outletStatus

Sentry3-MIB · .1.3.6.1.4.1.1718.3.2.3.1.5

Object

column Enumeration
The status of the outlet.  If the outletCapabilities
'onSense' bit is TRUE, then the state indicates the sensed
state of the outlet, not a derived state, and 'offError'
and 'onError' are supported to indicate a mismatch between
the control and sensed state.  If the outletCapabilities
'fusedBranch' bit is TRUE, then the outlet is on a fused
branch circuit that can detect the fuse state, and 'offFuse'
and 'onFuse' are supported to indicate a fuse error.

Context

MIB
Sentry3-MIB
OID
.1.3.6.1.4.1.1718.3.2.3.1.5
Type
column
Access
readonly
Status
current
Parent
outletEntry
Table
outletTable
Siblings
19

Syntax

Enumeration

Values & Constraints

Enumerated Values
0off
1on
2offWait
3onWait
4offError
5onError
6noComm
7reading
8offFuse
9onFuse
Object Constraints
range: 4-4

Related Objects

Sibling Objects