlet. If
the outletCapabilities 'powerControl' bit is TRUE, then the
'on', 'off', and 'reboot' actions can be used to change the
control state of the outlet. If the outle…
Enumerationr/w
Enumerated Values:
0none
1on
2off
3reboot
Constraints:
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.11
outletCapacity
The load capacity of the outlet. A non-negative value
indicates the maximum load in Amps. A negative value
indicates that the capacity was not available.
AmpsInteger32
Constraints:
range: -1-255
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.12
outletVoltage
The voltage of the outlet. A non-negative value indicates
the voltage in tenths of Volts. A negative value indicates
that the voltage was not available.
tenth VoltsInteger32
Constraints:
range: -1-2640
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.13
outletPower
The active power consumption of the device plugged into the
outlet. A non-negative value indicates the active power
consumption in Watts. A negative value indicates that the
active power consumption was not available.
WattsInteger32
Constraints:
range: -1-10000
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.14
outletApparentPower
The apparent power consumption of the device plugged into
the outlet. A non-negative value indicates the apparent
power consumption in Volt-Amps. A negative value indicates
that the apparent power consumption was not …
Volt-AmpsInteger32
Constraints:
range: -1-10000
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.15
outletPowerFactor
The power factor of the device plugged into the outlet. A
non-negative value indicates the power factor in hundredths.
A negative value indicates that the power factor was not able
to be measured.
hundredthsInteger32
Constraints:
range: -1-100
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.16
outletCrestFactor
The crest factor for the load of the device plugged into the
outlet. A non-negative value indicates the crest factor in
tenths. A negative value indicates that the crest factor
was not able to be measured.
tenthsInteger32
Constraints:
range: -1-1000
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.17
outletEnergy
The energy consumption of the device plugged into the outlet.
A non-negative value indicates the energy consumption in
Watt-Hours. A negative value indicates that the energy
consumption was not available.
Watt-HoursInteger32
Constraints:
range: -1-2147483647
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.18
outletWakeupState
The wakeup state of the outlet.
Enumerationr/w
Enumerated Values:
1last
2off
3on
Constraints:
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.19
outletPostOnDelay
The post-on delay of the outlet.
secondsInteger32r/w
Constraints:
range: 0-900
range: 4-4
.1.3.6.1.4.1.1718.3.2.3.1.20
.1.3.6.1.4.1.1718.3.2.4 · 1 row entry · 13 columns
A table of environmental monitors.
envMonEntry entry .1.3.6.1.4.1.1718.3.2.4.1
Row definition for the environmental monitor table.
Indexes
envMonIndex
Column Syntax OID
envMonIndex
Index for the environmental monitor table.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.3.2.4.1.1
envMonID
The ID of the environmental monitor.
OctetString
Constraints:
range: 1-1
.1.3.6.1.4.1.1718.3.2.4.1.2
envMonName
The name of the environmental monitor.
OctetStringr/w
Constraints:
range: 0-24
.1.3.6.1.4.1.1718.3.2.4.1.3
envMonStatus
The operational status of the environmental monitor.
Enumeration
Enumerated Values:
0normal
1noComm
.1.3.6.1.4.1.1718.3.2.4.1.4
envMonWaterSensorName
The name of the water sensor.
OctetStringr/w
Constraints:
range: 0-24
.1.3.6.1.4.1.1718.3.2.4.1.5
envMonWaterSensorStatus
The status of the water sensor.
Enumeration
Enumerated Values:
0normal
1alarm
2noComm
.1.3.6.1.4.1.1718.3.2.4.1.6
envMonADCName
The name of the analog-to-digital converter.
OctetStringr/w
Constraints:
range: 0-24
.1.3.6.1.4.1.1718.3.2.4.1.7
envMonADCStatus
The status of the analog-to-digital converter.
Enumeration
Enumerated Values:
0normal
1reading
2countLow
3countHigh
4readError
5noComm
.1.3.6.1.4.1.1718.3.2.4.1.8
envMonADCCount
The 8-bit count value from the analog-to-digital converter.
A non-negative value indicates the digital value retrieved
from the ADC. A negative value indicates that a digital
value was not able to be retrieved.
Integer32
Constraints:
range: -1-255
.1.3.6.1.4.1.1718.3.2.4.1.9
envMonADCLowThresh
The 8-bit count low threshold value of the analog-to-digital
converter.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.1718.3.2.4.1.10
envMonADCHighThresh
The 8-bit count high threshold value of the analog-to-digital
converter.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.1718.3.2.4.1.11
envMonTempHumidSensorCount
The number of temperature/humidity sensors on the
environmental monitor.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.1718.3.2.4.1.12
envMonContactClosureCount
The number of contact closures on the environmental
monitor.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.3.2.4.1.13
.1.3.6.1.4.1.1718.3.2.5 · 1 row entry · 15 columns
A table of temperature/humidity sensors.
tempHumidSensorEntry entry .1.3.6.1.4.1.1718.3.2.5.1
Row definition for the temperature/humidity sensor table.
Indexes
envMonIndex tempHumidSensorIndex
Column Syntax OID
tempHumidSensorIndex
Index for the temperature/humidity sensor table.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.1718.3.2.5.1.1
tempHumidSensorID
The ID of the temperature/humidity sensor.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.3.2.5.1.2
tempHumidSensorName
The name of the temperature/humidity sensor.
OctetStringr/w
Constraints:
range: 0-24
.1.3.6.1.4.1.1718.3.2.5.1.3
tempHumidSensorStatus
The operational status of the temperature/humidity sensor.
Enumeration
Enumerated Values:
0found
1notFound
2lost
3noComm
.1.3.6.1.4.1.1718.3.2.5.1.4
tempHumidSensorTempStatus
The status of the temperature sensor.
Enumeration
Enumerated Values:
0normal
1notFound
2reading
3tempLow
4tempHigh
5readError
6lost
7noComm
.1.3.6.1.4.1.1718.3.2.5.1.5
tempHumidSensorTempValue
The temperature measured by the sensor. A non-negative value
indicates the measured temperature in tenths of degrees, using
the scale selected by tempHumidSensorTempScale. If the agent
does not support the tempHumidSe…
tenth degreesInteger32
Constraints:
range: -1-2540
.1.3.6.1.4.1.1718.3.2.5.1.6
tempHumidSensorTempLowThresh
The temperature low threshold value of the sensor in degrees,
using the scale selected by tempHumidSensorTempScale. If the
agent does not support the tempHumidSensorTempScale object,
then the temperature scale used is …
degreesInteger32r/w
Constraints:
range: 0-254
.1.3.6.1.4.1.1718.3.2.5.1.7
tempHumidSensorTempHighThresh
The temperature high threshold value of the sensor in degrees,
using the scale selected by tempHumidSensorTempScale. If the
agent does not support the tempHumidSensorTempScale object,
then the temperature scale used is…
degreesInteger32r/w
Constraints:
range: 0-254
.1.3.6.1.4.1.1718.3.2.5.1.8
tempHumidSensorHumidStatus
The status of the humidity sensor.
Enumeration
Enumerated Values:
0normal
1notFound
2reading
3humidLow
4humidHigh
5readError
6lost
7noComm
.1.3.6.1.4.1.1718.3.2.5.1.9
tempHumidSensorHumidValue
The humidity measured by the sensor. A non-negative value
indicates the measured humidity in percentage relative
humidity. A negative value indicates that a humidity value
was not able to be measured.
percentage relative humidityInteger32
Constraints:
range: -1-100
.1.3.6.1.4.1.1718.3.2.5.1.10
tempHumidSensorHumidLowThresh
The humidity low threshold value of the sensor in percentage
relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.3.2.5.1.11
tempHumidSensorHumidHighThresh
The humidity low threshold value of the sensor in percentage
relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.3.2.5.1.12
tempHumidSensorTempScale
The scale used for temperature values. This is a global
setting for all temperature values in the system. If the
agent does not support this object, then the temperature
scale used is Celsius.
Enumerationr/w
Enumerated Values:
0celsius
1fahrenheit
.1.3.6.1.4.1.1718.3.2.5.1.13
tempHumidSensorTempRecDelta
The temperature recovery delta (hysteresis) value of the
sensor in degrees, using the scale selected by
tempHumidSensorTempScale.
degreesInteger32r/w
Constraints:
range: 0-54
range: 1-8
.1.3.6.1.4.1.1718.3.2.5.1.14
tempHumidSensorHumidRecDelta
The humidity recovery delta (hysteresis) value of the
sensor in percentage relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-20
.1.3.6.1.4.1.1718.3.2.5.1.15
.1.3.6.1.4.1.1718.3.2.6 · 1 row entry · 4 columns
A table of contact closures.
contactClosureEntry entry .1.3.6.1.4.1.1718.3.2.6.1
Row definition for the contact closure table.
Indexes
envMonIndex contactClosureIndex
Column Syntax OID
contactClosureIndex
Index for the contact closure table.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.3.2.6.1.1
contactClosureID
The ID of the contact closure.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.3.2.6.1.2
contactClosureName
The name of the contact closure.
OctetStringr/w
Constraints:
range: 0-24
.1.3.6.1.4.1.1718.3.2.6.1.3
contactClosureStatus
The status of the contact closure.
Enumeration
Enumerated Values:
0normal
1alarm
2noComm
.1.3.6.1.4.1.1718.3.2.6.1.4
.1.3.6.1.4.1.1718.3.2.7 · 1 row entry · 9 columns
A table of branches.
branchEntry entry .1.3.6.1.4.1.1718.3.2.7.1
Row definition for the branch table.
Indexes
towerIndex APOLLO-MIBapolloLacpStatsIndex infeedIndex branchIndex
Column Syntax OID
branchIndex
Index for the branch table.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.3.2.7.1.1
branchID
The ID of the branch.
OctetString
Constraints:
range: 3-3
.1.3.6.1.4.1.1718.3.2.7.1.2
branchName
The name of the branch.
OctetStringr/w
Constraints:
range: 0-24
.1.3.6.1.4.1.1718.3.2.7.1.3
branchCapabilities
The capabilities of the branch.
Bits
Enumerated Values:
0onSense
1loadSense
.1.3.6.1.4.1.1718.3.2.7.1.4
branchStatus
The status of the branch.
Enumeration
Enumerated Values:
0off
1on
2offWait
3onWait
4offError
5onError
6noComm
7reading
8offFuse
9onFuse
.1.3.6.1.4.1.1718.3.2.7.1.5
branchLoadStatus
The status of the load measured on the branch.
Enumeration
Enumerated Values:
0normal
1notOn
2reading
3loadLow
4loadHigh
5overLoad
6readError
7noComm
.1.3.6.1.4.1.1718.3.2.7.1.6
branchLoadValue
The load measured on the branch. A non-negative
value indicates the measured load in hundredths of Amps. A
negative value indicates that a load value was not able to
be measured.
hundredth AmpsInteger32
Constraints:
range: -1-4000
.1.3.6.1.4.1.1718.3.2.7.1.7
branchLoadHighThresh
The load high threshold value of the branch in Amps.
AmpsInteger32r/w
Constraints:
range: 0-40
.1.3.6.1.4.1.1718.3.2.7.1.8
branchCapacity
The load capacity of the branch. A non-negative value
indicates the maximum load in Amps. A negative value
indicates that the capacity was not available.
AmpsInteger32
Constraints:
range: -1-40
.1.3.6.1.4.1.1718.3.2.7.1.9