outletLoadStatus
Sentry3-MIB ·
.1.3.6.1.4.1.1718.3.2.3.1.6
Object
column
Enumeration
The status of the load measured on the outlet. If the outletCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the outletCapabilities 'loadSense' bit is FALSE, then only the 'normal' and 'noComm' states are supported.
Context
- MIB
- Sentry3-MIB
- OID
.1.3.6.1.4.1.1718.3.2.3.1.6- Type
- column
- Access
- readonly
- Status
- current
- Parent
- outletEntry
- Table
- outletTable
- Siblings
- 19
Syntax
Enumeration
Values & Constraints
Enumerated Values
0 | normal |
1 | notOn |
2 | reading |
3 | loadLow |
4 | loadHigh |
5 | overLoad |
6 | readError |
7 | noComm |
Object Constraints
range: 4-4
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| outletIndex Index for the outlet table. | column | Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.1 |
| outletControlState The control state of the outlet. The supported states are
dependent upon the outletCapabilities 'powerControl' and
'shutdown' bits, as well as the supported features of the
firmw… | column | Enumeration | .1.3.6.1.4.1.1718.3.2.3.1.10 |
| outletControlAction An action to change the control state of the outlet. If
the outletCapabilities 'powerControl' bit is TRUE, then the
'on', 'off', and 'reboot' actions can be used to change the
co… | column | Enumeration | .1.3.6.1.4.1.1718.3.2.3.1.11 |
| outletCapacity The load capacity of the outlet. A non-negative value
indicates the maximum load in Amps. A negative value
indicates that the capacity was not available. | column | Amps Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.12 |
| outletVoltage The voltage of the outlet. A non-negative value indicates
the voltage in tenths of Volts. A negative value indicates
that the voltage was not available. | column | tenth Volts Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.13 |
| outletPower The active power consumption of the device plugged into the
outlet. A non-negative value indicates the active power
consumption in Watts. A negative value indicates that the
act… | column | Watts Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.14 |
| outletApparentPower The apparent power consumption of the device plugged into
the outlet. A non-negative value indicates the apparent
power consumption in Volt-Amps. A negative value indicates
that… | column | Volt-Amps Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.15 |
| outletPowerFactor The power factor of the device plugged into the outlet. A
non-negative value indicates the power factor in hundredths.
A negative value indicates that the power factor was not ab… | column | hundredths Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.16 |
| outletCrestFactor The crest factor for the load of the device plugged into the
outlet. A non-negative value indicates the crest factor in
tenths. A negative value indicates that the crest factor
… | column | tenths Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.17 |
| outletEnergy The energy consumption of the device plugged into the outlet.
A non-negative value indicates the energy consumption in
Watt-Hours. A negative value indicates that the energy
cons… | column | Watt-Hours Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.18 |
| outletWakeupState The wakeup state of the outlet. | column | Enumeration | .1.3.6.1.4.1.1718.3.2.3.1.19 |
| outletID The ID of the outlet. | column | OctetString | .1.3.6.1.4.1.1718.3.2.3.1.2 |
| outletPostOnDelay The post-on delay of the outlet. | column | seconds Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.20 |
| outletName The name of the outlet. | column | OctetString | .1.3.6.1.4.1.1718.3.2.3.1.3 |
| outletCapabilities The capabilities of the outlet. | column | Bits | .1.3.6.1.4.1.1718.3.2.3.1.4 |
| outletStatus The status of the outlet. If the outletCapabilities
'onSense' bit is TRUE, then the state indicates the sensed
state of the outlet, not a derived state, and 'offError'
and 'onErr… | column | Enumeration | .1.3.6.1.4.1.1718.3.2.3.1.5 |
| outletLoadValue The load measured on the outlet. A non-negative value
indicates the measured load in hundredths of Amps. A
negative value indicates that a load value was not able to
be measured. | column | hundredth Amps Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.7 |
| outletLoadLowThresh The load low threshold value of the outlet in Amps. | column | Amps Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.8 |
| outletLoadHighThresh The load high threshold value of the outlet in Amps. | column | Amps Integer32 | .1.3.6.1.4.1.1718.3.2.3.1.9 |