TRIPPLITE-PRODUCTS Table View

Table-centric layout grouping table, row, and column objects.

Tables
80
Rows
80
Columns
556
.1.3.6.1.4.1.850.1.1.1.2 · 1 row entry · 10 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpDeviceTable'
A list of device table entries.  The number of entries
is given by the value of tlpDevicesNumDevices.
tlpDeviceEntry row .1.3.6.1.4.1.850.1.1.1.2.1
An entry containing information applicable to a particular device
managed by this agent.
Indexes
Column Syntax OID
The table row index for the device.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.1.2.1.1
Used with table edits to indicate the status of a given row in
tlpDeviceTable.
SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.850.1.1.1.2.1.2
The type of device. One of the appropriate hardware types:
ups, pdu, envirosense, etc.
ObjectIdentifier .1.3.6.1.4.1.850.1.1.1.2.1.3
The name of the manufacturer.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.1.2.1.4
The model designation.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.1.2.1.5
A user-supplied name for the device.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.1.2.1.6
A user-supplied ID for the device.
Integer32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.850.1.1.1.2.1.7
A user-supplied location for the device.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.1.2.1.8
A user-supplied region for the device.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.1.2.1.9
The currently most critical alarm status for the device.
Enumeration
Enumerated Values:
0none
1critical
2warning
3info
4status
5offline
6custom
7configuration
.1.3.6.1.4.1.850.1.1.1.2.1.10
.1.3.6.1.4.1.850.1.1.2.1 · 1 row entry · 12 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpDeviceIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpDeviceIdentTable'
The identity details of each device in device table. The number
of entries is given by the value of tlpDevicesNumDevices.
tlpDeviceIdentEntry row .1.3.6.1.4.1.850.1.1.2.1.1
An entry containing details for a particular device.
Indexes
Column Syntax OID
The Tripplite protocol used to communicate with the device.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.1
The type of communications port used to connect with the device.
Enumeration
Enumerated Values:
0unknown
1serial
2usb
3hid
4simulated
5unittest
.1.3.6.1.4.1.850.1.1.2.1.1.2
The name of the communications port.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.3
The firmware version of the device.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.4
The serial number of the device.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.5
The installation date for this device in the format of mm/dd/yyyy.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.6
The hardware revision of the device. This value will return ERROR_NO_SUCH_NAME
if not supported by the device.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.7
The device uptime since its last startup. The format of this value is a comma-
delimited string representing days, hours and minutes. For example, the value of
123,4,5 represents 123 days, 4 hours and 5 minutes. This va…
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.8
The cumulative (total) uptime for the device. The format of this value is a comma-
delimited string representing days, hours and minutes. For example, the value of
123,4,5 represents 123 days, 4 hours and 5 minutes. Thi…
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.9
The firmware version of second IC on the device. This value will return
ERROR_NO_SUCH_NAME if not supported by the device.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.10
The firmware version of third IC on the device. This value will return
ERROR_NO_SUCH_NAME if not supported by the device.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.11
The id of NVRAM. This value will return ERROR_NO_SUCH_NAME if not supported by the device.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.2.1.1.12
.1.3.6.1.4.1.850.1.1.3.1.1.2 · 1 row entry · 8 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsIdentTable'
The identity details of each ups in device table. This is a
sparse dependent table, and will contain some subset of devices
that are upss.
tlpUpsIdentEntry row .1.3.6.1.4.1.850.1.1.3.1.1.2.1
An entry containing details for a particular ups.
Indexes
Column Syntax OID
The number of input lines supported by the ups.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.1.2.1.1
The number of output lines supported by the ups.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.1.2.1.2
The number of bypass lines supported by the ups.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.1.2.1.3
The number of phases supported by the ups.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.1.2.1.4
The number of receptacles supported by the ups.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.1.2.1.5
The number of receptacle groups supported by the ups.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.1.2.1.6
The number of battery packs, internal and external combined,
supported by the ups.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.1.2.1.7
The number of fans supported by the ups.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.1.2.1.8
.1.3.6.1.4.1.850.1.1.3.1.1.3 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsSupportsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsSupportsTable'
The supported details of each ups in device table. This is a
sparse dependent table, and will contain some subset of devices
that are upss.
tlpUpsSupportsEntry row .1.3.6.1.4.1.850.1.1.3.1.1.3.1
An entry containing supported details for a particular ups.
Indexes
Column Syntax OID
Indicates whether the ups supports Cisco EnergyWise.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.1.3.1.1
Indicates whether the ups supports ramping and shedding.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.1.3.1.2
Indicates whether the ups supports outlet groups.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.1.3.1.3
Indicates whether the ups reports individual receptacle current
and power measurements. Devices that do not support individual
receptacle measurements will always return ERROR_NO_SUCH_NAME for
tlpUpsOutletCurrent and tl…
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.1.3.1.4
Indicates whether the ups reports individual receptacle voltage
measurements. Devices that do not support individual receptacle
measurements will always return ERROR_NO_SUCH_NAME for
tlpUpsOutletVoltage.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.1.3.1.5
.1.3.6.1.4.1.850.1.1.3.1.2.1 · 1 row entry · 11 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsDeviceTable'
The device details of each ups in device table. This is a
sparse dependent table, and will contain some subset of devices
that are upss.
tlpUpsDeviceEntry row .1.3.6.1.4.1.850.1.1.3.1.2.1.1
An entry containing device details for a particular ups.
Indexes
Column Syntax OID
The current state of the main output of the device.
Enumeration
Enumerated Values:
0unknown
1off
2on
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.1
Indicates whether or not the main output is controllable, and whether
the ups can be turned off and on.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.2
Reading this value will always return 0. Setting this value to
turnOff(1) will turn off the main output of the ups. Setting this
value to turnOn(2) will turn on the main output of the ups. Setting
this value to cycle(3)…
Enumerationr/w
Enumerated Values:
0idle
1turnOff
2turnOn
3cycle
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.3
The configurable delay value, which sets the amount of additional
time a given device will wait before it connects to a valid AC
source. By default the delay value is set to 0.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.4
The date of the last self-test run on the ups, in the format YYYY-MM-DD.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.5
The result of the last self-test run on the ups.
Enumeration
Enumerated Values:
0noTest
1doneAndPassed
2doneAndWarning
3doneAndError
4aborted
5inProgress
6noTestInitiated
7badBattery
8overCurrent
9batteryFailed
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.6
The ambient temperature at or near the ups casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.7
The ambient temperature at or near the ups casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.8
The last AC failure reason.
Enumeration
Enumerated Values:
0noACFailureSinceReset
1blackout
2instantaneousHighLineFrequency
3highLineVoltage
4lowLineVoltage
5averageFrequencyFault
6instantaneousLowLineFrequency
7delayedBrownout
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.9
The last unit shut down reason.
Enumeration
Enumerated Values:
0noShutdownSinceReset
1onOffButtonShutdown
2averageVbattSmallerThenLVCShutdown
3fastVbattKeepaliveVoltageFastShutdown
4averageCurrentLimitShutdown
5fastCurrentLimitShutdown
6heavyLoadThermalTimeLimitShutdown
7fixedInvertModeTimeLimitShutdown
8highBatteryVoltageFault
9averageVbattKeepaliveVoltageShutdown
10shutdownCommandWithAutorestartEnabled
11shutdownCommandWithoutAutorestartEnabled
12lineConnectRelayFault
13epoInvertMode
14epoRebootMode
15invalidLineStandbyMode
16chargerLimitMinBatteryVoltage
17chargerLimitMaxBatteryVoltage
18invalidLineDelayedWakeupAutorestartEnabled
19invalidLineDelayedWakeupAutorestartDisabled
20minBatteryVoltagePriorDelayedWakeupAutorestartEnabled
21minBatteryVoltagePriorDelayedWakeupAutorestartDisabled
22lvcShutdownAutorestartEnabled
23lvcShutdownAutorestartDisabled
24overloadShutdownAutorestartEnabled
25overloadShutdownAutorestartDisabled
26overTemperatureShutdownAutorestartEnabled
27overTemperatureShutdownAutorestartDisabled
28onOffButtonShutdownAutorestartEnabled
29onOffButtonShutdownAutorestartDisabled
30batteryReportedFault
31batteryCommunicationLost
32batteryJumpStartChargerTimeoutError
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.10
Output current is reported by tlpUpsOutputLineCurrent, tlpUpsOutputLineCurrentMin and
tlpUpsOutputLineCurrentMax. These values are all reported in hundredths(0.01A),which
accommodates all models; however, on any give…
Enumeration
Enumerated Values:
0wholeNumber
1tenths
2hundredths
.1.3.6.1.4.1.850.1.1.3.1.2.1.1.11
.1.3.6.1.4.1.850.1.1.3.1.3.1.1 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsBatterySummaryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsBatterySummaryTable'
The battery system summary of each ups in the device
table. This is a sparse dependent table, and will contain the
number of entries based upon the number of upss managed by
the agent as reported by tlpUpsIdentNumUps.
tlpUpsBatterySummaryEntry row .1.3.6.1.4.1.850.1.1.3.1.3.1.1.1
An entry containing information applicable to a particular
battery system managed by this agent.
Indexes
Column Syntax OID
The indication of the capacity remaining in the UPS system's
batteries. A value of batteryNormal indicates that the
remaining run-time is greater than tlpUpsConfigLowBattTime. A
value of batteryLow indicates that the re…
Enumeration
Enumerated Values:
1unknown
2batteryNormal
3batteryLow
4batteryDepleted
.1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.1
If the unit is on battery power, the elapsed time since the UPS
last switched to battery power, or the time since the network
management subsystem was last restarted, whichever is less. Zero
shall be returned if the uni…
secondsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.2
An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off.
minutesSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.3
An estimate of the battery charge remaining expressed
as a percent of full charge.
percentInteger32
Constraints:
range: 0-100
.1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.4
The run time remaining before batteries are exhausted. If the device
does not support run time remaining, then the agent reports
ERROR_NO_SUCH_NAME.
SNMPv2-SMITimeTicks
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.1.1.5
.1.3.6.1.4.1.850.1.1.3.1.3.1.2 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsBatteryDetailTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsBatteryDetailTable'
The battery detail of each ups in the device table. This is a sparse
dependent table, and will contain the number of entries based upon the
number of upss managed by the agent as reported by tlpUpsIdentNumUps.
tlpUpsBatteryDetailEntry row .1.3.6.1.4.1.850.1.1.3.1.3.1.2.1
An entry containing information applicable to a particular
battery system managed by this agent.
Indexes
Column Syntax OID
The magnitude of the present battery voltage.
0.1 Volt DCSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.1
The present battery current.
0.01 Amps DCSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.2
The estimated remaining battery capacity expressed as a percent of
full capacity.
percentInteger32
Constraints:
range: 0-100
.1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.3
Denotes the charge state of the battery.
Enumeration
Enumerated Values:
0floating
1charging
2resting
3discharging
4normal
5standby
.1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.4
The status of the battery charger. If the device does not support this
value, then the agent will report ERROR_NO_SUCH_NAME.
Enumeration
Enumerated Values:
0ok
1inFaultCondition
.1.3.6.1.4.1.850.1.1.3.1.3.1.2.1.5
.1.3.6.1.4.1.850.1.1.3.1.3.1.3 · 1 row entry · 6 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsBatteryPackIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsBatteryPackIdentTable'
The battery identification details for each ups in the device
table. This is a sparse dependent table, and will contain the
number of entries based upon the number of upss managed by the
agent as reported by upsIdentNumUps and the number of battery
battery packs per each as reported by tlpUpsNumBatteryPacks.
tlpUpsBatteryPackIdentEntry row .1.3.6.1.4.1.850.1.1.3.1.3.1.3.1
An entry containing information applicable to a particular
battery pack managed by this agent.
Column Syntax OID
The table row index for the ups battery pack.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.1
The manufacturer of the battery pack. If the device does not
support this value, then the agent reports ERROR_NO_SUCH_NAME.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.2
The model or device name of the battery pack. If the device does not
support this value, then the agent reports ERROR_NO_SUCH_NAME.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.3
The serial number of the battery pack. If the device does not support
this value, then the agent reports ERROR_NO_SUCH_NAME.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.4
The firmware of the battery pack. If the device does not support this
value, then the agent reports ERROR_NO_SUCH_NAME.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.5
The SKU of the battery pack. If the device does not support this value,
then the agent reports ERROR_NO_SUCH_NAME.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.1.3.1.6
.1.3.6.1.4.1.850.1.1.3.1.3.1.4 · 1 row entry · 12 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsBatteryPackConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsBatteryPackConfigTable'
The battery configuration details for each ups in the device
table. This is a sparse dependent table, and will contain the
number of entries based upon the number of upss managed by the
agent as reported by upsIdentNumUps and the number of battery
battery packs per each as reported by tlpUpsNumBatteryPacks.
tlpUpsBatteryPackConfigEntry row .1.3.6.1.4.1.850.1.1.3.1.3.1.4.1
An entry containing information applicable to a particular
battery pack managed by this agent.
Column Syntax OID
The type of battery pack.
Enumeration
Enumerated Values:
0unknown
1leadAcid
2nickelCadmium
3lithiumIon
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.1
The style of battery pack.
Enumeration
Enumerated Values:
0unknown
1nonsmart
2smart
3bms
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.2
The location of the battery pack.
Enumeration
Enumerated Values:
0unknown
1internal
2external
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.3
The number of series strings in parallel contained in the battery
pack. If the device does not support this value, then the agent will
report ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.4
The number of battery per each string in the battery pack. If the
device does not support this value, then the agent will report
ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.5
The number of cells per battery..
Enumeration
Enumerated Values:
0unknown
1one
2two
4four
6six
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.6
The total number of batteries contained in the battery pack. If the device
does not support this value, then the agent will report ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.7
The units of measurement used for tlpUpsBatteryPackConfigDesignCapacity and
tlpUpsBatteryPackConfigCellCapacity. If supported, this value will report either
mAHR(1), amps per hour, or mWhr(1), watts per hour. If the dev…
Enumeration
Enumerated Values:
0mAHr
1mWHr
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.8
The theoretical or nominal capacity of the battery pack in the measurement
defined by tlpUpsBatteryPackConfigCapacityUnits. If the device does not support
this value, then the agent will report ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.9
The capacity of the batteries in the measurement defined by
tlpUpsBatteryPackConfigCapacityUnits. If the device does not support this value,
then the agent will report ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.10
The minimum cell voltage for the batteries. If the device does not support
this value, then the agent will report ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.11
The maximum cell voltage for the batteries. If the device does not support
this value, then the agent will report ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.4.1.12
.1.3.6.1.4.1.850.1.1.3.1.3.1.5 · 1 row entry · 7 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsBatteryPackDetailTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsBatteryPackDetailTable'
The details of each battery pack for each ups in the device
table. This is a sparse dependent table, and will contain the
number of entries based upon the number of upss and battery
packs managed by the agent as reported by tlpUpsIdentNumUps
and tlpUpsIdentNumBatteryPacks.
tlpUpsBatteryPackDetailEntry row .1.3.6.1.4.1.850.1.1.3.1.3.1.5.1
An entry containing information applicable to a particular
battery system managed by this agent.
Column Syntax OID
The condition of the battery. A bad battery should be replaced.
Enumeration
Enumerated Values:
0unknown
1good
2weak
3bad
.1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.1
The ambient temperature at or near the UPS Battery casing.
0.1 degrees CelsiusSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.2
The ambient temperature at or near the UPS Battery casing.
0.1 degrees FahrenheitSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.3
The age of the battery in years. This is equal to the current
date minus tlpUpsBatteryPackIdentInstallDate.
0.1 YearsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.4
The date when the batteries were last replaced in YYYYMMDD format.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.5
The date when the batteries should next be replaced in YYYYMMDD
format.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.6
The number of times the battery went into invert mode. This number
is incremented by 1 each time the unit goes on battery mode (with
the exception of Self Test mode). If the device does not support this
value, then the …
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.1.5.1.7
.1.3.6.1.4.1.850.1.1.3.1.3.2.1 · 1 row entry · 10 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsInputTable'
The input details of each ups in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported
by tlpUpsIdentNumUps.
tlpUpsInputEntry row .1.3.6.1.4.1.850.1.1.3.1.3.2.1.1
An entry containing information applicable to all input lines per
each ups managed by this agent.
Indexes
Column Syntax OID
A count of the number of times the input entered an out-of-tolerance
condition as defined by the manufacturer. This count is incremented
by one each time the input transitions from zero out-of-tolerance
lines to one or…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.1
The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.2
The nominal value of the input line frequency. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.3
The minimum line voltage allowed before the ups system transfers to
battery backup.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.4
The lower boundary value of tlpUpsInputLowTransferVoltage as dictated
by the hardware of the unit.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.5
The upper boundary value of tlpUpsInputLowTransferVoltage as dictated
by the hardware of the unit.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.6
The maximum line voltage allowed before the ups system transfers to
battery backup.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.7
The lower boundary value of tlpUpsInputHighTransferVoltage as dictated
by the hardware of the unit.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.8
The upper boundary value of tlpUpsInputHighTransferVoltage as dictated
by the hardware of the unit.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.9
The number of watt hours of energy utilized in the past 24 hours. Use
tlpUpsControlResetWattHours to reset the watt hours calculation algorithm.
WHSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.1.1.10
.1.3.6.1.4.1.850.1.1.3.1.3.2.2 · 1 row entry · 7 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsInputPhaseTable'
The input phase details of each ups in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported
by tlpUpsIdentNumUps and tlpUpsIdentNumPhases.
tlpUpsInputPhaseEntry row .1.3.6.1.4.1.850.1.1.3.1.3.2.2.1
An entry containing information applicable to a particular
input phase managed by this agent.
Column Syntax OID
The table row index for the ups input phase.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.1
The present input frequency for a given input line.
0.1 HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.2
The magnitude of the present input voltage for a given input line.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.3
The minimum input voltage value since the last reset of this
value for a given input line. If any value is written to either
tlpUpsInputVoltageMin or tlpUpsInputVoltageMax, both will be reset to
their appropriate minimu…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.4
The maximum input voltage value since the last reset of this
value for a given input line. If any value is written to either
tlpUpsInputVoltageMin or tlpUpsInputVoltageMax, both will be reset to
their appropriate minimu…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.5
The magnitude of the present input current.
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.6
The magnitude of the present input true power.
WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.2.2.1.7
.1.3.6.1.4.1.850.1.1.3.1.3.3.1 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsOutputTable'
The output details of each ups in the device table. This is a sparse
dependent table, and will contain the number of entries based upon the
number of upss managed by the agent as reported by tlpUpsIdentNumUps.
tlpUpsOutputEntry row .1.3.6.1.4.1.850.1.1.3.1.3.3.1.1
An entry containing information applicable to a particular
output line managed by this agent.
Indexes
Column Syntax OID
The present source of output power. The enumeration none(2)
indicates that there is no source of output power (and
therefore no output power), for example, the system has opened
the output breaker.
Enumeration
Enumerated Values:
0unknown
1other
2none
3normal
4bypass
5battery
6boosting
7reducing
8second
9economy
.1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.1
The nominal value of the output voltage. This value may not be
supported on all models. If not supported, the agent reports
ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.2
The present output frequency. The output frequency on most ups
devices is common across all output lines. Some ups devices, however,
maintain the output frequency per each line. If a common frequency is
supported by the…
0.1 HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.3
The VA Rating of the ups. This value may not be
supported on all models. If not supported, the agent reports
ERROR_NO_SUCH_NAME.
VASNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.3.1.1.4
.1.3.6.1.4.1.850.1.1.3.1.3.3.2 · 1 row entry · 6 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsOutputLineTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsOutputLineTable'
The output line details of each ups in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported
by tlpUpsIdentNumUps.
tlpUpsOutputLineEntry row .1.3.6.1.4.1.850.1.1.3.1.3.3.2.1
An entry containing information applicable to a particular
output line managed by this agent.
Column Syntax OID
The table row index for the ups output line.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.1
The magnitude of the present output voltage for a given output line.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.2
The output current, in hundredths of amps, for a given line. The actual
precision of this value, whether a whole number, tenths or hundredths, is
returned by tlpUpsDeviceOutputCurrentPrecision.
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.3
The present output true power.
WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.4
The percentage of the UPS power capacity presently being used on
this output line, i.e., the greater of the percent load of true
power capacity and the percent load of VA.
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.5
The present output frequency on this output line. The output frequency on
most ups devices is common across all output lines. Some ups devices, however,
maintain the output frequency per each line. If a per line frequen…
0.1 HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.3.2.1.6
.1.3.6.1.4.1.850.1.1.3.1.3.4.1 · 1 row entry · 1 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsBypassTable'
The bypass details of each ups in the device table. This is a sparse
dependent table, and will contain the number of entries based upon the
number of upss managed by the agent as reported by tlpUpsIdentNumUps.
tlpUpsBypassEntry row .1.3.6.1.4.1.850.1.1.3.1.3.4.1.1
An entry containing information applicable to all input lines per
each ups managed by this agent.
Indexes
Column Syntax OID
The present bypass frequency.
0.1 HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.4.1.1.1
.1.3.6.1.4.1.850.1.1.3.1.3.4.2 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsBypassLineTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsBypassLineTable'
The bypass line details of each ups in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported
by tlpUpsIdentNumUps.
tlpUpsBypassLineEntry row .1.3.6.1.4.1.850.1.1.3.1.3.4.2.1
An entry containing information applicable to a particular
bypass line managed by this agent.
Column Syntax OID
The bypass line identifier.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.1
The present bypass voltage.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.2
The present bypass current.
0.1 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.3
The present true power conveyed by the bypass.
WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.4.2.1.4
.1.3.6.1.4.1.850.1.1.3.1.3.5.1 · 1 row entry · 14 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsOutletTable'
The details of each ups outlet in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported
by tlpUpsIdentNumUps.
tlpUpsOutletEntry row .1.3.6.1.4.1.850.1.1.3.1.3.5.1.1
An entry containing information applicable to a particular outlet
managed by this agent.
Column Syntax OID
The table row index for the ups outlet.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.1
A user-definable string identifying the name of the outlet.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.2
A user-definable string identifying the device(s) connected to
the given outlet.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.3
The current state of the outlet.
Enumeration
Enumerated Values:
0unknown
1off
2on
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.4
Denotes whether this outlet is controllable.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.5
Reading this value will always return 0. Setting this value
to turnOff(1) will turn off the outlet. Setting this value
to turnOn(2) will turn on the outlet. Setting this value to
cycle(3) will turn the outlet off, then …
Enumerationr/w
Enumerated Values:
0idle
1turnOff
2turnOn
3cycle
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.6
The magnitude of the present output voltage for a given outlet.
If the voltage measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value will a…
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.7
The present output current, in hundredths of amps, of a given outlet.
If the current measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value …
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.8
The output power of a given outlet. If the power measurement is
not supported for an individual receptacle regardless whether
device-wide or just for this receptacle, then this value will
always return ERROR_NO_SUCH_NAM…
WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.9
The ramp action to take on a given outlet when powering on the
device. If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0remainOff
1turnOnAfterDelay
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.10
The number of seconds to delay before powering on the given outlet.
If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
secondsSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.11
The shed action to take on a given outlet when powering off the
device. If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0remainOn
1turnOffAfterDelay
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.12
The number of seconds to delay before powering off the given outlet.
If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
secondsSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.13
The tlpUpsOutletGroupIndex group index of the respective group to
which the given outlet is assigned, or zero (0) if the given
outlet is not grouped.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.1.3.5.1.1.14
.1.3.6.1.4.1.850.1.1.3.1.3.5.2 · 1 row entry · 6 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsOutletGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsOutletGroupTable'
The receptacle grouping details of each ups in device table.
This is a sparse dependent table, and will contain the number
of entries based upon the value of tlpUpsIdentNumOutletGroups per
each device.
tlpUpsOutletGroupEntry row .1.3.6.1.4.1.850.1.1.3.1.3.5.2.1
An entry containing information applicable to a particular outlet
group managed by this agent.
Column Syntax OID
The table row index for the ups outlet group.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.1
Row status for the tlpUpsOutletGroupTable
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.2
The name of this outlet group.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.3
A description for this outlet group.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.4
The current state of the outlet group. This value will report
off(1) if all outlets in the group are off, on(2) if all outlets
in the group are on, mixed(3) if some outlets in the group are
off and others are on, or unk…
Enumeration
Enumerated Values:
0unknown
1off
2on
3mixed
.1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.5
Reading this value will always return 0. Setting this value to
turnOff(1) will turn off every outlet associated with the group.
Setting this value to turnOn(2) will turn on every outlet associated
with the group. Settin…
Enumerationr/w
Enumerated Values:
0idle
1turnOff
2turnOn
3cycle
.1.3.6.1.4.1.850.1.1.3.1.3.5.2.1.6
.1.3.6.1.4.1.850.1.1.3.1.3.6.1 · 1 row entry · 2 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsWatchdogTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsWatchdogTable'
The watchdog details of each ups in device table. This is a
sparse dependent table, and will contain some subset of devices
that are upss.
tlpUpsWatchdogEntry row .1.3.6.1.4.1.850.1.1.3.1.3.6.1.1
An entry containing watchdog details for a particular ups.
Indexes
Column Syntax OID
Indicates whether or not this ups supports a watchdog reboot.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.3.6.1.1.1
The maximum number of seconds that can expire between polls that
the engine makes to the ups for data. If this time runs out, then
the ups will cycle its outputs. Set this to zero to turns disable
this feature.
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.6.1.1.2
.1.3.6.1.4.1.850.1.1.3.1.3.7.1 · 1 row entry · 2 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsFanTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsFanTable'
The fan speed of each ups in the device table. This is a sparse
dependent table, and will contain the number of entries based upon the
number of upss managed by the agent as reported by tlpUpsIdentNumFans.
tlpUpsFanEntry row .1.3.6.1.4.1.850.1.1.3.1.3.7.1.1
An entry containing information applicable to a particular fan
managed by this agent.
Column Syntax OID
The table row index for the ups fan speed.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.7.1.1.1
The fan speed in rotations per minute.
RPMSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.3.7.1.1.2
.1.3.6.1.4.1.850.1.1.3.1.4.1 · 1 row entry · 8 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsControlTable'
The actionable controls for each ups in device table. This is a
sparse dependent table, and will contain some subset of devices
that are upss.
tlpUpsControlEntry row .1.3.6.1.4.1.850.1.1.3.1.4.1.1
An entry containing controls for a particular ups.
Indexes
Column Syntax OID
Set to TRUE to initiate a self test on the ups.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.4.1.1.1
Set to TRUE to initiate the pre-designated ramp
sequence on the ups.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.4.1.1.2
Set to TRUE to initiate the pre-designated shed
sequence on the ups.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.4.1.1.3
Set to TRUE to turn the ups on.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.4.1.1.4
Set to TRUE to turn the ups off.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.4.1.1.5
Set to TRUE to reboot the ups.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.4.1.1.6
This switches the ups in and out of bypass mode. This value returns
the current bypass mode: disable(0) if the ups is not in bypass mode,
enable(1) if the ups is in bypass mode. Set to disable(0) to exit
bypass mode, or…
Enumerationr/w
Enumerated Values:
0disable
1enable
.1.3.6.1.4.1.850.1.1.3.1.4.1.1.7
Set to TRUE to reset the tlpUpsInputWattHours calculation algorithm.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.1.4.1.1.8
.1.3.6.1.4.1.850.1.1.3.1.5.1 · 1 row entry · 18 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsConfigTable'
The configuration details of each ups in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported by
tlpUpsIdentNumUps.
tlpUpsConfigEntry row .1.3.6.1.4.1.850.1.1.3.1.5.1.1
An entry containing information applicable to all input lines per
each ups managed by this agent.
Indexes
Column Syntax OID
The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME. This value may not be writable on all models. If
not writable, the…
VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.1
The nominal input frequency. On those systems which support read-write
access to this object, if there is an attempt to set this variable to a
value that is not supported, the request must be rejected and the agent
shal…
0.1 HertzSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.2
The nominal value of the output voltage. This value may not be
supported on all models. If not supported, the agent reports
ERROR_NO_SUCH_NAME. This value may not be writable on all models. If
not writable, the value wi…
VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.3
The nominal output frequency. On those systems which support read-write
access to this object, if there is an attempt to set this variable to a
value that is not supported, the request will be rejected and the agent
wil…
0.1 HertzSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.4
The requested state of the audible alarm. When in the disabled state,
the audible alarm should never sound. The enabled state is self-
describing. Setting this object to muted(3) when the audible alarm is
sounding shall…
Enumerationr/w
Enumerated Values:
1disabled
2enabled
3muted
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.5
When disabled(0), the ups will not perform an automatic battery selftest.
When set to another value, the ups will perform an automatic selftest in
the approximate period defined by each respective enumerated value. This…
Enumerationr/w
Enumerated Values:
0disabled
1biweekly
2monthly
3quarterly
4semiannually
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.6
When enabled(1), the ups should autorestart after a shutdown from battery
mode if valid AC is applied. When disabled(0), the ups should not autorestart
when AC is restored and instead power up into standby mode.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.7
When enabled(1), the ups should perform its preconfigured ramp sequence when
valid AC is restored while in battery mode. If this value is not supported by
the ups, then this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.8
When enabled(1), the ups should perform its preconfigured shed sequence when
valid AC is lost causing the ups to enter battery mode. If this value is not
supported by the ups, then this value will always return ERROR_NO…
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.9
The lowest AC input voltage allowed to be output to the load while in bypass
mode. This setting is expressed as a percentage from nominal voltage. If this
value is not supported by the ups, then this value will always r…
percentInteger32r/w
Constraints:
range: -20--5
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.10
The highest AC input voltage allowed to be output to the load while in bypass
mode. This setting is expressed as a percentage from nominal voltage. If this
value is not supported by the ups, then this value will always …
percentInteger32r/w
Constraints:
range: 5-20
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.11
The lowest AC input voltage allowed to be output to the load while in bypass
mode. If this value is not supported by the ups, then this value will always
return ERROR_NO_SUCH_NAME.
VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.12
The highest AC input voltage allowed to be output to the load while in bypass
mode. If this value is not supported by the ups, then this value will always
return ERROR_NO_SUCH_NAME.
VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.13
This option enables or disables the ability to turn the ups on without AC
supplied. If this value is not supported by the ups, then this value will
always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.14
The configurable economic mode options for the ups. The online(0) mode is
the default configuration of most upss, which is synonymous as having the
economic mode disabled. The economy(1) mode is the typical configuratio…
Enumerationr/w
Enumerated Values:
0online
1economy
2constant50Hz
3constant60Hz
4constantAuto
5autoAdaptive
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.15
Determines the action to take if the output needs to be shut down due to a
fault condition, limited by the type of fault incurred. When configured for
bypass(0), the ups will go to bypass on a fault condition. When conf…
Enumerationr/w
Enumerated Values:
0bypass
1standby
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.16
This option governs what mode the ups should go into when AC input is
available, but the load is either off or not battery backed up. If this
setting is configured for bypass(1), the intention is that any time the ups
w…
Enumerationr/w
Enumerated Values:
0standby
1bypass
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.17
Adjusts the AC line voltage sensitivity setting. If this value is not supported
by the ups, then this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0normal
1reduced
2fullyReduced
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.18
.1.3.6.1.4.1.850.1.1.3.1.5.2 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsConfigAutoRestartTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsConfigAutoRestartTable'
The configurable automatic restart options of each ups in device table.
This is a sparse dependent table, and will contain some subset of devices
that are upss. Not all options are available on all upss.
tlpUpsConfigAutoRestartEntry row .1.3.6.1.4.1.850.1.1.3.1.5.2.1
An entry containing configurable automatic restart options for a particular
ups.
Indexes
Column Syntax OID
If enabled(1) and the ups is turned off from invert mode (via user
interaction), if line becomes valid, the ups will automatically go to line
mode. If disabled(0), the ups will turn back on and go to standby mode
instea…
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.1.5.2.1.1
If enabled(1) and power fails during a DelayBeforeStartup and line remains
invalid after the timeout expires, the ups will be set to turn back on
automatically. If disabled(0), the ups will turn back on and go to standb…
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.1.5.2.1.2
If enabled(1) and the ups is turned off from invert mode (via low voltage
cutoff), if line becomes valid, the ups will automatically go to line mode.
If disabled(0), the ups will turn back on and go to standby mode inst…
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.1.5.2.1.3
If enabled(1) and the ups is turned off from invert mode (via overload), if
line becomes valid, the ups will automatically go to line mode. If disabled(0),
the ups will turn back on and go to standby mode instead.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.1.5.2.1.4
If enabled(1) and the ups is turned off from invert mode (via over temperature),
if line becomes valid, the ups will automatically go to line mode. If disabled(0),
the ups will turn back on and go to standby mode instea…
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.1.5.2.1.5
.1.3.6.1.4.1.850.1.1.3.1.5.3 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpUpsConfigThresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpUpsConfigThresholdTable'
The configurable threshold options of each ups in device table. This
is a sparse dependent table, and will contain some subset of devices that
are upss. Not all options are available on all upss.
tlpUpsConfigThresholdEntry row .1.3.6.1.4.1.850.1.1.3.1.5.3.1
An entry containing configurable threshold options for a particular ups.
Indexes
Column Syntax OID
The number of months for a battery to be in service. The battery age alarm,
tlpUpsAlarmBatteryAgeAboveThreshold, is triggered when the current date
exceeds tlpUpsBatteryPackIdentInstallDate by tlpUpsConfigBatteryAgeThre…
monthsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.5.3.1.1
This value denotes the percentage of battery capacity remaining warning
level. The low battery alarm, tlpUpsAlarmLowBattery, is triggered when
tlpUpsEstimatedChargeRemaining drops below this value.
percentInteger32r/w
Constraints:
range: 5-95
.1.3.6.1.4.1.850.1.1.3.1.5.3.1.2
The value in seconds of tlpUpsEstimatedMinutesRemaining at which a lowBattery
condition is declared. For agents which support only discrete (discontinuous)
values, then the agent shall round up to the next supported val…
secondsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.1.5.3.1.3
This value denotes the percentage of load at which the overload condition
occurs. The overload alarm, tlpUpsAlarmOutputOverload, is triggered when the
percentage of output load exceeds this value.
percentInteger32r/w
Constraints:
range: 5-105
.1.3.6.1.4.1.850.1.1.3.1.5.3.1.4
.1.3.6.1.4.1.850.1.1.3.2.1.2 · 1 row entry · 8 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduIdentTable'
The identity details of each pdu in device table. This is a
sparse dependent table, and will contain some subset of devices
that are pdus.
tlpPduIdentEntry row .1.3.6.1.4.1.850.1.1.3.2.1.2.1
An entry containing details for a particular pdu.
Indexes
Column Syntax OID
The number of input lines supported by the pdu.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.1.2.1.1
The number of output lines supported by the pdu.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.1.2.1.2
The number of phases supported by the pdu.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.1.2.1.3
The number of receptacles supported by the pdu.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.1.2.1.4
The number of receptacle groups supported by the pdu.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.1.2.1.5
The number of circuits supported by the pdu.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.1.2.1.6
The number of monitored bank breakers supported by the pdu.
If the pdu has breakers that are not monitored by the device,
the value of zero(0) will be returned.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.1.2.1.7
The number of heatsink thermistors supported by the pdu.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.1.2.1.8
.1.3.6.1.4.1.850.1.1.3.2.1.3 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduSupportsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduSupportsTable'
The supported details of each pdu in device table. This is a
sparse dependent table, and will contain some subset of devices
that are pdus.
tlpPduSupportsEntry row .1.3.6.1.4.1.850.1.1.3.2.1.3.1
An entry containing supported details for a particular pdu.
Indexes
Column Syntax OID
Indicates whether the pdu supports Cisco EnergyWise.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.1.3.1.1
Indicates whether the pdu supports ramping and shedding.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.1.3.1.2
Indicates whether the pdu supports outlet groups.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.1.3.1.3
Indicates whether the pdu reports individual receptacle current
and power measurements. Devices that do not support individual
receptacle measurements will always return ERROR_NO_SUCH_NAME for
tlpPduOutletCurrent and tl…
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.1.3.1.4
Indicates whether the pdu reports individual receptacle voltage
measurements. Devices that do not support individual receptacle
measurements will always return ERROR_NO_SUCH_NAME for
tlpPduOutletVoltage.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.1.3.1.5
.1.3.6.1.4.1.850.1.1.3.2.1.4 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduDisplayTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduDisplayTable'
The display details of each pdu in device table. This is a
sparse dependent table, and will contain some subset of devices
that are pdus.
tlpPduDisplayEntry row .1.3.6.1.4.1.850.1.1.3.2.1.4.1
An entry containing display details for a particular pdu.
Indexes
Column Syntax OID
Indicates the display scheme of the LED display. The value
schemeReverse(0) indicates the tricolor LED indicator uses an
alternate pattern. The value schemeNormal(1) indicates the
LED indicator uses the standard pattern…
Enumerationr/w
Enumerated Values:
0schemeReverse
1schemeNormal
.1.3.6.1.4.1.850.1.1.3.2.1.4.1.1
Indicates the physical orientation of the LED display. The value
displayNormal(0) indicates the display is right-side-up (normal).
The value displayReverse(1) indicates the display is upside-down.
This value may not be …
Enumerationr/w
Enumerated Values:
0displayNormal
1displayReverse
.1.3.6.1.4.1.850.1.1.3.2.1.4.1.2
Indicates whether the LED display automatically scrolls through
displaying status values.
Enumerationr/w
Enumerated Values:
0scrollDisabled
1scrollEnabled
.1.3.6.1.4.1.850.1.1.3.2.1.4.1.3
Indicates the intensity, as a percentage, of the LED display. The
value intensity100(4) indicates the display is at 100% intensity.
The other values indicate the display is at a lesser intensity based
upon the respectiv…
Enumerationr/w
Enumerated Values:
1intensity25
2intensity50
3intensity75
4intensity100
.1.3.6.1.4.1.850.1.1.3.2.1.4.1.4
Indicates the units of measurement displayed on the LED display.
The value normal(0) indicates that a temperature value, for example,
is displayed in degrees Fahrenheit. The value metric(1) indicates a
temperature value…
Enumerationr/w
Enumerated Values:
0normal
1metric
.1.3.6.1.4.1.850.1.1.3.2.1.4.1.5
.1.3.6.1.4.1.850.1.1.3.2.2.1 · 1 row entry · 11 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduDeviceTable'
The device details of each pdu in device table. This is a
sparse dependent table, and will contain some subset of devices
that are pdus.
tlpPduDeviceEntry row .1.3.6.1.4.1.850.1.1.3.2.2.1.1
An entry containing device details for a particular pdu.
Indexes
Column Syntax OID
The current state of the main output of the device.
Enumeration
Enumerated Values:
0unknown
1off
2on
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.1
Indicates whether or not the main output is controllable, and whether
the ups can be turned off and on.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.2
Reading this value will always return 0. Setting this value to
turnOff(1) will turn off the main output of the ups. Setting this
value to turnOn(2) will turn on the main output of the ups. Setting
this value to cycle(3)…
Enumerationr/w
Enumerated Values:
0idle
1turnOff
2turnOn
3cycle
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.3
The configurable delay value, which sets the amount of additional
time a given device will wait before it connects to a valid AC
source. By default the delay value is set to 0. For devices with
multiple AC input sources…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.4
The total input power rating of all phases on the device. This
value may not be supported on all models. If not supported, this
value will always return ERROR_NO_SUCH_NAME.
WattsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.5
The ambient temperature at or near the PDU casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.6
The ambient temperature at or near the PDU casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.7
The percentage of imbalance of the three phases. This value is in
the range from 0% imbalance to 100% imbalance. The lower the value,
the better balanced the phases are. If all load is on a single phase,
the imbalance i…
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.8
The AC output total power for all circuits.
WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.9
The aggregate power factor of all phases.
0.1 WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.10
Output current is reported by tlpPduOutputCurrent, tlpPduOutputCurrentMin
and tlpPduOutputCurrentMax. These values are all reported in hundredths(0.01A),
which accommodates all models; however, on any given device the…
Enumeration
Enumerated Values:
0wholeNumber
1tenths
2hundredths
.1.3.6.1.4.1.850.1.1.3.2.2.1.1.11
.1.3.6.1.4.1.850.1.1.3.2.3.1.1 · 1 row entry · 10 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduInputTable'
The input details of each pdu in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the number of pdus managed by the agent as reported by tlpPduIdentNumPdus.
tlpPduInputEntry row .1.3.6.1.4.1.850.1.1.3.2.3.1.1.1
An entry containing information applicable to a particular pdu managed
by this agent.
Indexes
Column Syntax OID
The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.1
The nominal value of the input line voltage as measured from
phase to phase. This value may not be supported on all models.
If not supported, this value will always return zero.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.2
The nominal value of the input line voltage as measured from
phase to neutral. This value may not be supported on all models.
If not supported, this value will always return zero.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.3
The minimum line voltage allowed before the unit disconnects the
AC input connection. This value may not be writable on all models.
If not writable, the value will be rejected and an appropriate error
message will be re…
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.4
The lower boundary value of tlpPduInputLowTransferVoltage as dictated
by the hardware of the unit.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.5
The upper boundary value of tlpPduInputLowTransferVoltage as dictated
by the hardware of the unit.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.6
The maximum line voltage allowed before the unit disconnects the
AC input connection. This value may not be writable on all models.
If not writable, the value will be rejected and an appropriate error
message will be re…
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.7
The lower boundary value of tlpPduInputHighTransferVoltage as dictated
by the hardware of the unit.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.8
The upper boundary value of tlpPduInputHighTransferVoltage as dictated
by the hardware of the unit.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.9
The capacity of each phase conductor in the pdu limited by the AC input
cord or any other potential limiting factors unique to a given unit.
AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.1.1.10
.1.3.6.1.4.1.850.1.1.3.2.3.1.2 · 1 row entry · 7 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduInputPhaseTable'
The input phase details of each pdu in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the value of tlpPduIdentNumInputs and tlpPduIdentNumPhases per each
device.
tlpPduInputPhaseEntry row .1.3.6.1.4.1.850.1.1.3.2.3.1.2.1
An entry containing information applicable to a particular input
phase managed by this agent.
Column Syntax OID
The table row index for the pdu phase.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.1
Denotes whether measurements are phase to neutral(0) or phase
to phase(1).
Enumeration
Enumerated Values:
0phaseToNeutral
1phaseToPhase
.1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.2
The present input frequency for a given phase.
0.1 HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.3
The magnitude of the present input voltage for a given phase.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.4
The minimum input voltage value since the last reset of this
value for a given phase. If any value is written to either
tlpPduInputVoltageMin or tlpPduInputVoltageMax, both will be
reset to their appropriate minimum and…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.5
The maximum input voltage value since the last reset of this
value for a given phase. If any value is written to either
tlpPduInputVoltageMin or tlpPduInputVoltageMax, both will be
reset to their appropriate minimum and…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.6
The magnitude of the present input current for a given phase.
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.1.2.1.7
.1.3.6.1.4.1.850.1.1.3.2.3.2.1 · 1 row entry · 14 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduOutputTable'
The output details of each pdu in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the value of tlpPduIdentNumOutputs per each device.
tlpPduOutputEntry row .1.3.6.1.4.1.850.1.1.3.2.3.2.1.1
An entry containing output information applicable to a particular
phase managed by this agent.
Column Syntax OID
The table row index for the pdu phase.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.1
Indicates the phase associated with the output line.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.2
Denotes whether measurements are phase to neutral(0) or phase
to phase(1).
Enumeration
Enumerated Values:
0phaseToNeutral
1phaseToPhase
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.3
The magnitude of the present output voltage for a given output line.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.4
The output current, in hundredths of amps, for a given phase.
The actual precision of this value, whether a whole number, tenths
or hundredths, is returned by tlpPduDeviceOutputCurrentPrecision.
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.5
The minimum current, in hundredths of amps, observed for a given phase since last reset.
The actual precision of this value, whether a whole number, tenths or hundredths, is
returned by tlpPduDeviceOutputCurrentPrecisio…
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.6
The maximum current, in hundredths of amps, observed for a given phase since last reset.
The actual precision of this value, whether a whole number, tenths or hundredths, is
returned by tlpPduDeviceOutputCurrentPrecisio…
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.7
The output power for a given phase.
WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.8
The output power factor, in hundredths of a percent, for a given
phase.
0.01 percentSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.9
The present source of output power. The enumeration none(0)
indicates that there is no source of output power (and
therefore no output power), for example, the system has opened
the output breaker.
Enumeration
Enumerated Values:
0none
1normal
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.10
The present output frequency. If not supported, the agent reports ERROR_NO_SUCH_NAME.
0.1 HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.11
The calculated amount of apparent power being used.
0.01 KVASNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.12
The calculated amount of active power being used.
0.01 KWSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.13
Estimated 24 hour power consumption using present value
of tlpPduOutputCalculatedPowerKW.
0.01 KWHSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.2.1.1.14
.1.3.6.1.4.1.850.1.1.3.2.3.3.1 · 1 row entry · 17 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduOutletTable'
The receptacle status details of each pdu in device table. This
is a sparse dependent table, and will contain the number of entries
based upon the value of tlpPduIdentNumOutlets per each device.
tlpPduOutletEntry row .1.3.6.1.4.1.850.1.1.3.2.3.3.1.1
An entry containing information applicable to a particular outlet
managed by this agent.
Column Syntax OID
The table row index for the pdu outlet.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.1
A user-definable string identifying the name of the outlet.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.2
A user-definable string identifying the device(s) connected to
the given outlet.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.3
The current state of the outlet.
Enumeration
Enumerated Values:
0unknown
1off
2on
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.4
Denotes whether this outlet is controllable.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.5
Reading this value will always return 0. Setting this value
to turnOff(1) will turn off the outlet. Setting this value
to turnOn(2) will turn on the outlet. Setting this value to
cycle(3) will turn the outlet off, then …
Enumerationr/w
Enumerated Values:
0idle
1turnOff
2turnOn
3cycle
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.6
The magnitude of the present output voltage for a given outlet.
If the voltage measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value will a…
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.7
The present output current, in hundredths of amps, of a given outlet.
If the current measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value …
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.8
The output power of a given outlet. If the power measurement is
not supported for an individual receptacle regardless whether
device-wide or just for this receptacle, then this value will
always return ERROR_NO_SUCH_NAM…
WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.9
The ramp action to take on a given outlet when powering on the
device. If this receptacle is not controllable, as denoted by
tlpPduOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0remainOff
1turnOnAfterDelay
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.10
The number of seconds to delay before powering on the given outlet.
If this receptacle is not controllable, as denoted by
tlpPduOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
secondsSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.11
The shed action to take on a given outlet when powering off the
device. If this receptacle is not controllable, as denoted by
tlpPduOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0remainOn
1turnOffAfterDelay
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.12
The number of seconds to delay before powering off the given outlet.
If this receptacle is not controllable, as denoted by
tlpPduOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
secondsSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.13
The tlpPduOutletGroupIndex group index of the respective group to
which the given outlet is assigned, or zero (0) if the given
outlet is not grouped.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.14
Indicates on which bank the given outlet is located.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.15
Indicates on which circuit the given outlet is wired.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.16
Indicates on which phase or phases the given outlet is
associated. For single phase devices, this object will
always return phase1(1). For 3-phase devices with outlets
wired to a single phase, this object will return ph…
Enumeration
Enumerated Values:
0unknown
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.850.1.1.3.2.3.3.1.1.17
.1.3.6.1.4.1.850.1.1.3.2.3.3.2 · 1 row entry · 6 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduOutletGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduOutletGroupTable'
The receptacle grouping details of each pdu in device table.
This is a sparse dependent table, and will contain the number
of entries based upon the value of tlpPduIdentNumOutletGroups per
each device.
tlpPduOutletGroupEntry row .1.3.6.1.4.1.850.1.1.3.2.3.3.2.1
An entry containing information applicable to a particular outlet
group managed by this agent.
Column Syntax OID
The table row index for the pdu outlet group.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.1
Row status for the tlpPduOutletGroupTable
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.2
The name of this outlet group.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.3
A description for this outlet group.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.4
The current state of the outlet group. This value will report
off(1) if all outlets in the group are off, on(2) if all outlets
in the group are on, mixed(3) if some outlets in the group are
off and others are on, or unk…
Enumeration
Enumerated Values:
0unknown
1off
2on
3mixed
.1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.5
Reading this value will always return 0. Setting this value to
turnOff(1) will turn off every outlet associated with the group.
Setting this value to turnOn(2) will turn on every outlet associated
with the group. Settin…
Enumerationr/w
Enumerated Values:
1turnOff
2turnOn
3cycle
.1.3.6.1.4.1.850.1.1.3.2.3.3.2.1.6
.1.3.6.1.4.1.850.1.1.3.2.3.4.1 · 1 row entry · 10 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduCircuitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduCircuitTable'
A list of pdu circuit table entries.  The number of entries
is given by the value of tlpPduIdentNumCircuits.
tlpPduCircuitEntry row .1.3.6.1.4.1.850.1.1.3.2.3.4.1.1
An entry containing information applicable to a particular circuit
managed by this agent.
Column Syntax OID
The table row index for the pdu circuit.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.1
Indicates on which phase or phases the given circuit is
wired. For single phase devices, this object will always
return phase1(1). For 3-phase devices with outlets wired
to a single phase, this object will return phase1…
Enumeration
Enumerated Values:
0unknown
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.2
The input voltage for a circuit.
0.1 VoltsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.3
The total current, in hundredths of amps, for all receptacles
in a given circuit.
0.01 AmpsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.4
The current capacity, in hundredths of amps, of a circuit in
the system limited by the circuit breaker or wiring used in a
given unit.
0.01 AmpsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.5
The minimum total current, in hundredths of amps, for
all receptacles in a given circuit since last reset.
0.01 AmpsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.6
The maximum total current, in hundredths of amps, for
all receptacles in a given circuit since last reset.
0.01 AmpsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.7
The total power for all receptacles in a given circuit.
WattsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.8
The power factor for all receptacles in a given circuit.
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.9
The percentage of utilization of a given circuit. This is typically
a calculation of tlpPduCircuitTotalCurrent / tlpPduCircuitCurrentLimit.
0.01 percentSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.4.1.1.10
.1.3.6.1.4.1.850.1.1.3.2.3.5.1 · 1 row entry · 2 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduBreakerTable'
A list of pdu bank breaker table entries. The number of entries
is given by the value of tlpPduIdentNumBreakers.
tlpPduBreakerEntry row .1.3.6.1.4.1.850.1.1.3.2.3.5.1.1
An entry containing information applicable to a particular bank
breaker managed by this agent.
Column Syntax OID
The table row index for the pdu bank breaker.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.5.1.1.1
Indicates whether the bank breaker is open(0), closed(1) or not
installed(2).
Enumeration
Enumerated Values:
0open
1closed
2notInstalled
.1.3.6.1.4.1.850.1.1.3.2.3.5.1.1.2
.1.3.6.1.4.1.850.1.1.3.2.3.6.1 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduHeatsinkTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduHeatsinkTable'
A list of pdu heatsink thermistor table entries. The number of entries
is given by the value of tlpPduIdentNumHeatsinks.
tlpPduHeatsinkEntry row .1.3.6.1.4.1.850.1.1.3.2.3.6.1.1
An entry containing information applicable to a particular heatsink
thermistor managed by this agent.
Column Syntax OID
The table row index for the pdu heatsink thermistor.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.1
Indicates whether the heatsink thermistor is available. The entry
will return notAvailable(0) if a thermistor is either non-existent or
disconnected, or available(1) when connected.
Enumeration
Enumerated Values:
0notAvailable
1available
.1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.2
The temperature at the heatsink thermistor in tenths degrees Celsius.
Heatsink temperature measurements are not supported on all models. If
not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.3
The temperature at the heatsink thermistor in tenths degrees Fahrenheit.
Heatsink temperature measurements are not supported on all models. If
not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.2.3.6.1.1.4
.1.3.6.1.4.1.850.1.1.3.2.4.1 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduControlTable'
The actionable controls for each pdu in device table. This is a
sparse dependent table, and will contain some subset of devices
that are pdus.
tlpPduControlEntry row .1.3.6.1.4.1.850.1.1.3.2.4.1.1
An entry containing controls for a particular pdu.
Indexes
Column Syntax OID
Set to TRUE to initiate the pre-designated ramp
sequence on the pdu.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.4.1.1.1
Set to TRUE to initiate the pre-designated shed
sequence on the pdu.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.4.1.1.2
Set to TRUE to turn the pdu on.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.4.1.1.3
Set to TRUE to turn the pdu off.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.4.1.1.4
Set to TRUE to reboot the pdu.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.2.4.1.1.5
.1.3.6.1.4.1.850.1.1.3.2.5.1 · 1 row entry · 1 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduConfigTable'
The configuration options of each pdu in device table. This
is a sparse dependent table, and will contain some subset of
devices that are pdus. Not all options are available on all
pdus.
tlpPduConfigEntry row .1.3.6.1.4.1.850.1.1.3.2.5.1.1
An entry containing configuration options for a particular pdu.
Indexes
Column Syntax OID
The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME. This value may not be writable on all models. If
not writable, the…
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.5.1.1.1
.1.3.6.1.4.1.850.1.1.3.2.5.2 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpPduConfigPhaseThresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpPduConfigPhaseThresholdTable'
The configuration options of each pdu in device table. This
is a sparse dependent table, and will contain some subset of
devices that are pdus. Not all options are available on all
pdus.
tlpPduConfigPhaseThresholdEntry row .1.3.6.1.4.1.850.1.1.3.2.5.2.1
An entry containing threshold configuration options for a particular pdu.
Column Syntax OID
The table row index for the pdu phase.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.5.2.1.1
The threshold tolerance value used together with output current high/low
threshold to evaluate output current high/low condition.
0.1 AmpsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.5.2.1.2
The value at which a output current high condition is declared.
0.1 AmpsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.5.2.1.3
The value at which a output current low condition is declared.
0.1 AmpsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.2.5.2.1.4
.1.3.6.1.4.1.850.1.1.3.3.1.2 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpEnvIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpEnvIdentTable'
The identity details of each envirosense in device table. This is a
sparse dependent table, and will contain some subset of devices
that are envirosenses.
tlpEnvIdentEntry row .1.3.6.1.4.1.850.1.1.3.3.1.2.1
An entry containing details for a particular envirosense.
Indexes
Column Syntax OID
Indicates whether or not temperature is supported.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.3.1.2.1.1
Indicates whether or not temperature is supported.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.3.1.2.1.2
The number of input contacts supported by the envirosense.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.3.1.2.1.3
The number of output contacts supported by the envirosense.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.3.1.2.1.4
.1.3.6.1.4.1.850.1.1.3.3.3.1 · 1 row entry · 3 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpEnvTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpEnvTemperatureTable'
The temperature details of each envirosense in device table. The
number of entries is given by the value of tlpDevicesNumDevices.
tlpEnvTemperatureEntry row .1.3.6.1.4.1.850.1.1.3.3.3.1.1
An entry containing temperature details for a particular
envirosense.
Indexes
Column Syntax OID
The ambient temperature.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.3.3.1.1.1
The ambient temperature.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.3.3.1.1.2
Indicates whether or not temperature is in alarm.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.3.3.1.1.3
.1.3.6.1.4.1.850.1.1.3.3.3.2 · 1 row entry · 2 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpEnvHumidityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpEnvHumidityTable'
The humidity details of each envirosense in device table. The
number of entries is given by the value of tlpDevicesNumDevices.
tlpEnvHumidityEntry row .1.3.6.1.4.1.850.1.1.3.3.3.2.1
An entry containing humidity details for a particular
envirosense.
Indexes
Column Syntax OID
The ambient humidity.
percentInteger32
Constraints:
range: 0-100
.1.3.6.1.4.1.850.1.1.3.3.3.2.1.1
Indicates whether or not humidity is in alarm.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.3.3.2.1.2
.1.3.6.1.4.1.850.1.1.3.3.3.3 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpEnvInputContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpEnvInputContactTable'
The input contact details of each envirosense in device table.
The number of entries is given by the value of tlpDevicesNumDevices.
tlpEnvInputContactEntry row .1.3.6.1.4.1.850.1.1.3.3.3.3.1
An entry containing input contact details for a particular
envirosense.
Column Syntax OID
The table row index for the envirosense input contact details.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.3.3.3.1.1
The name or description of the contact.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.3.3.3.1.2
The normal operating position of the contact.
Enumerationr/w
Enumerated Values:
0open
1closed
.1.3.6.1.4.1.850.1.1.3.3.3.3.1.3
The current state of the contact.
Enumeration
Enumerated Values:
0open
1closed
.1.3.6.1.4.1.850.1.1.3.3.3.3.1.4
Indicates whether or not the contact is in alarm.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.3.3.3.1.5
.1.3.6.1.4.1.850.1.1.3.3.3.4 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpEnvOutputContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpEnvOutputContactTable'
The output contact details of each envirosense in device table.
The number of entries is given by the value of tlpDevicesNumDevices.
tlpEnvOutputContactEntry row .1.3.6.1.4.1.850.1.1.3.3.3.4.1
An entry containing output contact details for a particular
envirosense.
Column Syntax OID
The table row index for the envirosense output contact details.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.3.3.4.1.1
The name or description of the contact.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.3.3.4.1.2
The normal operating position of the contact.
Enumerationr/w
Enumerated Values:
0open
1closed
.1.3.6.1.4.1.850.1.1.3.3.3.4.1.3
The current state of the contact.
Enumerationr/w
Enumerated Values:
0open
1closed
.1.3.6.1.4.1.850.1.1.3.3.3.4.1.4
Indicates whether or not the contact is in alarm.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.3.3.4.1.5
.1.3.6.1.4.1.850.1.1.3.3.5.1 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpEnvConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpEnvConfigTable'
The configuration options of each envirosense in device table.
This is a sparse dependent table, and will contain some subset of
devices that are envirosenses. Not all options are available on
all envirosenses.
tlpEnvConfigEntry row .1.3.6.1.4.1.850.1.1.3.3.5.1.1
An entry containing configuration options for a particular
envirosenses.
Indexes
Column Syntax OID
The lower alarm limit for ambient temperature.
degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.3.5.1.1.1
The upper alarm limit for ambient temperature.
degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.3.5.1.1.2
The lower alarm limit for ambient humidity.
percentInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.850.1.1.3.3.5.1.1.3
The upper alarm limit for ambient humidity.
percentInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.850.1.1.3.3.5.1.1.4
.1.3.6.1.4.1.850.1.1.3.4.1.2 · 1 row entry · 8 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsIdentTable'
The identity details of each ats in device table. This is a
sparse dependent table, and will contain some subset of devices
that are atss.
tlpAtsIdentEntry row .1.3.6.1.4.1.850.1.1.3.4.1.2.1
An entry containing details for a particular ats.
Indexes
Column Syntax OID
The number of inputs supported by the ats.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.1.2.1.1
The number of outputs supported by the ats.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.1.2.1.2
The number of phases per input supported by the ats.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.1.2.1.3
The number of receptacles supported by the ats.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.1.2.1.4
The number of receptacle groups supported by the ats.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.1.2.1.5
The number of circuits supported by the ats.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.1.2.1.6
The number of monitored bank breakers supported by the ats.
If the ats has breakers that are not monitored by the device,
the value of zero(0) will be returned.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.1.2.1.7
The number of heatsink thermistors supported by the ats.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.1.2.1.8
.1.3.6.1.4.1.850.1.1.3.4.1.3 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsSupportsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsSupportsTable'
The supported details of each ats in device table. This is a
sparse dependent table, and will contain some subset of devices
that are atss.
tlpAtsSupportsEntry row .1.3.6.1.4.1.850.1.1.3.4.1.3.1
An entry containing supported details for a particular ats.
Indexes
Column Syntax OID
Indicates whether the ats supports Cisco EnergyWise.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.1.3.1.1
Indicates whether the ats supports ramping and shedding.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.1.3.1.2
Indicates whether the ats supports outlet groups.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.1.3.1.3
Indicates whether the ats reports individual receptacle current
and power measurements. Devices that do not support individual
receptacle measurements will always return ERROR_NO_SUCH_NAME for
tlpAtsOutletCurrent and tl…
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.1.3.1.4
Indicates whether the ats reports individual receptacle voltage
measurements. Devices that do not support individual receptacle
measurements will always return ERROR_NO_SUCH_NAME for
tlpAtsOutletVoltage.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.1.3.1.5
.1.3.6.1.4.1.850.1.1.3.4.1.4 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsDisplayTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsDisplayTable'
The display details of each ats in device table. This is a
sparse dependent table, and will contain some subset of devices
that are atss.
tlpAtsDisplayEntry row .1.3.6.1.4.1.850.1.1.3.4.1.4.1
An entry containing display details for a particular ats.
Indexes
Column Syntax OID
Indicates the display scheme of the LED display. The value
schemeReverse(0) indicates the tricolor LED indicator uses an
alternate pattern. The value schemeNormal(1) indicates the
LED indicator uses the standard pattern…
Enumerationr/w
Enumerated Values:
0schemeReverse
1schemeNormal
.1.3.6.1.4.1.850.1.1.3.4.1.4.1.1
Indicates the physical orientation of the LED display. The value
displayNormal(0) indicates the display is right-side-up (normal).
The value displayReverse(1) indicates the display is upside-down.
This value may not be …
Enumerationr/w
Enumerated Values:
0displayNormal
1displayReverse
.1.3.6.1.4.1.850.1.1.3.4.1.4.1.2
Indicates whether the LED display automatically scrolls through
displaying status values.
Enumerationr/w
Enumerated Values:
0scrollDisabled
1scrollEnabled
.1.3.6.1.4.1.850.1.1.3.4.1.4.1.3
Indicates the intensity, as a percentage, of the LED display. The
value intensity100(4) indicates the display is at 100% intensity.
The other values indicate the display is at a lesser intensity based
upon the respectiv…
Enumerationr/w
Enumerated Values:
1intensity25
2intensity50
3intensity75
4intensity100
.1.3.6.1.4.1.850.1.1.3.4.1.4.1.4
Indicates the units of measurement displayed on the LED display.
The value normal(0) indicates that a temperature value, for example,
is displayed in degrees Fahrenheit. The value metric(1) indicates a
temperature value…
Enumerationr/w
Enumerated Values:
0normal
1metric
.1.3.6.1.4.1.850.1.1.3.4.1.4.1.5
.1.3.6.1.4.1.850.1.1.3.4.2.1 · 1 row entry · 12 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsDeviceTable'
The device details of each ats in device table. This is a
sparse dependent table, and will contain some subset of devices
that are atss.
tlpAtsDeviceEntry row .1.3.6.1.4.1.850.1.1.3.4.2.1.1
An entry containing device details for a particular ats.
Indexes
Column Syntax OID
The current state of the main output of the device.
Enumeration
Enumerated Values:
0unknown
1off
2on
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.1
Indicates whether or not the main output is controllable, and whether
the ups can be turned off and on.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.2
Reading this value will always return 0. Setting this value to
turnOff(1) will turn off the main output of the ups. Setting this
value to turnOn(2) will turn on the main output of the ups. Setting
this value to cycle(3)…
Enumerationr/w
Enumerated Values:
0idle
1turnOff
2turnOn
3cycle
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.3
The configurable delay value, which sets the amount of additional
time a given device will wait before it connects to a valid AC
source. By default the delay value is set to 0. For devices with
multiple AC input sources…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.4
The total input power rating of all phases on the device. This
value may not be supported on all models. If not supported, this
value will always return ERROR_NO_SUCH_NAME.
WattsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.5
The ambient temperature at or near the ats casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.6
The ambient temperature at or near the ats casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.7
The percentage of imbalance of the three phases. This value is in
the range from 0% imbalance to 100% imbalance. The lower the value,
the better balanced the phases are. If all load is on a single phase,
the imbalance i…
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.8
The AC output total power for all circuits.
WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.9
The aggregate power factor of all phases.
0.1 WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.10
Output current is reported by tlpAtsOutputCurrent, tlpAtsOutputCurrentMin
and tlpAtsOutputCurrentMax. These values are all reported in hundredths
(0.01A), which accommodates all models; however, on any given device the
Enumeration
Enumerated Values:
0none
1tenths
2hundredths
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.11
Indicates whether or not the ats is in a system fault condition. When the
ats is in such a fault condition, the condition can be cleared with
tlpAtsControlResetGeneralFault.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.2.1.1.12
.1.3.6.1.4.1.850.1.1.3.4.3.1.1 · 1 row entry · 15 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsInputTable'
The input details of each ats in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the number of atss managed by the agent as reported by tlpAtsIdentNumAts.
tlpAtsInputEntry row .1.3.6.1.4.1.850.1.1.3.4.3.1.1.1
An entry containing information applicable to a particular primary
input phase managed by this agent.
Indexes
Column Syntax OID
The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.1
The nominal value of the input line voltage as measured from
phase to phase. This value may not be supported on all models.
If not supported, this value will always return zero.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.2
The nominal value of the input line voltage as measured from
phase to neutral. This value may not be supported on all models.
If not supported, this value will always return zero.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.3
The minimum line voltage allowed before the unit disconnects the
AC input connection.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.4
The lower boundary value of tlpAtsInputBadTransferVoltage as dictated
by the hardware of the unit.
VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.5
The upper boundary value of tlpAtsInputBadTransferVoltage as dictated
by the hardware of the unit.
VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.6
The maximum line voltage allowed before the unit disconnects the
AC input connection.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.7
The lower boundary value of tlpAtsInputHighTransferVoltage as dictated
by the hardware of the unit.
VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.8
The upper boundary value of tlpAtsInputHighTransferVoltage as dictated
by the hardware of the unit.
VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.9
The voltage level at which the device will transition between sources.
VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.10
The minimum line voltage allowed before the device disconnects the AC input
connection.
VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.11
The determination as to which of two AC input lines are available.
The agent will return either inputSourceA(1) or inputSourceB(2) if
only one line is available, or inputSourceAB(3) if both lines are
available. The agen…
Enumeration
Enumerated Values:
0none
1inputSourceA
2inputSourceB
3inputSourceAB
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.12
The determination as to which one of two AC input lines is in use. Not all
devices support the reporting of which source is currently in use. If not
supported, this value will always return ERROR_NO_SUCH_NAME.
Enumeration
Enumerated Values:
0inputSourceA
1inputSourceB
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.13
The number of times the device transitions between primary and secondary
sources. Most devices are limited to 65533 transitions, after which the
value will not increment. If not supported, this value will always return
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.14
The capacity of each phase conductor in the ats limited by the AC input
cord or any other potential limiting factors unique to a given unit. If not
supported, this value will always return ERROR_NO_SUCH_NAME.
AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.1.1.15
.1.3.6.1.4.1.850.1.1.3.4.3.1.2 · 1 row entry · 8 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsInputPhaseTable'
The input phase details of each ats in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the value of tlpAtsIdentNumInputs and tlpAtsIdentNumPhases per each
device.
tlpAtsInputPhaseEntry row .1.3.6.1.4.1.850.1.1.3.4.3.1.2.1
An entry containing information applicable to a particular primary
input phase managed by this agent.
Column Syntax OID
The table row index for the input line on the ats.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.1
The table row index for the input phase for the input line.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.2
Denotes whether measurements are phase to neutral(0) or phase
to phase(1).
Enumeration
Enumerated Values:
0phaseToNeutral
1phaseToPhase
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.3
The present input frequency for a given phase.
0.1 HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.4
The magnitude of the present input voltage for a given phase.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.5
The minimum input voltage value since the last reset of this
value for a given phase. If any value is written to either
tlpAtsInputVoltageMin or tlpAtsInputVoltageMax, both
will be reset to their appropriate minimum and…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.6
The maximum input voltage value since the last reset of this
value for a given phase. If any value is written to either
tlpAtsInputVoltageMin or tlpAtsInputVoltageMax, both
will be reset to their appropriate minimum and…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.7
The magnitude of the present input current for a given phase.
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.1.2.1.8
.1.3.6.1.4.1.850.1.1.3.4.3.2.1 · 1 row entry · 14 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsOutputTable'
The output details of each ats in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the value of tlpAtsIdentNumOutputs per each device.
tlpAtsOutputEntry row .1.3.6.1.4.1.850.1.1.3.4.3.2.1.1
An entry containing output information applicable to a particular
phase managed by this agent.
Column Syntax OID
The table row index for the ats phase.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.1
Indicates the phase associated with the output line.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.2
Denotes whether measurements are phase to neutral(0) or phase
to phase(1).
Enumeration
Enumerated Values:
0phaseToNeutral
1phaseToPhase
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.3
The magnitude of the present output voltage for a given output line.
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.4
The output current, in hundredths of amps, for a given phase.
The actual precision of this value, whether a whole number, tenths
or hundredths, is returned by tlpAtsDeviceOutputCurrentPrecision.
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.5
The minimum current, in hundredths of amps, observed for a given phase
since last reset. The actual precision of this value, whether a whole number,
tenths or hundredths, is returned by tlpAtsDeviceOutputCurrentPrecisio…
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.6
The maximum current, in hundredths of amps, observed for a given phase
since last reset. The actual precision of this value, whether a whole number,
tenths or hundredths, is returned by tlpAtsDeviceOutputCurrentPrecisio…
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.7
The output power for a given phase.
WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.8
The output power factor, in hundredths of a percent, for a given
phase.
0.01 percentSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.9
The present source of output power. The enumeration none(0)
indicates that there is no source of output power (and
therefore no output power), for example, the system has opened
the output breaker.
Enumeration
Enumerated Values:
0none
1normal
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.10
The present output frequency. If not supported, the agent reports ERROR_NO_SUCH_NAME.
0.1 HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.11
The calculated amount of apparent power being used.
0.01 KVASNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.12
The calculated amount of active power being used.
0.01 KWSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.13
Estimated 24 hour power consumption using present value
of tlpAtsOutputCalculatedPowerKW.
0.01 KWHSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.2.1.1.14
.1.3.6.1.4.1.850.1.1.3.4.3.3.1 · 1 row entry · 17 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsOutletTable'
The receptacle status details of each ats in device table. This
is a sparse dependent table, and will contain the number of entries
based upon the value of tlpAtsIdentNumOutlets per each device.
tlpAtsOutletEntry row .1.3.6.1.4.1.850.1.1.3.4.3.3.1.1
An entry containing information applicable to a particular outlet
managed by this agent.
Column Syntax OID
The table row index for the ats outlet.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.1
A user-definable string identifying the name of the outlet.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.2
A user-definable string identifying the device(s) connected to
the given outlet.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.3
The current state of the outlet.
Enumeration
Enumerated Values:
0unknown
1off
2on
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.4
Denotes whether this outlet is controllable.
SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.5
Reading this value will always return 0. Setting this value
to turnOff(1) will turn off the outlet. Setting this value
to turnOn(2) will turn on the outlet. Setting this value to
cycle(3) will turn the outlet off, then …
Enumerationr/w
Enumerated Values:
0idle
1turnOff
2turnOn
3cycle
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.6
The magnitude of the present output voltage for a given outlet.
If the voltage measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value will a…
0.1 VoltsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.7
The present output current, in hundredths of amps, of a given outlet.
If the current measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value …
0.01 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.8
The output power of a given outlet. If the power measurement is
not supported for an individual receptacle regardless whether
device-wide or just for this receptacle, then this value will
always return ERROR_NO_SUCH_NAM…
WattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.9
The ramp action to take on a given outlet when powering on the
device. If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0remainOff
1turnOnAfterDelay
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.10
The number of seconds to delay before powering on the given outlet.
If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
secondsSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.11
The shed action to take on a given outlet when powering off the
device. If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0remainOn
1turnOffAfterDelay
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.12
The number of seconds to delay before powering off the given outlet.
If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME.
secondsSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.13
The tlpAtsOutletGroupIndex group index of the respective group to
which the given outlet is assigned, or zero (0) if the given
outlet is not grouped.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.14
Indicates on which bank the given outlet is located.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.15
Indicates on which circuit the given outlet is wired.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.16
Indicates on which phase or phases the given outlet is
associated. For single phase devices, this object will
always return phase1(1). For 3-phase devices with outlets
wired to a single phase, this object will return ph…
Enumeration
Enumerated Values:
0unknown
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.850.1.1.3.4.3.3.1.1.17
.1.3.6.1.4.1.850.1.1.3.4.3.3.2 · 1 row entry · 6 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsOutletGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsOutletGroupTable'
The receptacle grouping details of each ats in device table.
This is a sparse dependent table, and will contain the number
of entries based upon the value of tlpAtsIdentNumOutletGroups per
each device.
tlpAtsOutletGroupEntry row .1.3.6.1.4.1.850.1.1.3.4.3.3.2.1
An entry containing information applicable to a particular outlet
group managed by this agent.
Column Syntax OID
The table row index for the ats outlet group.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.1
Row status for the tlpAtsOutletGroupTable
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.2
The name of this outlet group.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.3
A description for this outlet group.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.4
The current state of the outlet group. This value will report
off(1) if all outlets in the group are off, on(2) if all outlets
in the group are on, mixed(3) if some outlets in the group are
off and others are on, or unk…
Enumeration
Enumerated Values:
0unknown
1off
2on
3mixed
.1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.5
Reading this value will always return 0. Setting this value to
turnOff(1) will turn off every outlet associated with the group.
Setting this value to turnOn(2) will turn on every outlet associated
with the group. Settin…
Enumerationr/w
Enumerated Values:
1turnOff
2turnOn
3cycle
.1.3.6.1.4.1.850.1.1.3.4.3.3.2.1.6
.1.3.6.1.4.1.850.1.1.3.4.3.4.1 · 1 row entry · 10 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsCircuitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsCircuitTable'
A list of ats circuit table entries.  The number of entries
is given by the value of tlpAtsIdentNumCircuits.
tlpAtsCircuitEntry row .1.3.6.1.4.1.850.1.1.3.4.3.4.1.1
An entry containing information applicable to a particular circuit
managed by this agent.
Column Syntax OID
The table row index for the ats circuit.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.1
Indicates on which phase or phases the given circuit is
wired. For single phase devices, this object will always
return phase1(1). For 3-phase devices with outlets wired
to a single phase, this object will return phase1…
Enumeration
Enumerated Values:
0unknown
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.2
The input voltage for a circuit.
0.1 VoltsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.3
The total current for all receptacles in a given circuit.
0.01 AmpsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.4
The current capacity of a circuit in the system limited by
the circuit breaker or wiring used in a given unit.
0.01 AmpsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.5
The minimum total current for all receptacles in a given
circuit since last reset.
0.01 AmpsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.6
The maximum total current for all receptacles in a given
circuit since last reset.
0.01 AmpsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.7
The total power for all receptacles in a given circuit.
WattsSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.8
The power factor for all receptacles in a given circuit.
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.9
The percentage of utilization of a given circuit. This is typically
a calculation of tlpAtsCircuitTotalCurrent / tlpAtsCircuitCurrentLimit.
0.01 percentSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.4.1.1.10
.1.3.6.1.4.1.850.1.1.3.4.3.5.1 · 1 row entry · 2 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsBreakerTable'
A list of ats bank breaker table entries. The number of entries
is given by the value of tlpAtsIdentNumBreakers.
tlpAtsBreakerEntry row .1.3.6.1.4.1.850.1.1.3.4.3.5.1.1
An entry containing information applicable to a particular bank
breaker managed by this agent.
Column Syntax OID
The table row index for the ats bank breaker.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.5.1.1.1
Indicates whether the bank breaker is open(0), closed(1) or not
installed(2).
Enumeration
Enumerated Values:
0open
1closed
2notInstalled
.1.3.6.1.4.1.850.1.1.3.4.3.5.1.1.2
.1.3.6.1.4.1.850.1.1.3.4.3.6.1 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsHeatsinkTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsHeatsinkTable'
A list of ats heatsink thermistor table entries. The number of entries
is given by the value of tlpAtsIdentNumHeatsinks.
tlpAtsHeatsinkEntry row .1.3.6.1.4.1.850.1.1.3.4.3.6.1.1
An entry containing information applicable to a particular heatsink
thermistor managed by this agent.
Column Syntax OID
The table row index for the ats heatsink thermistor.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.1
Indicates whether the heatsink thermistor is available. The entry
will return notAvailable(0) if a thermistor is either non-existent or
disconnected, or available(1) when connected.
Enumeration
Enumerated Values:
0notAvailable
1available
.1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.2
The temperature at the heatsink thermistor in tenths degrees Celsius.
Heatsink temperature measurements are not supported on all models. If
not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.3
The temperature at the heatsink thermistor in tenths degrees Fahrenheit.
Heatsink temperature measurements are not supported on all models. If
not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.4.3.6.1.1.4
.1.3.6.1.4.1.850.1.1.3.4.4.1 · 1 row entry · 6 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsControlTable'
The actionable controls for each ats in device table. This is a
sparse dependent table, and will contain some subset of devices
that are atss.
tlpAtsControlEntry row .1.3.6.1.4.1.850.1.1.3.4.4.1.1
An entry containing controls for a particular ats.
Indexes
Column Syntax OID
Set to TRUE to initiate the pre-designated ramp
sequence on the ats.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.4.1.1.1
Set to TRUE to initiate the pre-designated shed
sequence on the ats.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.4.1.1.2
Set to TRUE to turn the ats on.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.4.1.1.3
Set to TRUE to turn the ats off.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.4.1.1.4
Set to TRUE to reboot the ats.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.4.1.1.5
Set to TRUE to reset the general fault alarm indicated by
tlpAtsDeviceGeneralFault.
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.850.1.1.3.4.4.1.1.6
.1.3.6.1.4.1.850.1.1.3.4.5.1 · 1 row entry · 6 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsConfigTable'
The configuration options of each ats in device table. This
is a sparse dependent table, and will contain some subset of
devices that are atss. Not all options are available on all
atss.
tlpAtsConfigEntry row .1.3.6.1.4.1.850.1.1.3.4.5.1.1
An entry containing configuration options for a particular ats.
Indexes
Column Syntax OID
The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME. This value may not be writable on all models. If
not writable, the…
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.1.1.1
The determination as to which of two AC input lines is designated
as the primary input source. The other is designated as the
secondary input source. This value will always return inputSourceA(1)
for devices with a sing…
Enumerationr/w
Enumerated Values:
1inputSourceA
2inputSourceB
.1.3.6.1.4.1.850.1.1.3.4.5.1.1.2
The nominal time to delay a transition to Source 1, if it is the
preferred source.
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.1.1.3
The nominal time to delay a transition to Source 2, if it is the
preferred source.
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.1.1.4
When enabled(1), the ats should perform its preconfigured ramp sequence when
the input source transfers from its designated secondary source to its
designated primary source. This value not supported on all ats devices.…
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.4.5.1.1.5
When enabled(1), the ats should perform its preconfigured shed sequence when
the input source transfers from its designated primary source to its designated
secondary source. This value not supported on all ats devices.…
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.4.5.1.1.6
.1.3.6.1.4.1.850.1.1.3.4.5.2 · 1 row entry · 10 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsConfigVoltageRangeOldTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsConfigVoltageRangeOldTable'
The voltage range options in this table is intended to configure the
operating voltages of an ats. This is a sparse dependent table, and will
contain some subset of devices that are atss. All voltage points defined
in this table are listed in a specific order from high to low. All voltage
points must satisfy the conditions and ranges defined for each point. Any
point violating any of the relative limits will be rejected.
          
For optimal operation, it is recommended that tlpAtsConfigHighVoltageReset
be set lower than tlpAtsConfigHighVoltageTransfer by a margin no less than 1%
of tlpAtsConfigHighVoltageTransfer; and that tlpAtsConfigSource1TransferReset
(tlpAtsConfigSource2TransferReset) be set higher than
tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet) by a margin no
less than 1% of tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet).
          
*The upper limit of line voltage is tlpAtsInputHighTransferVoltageUpperBound.
The lower limit of line voltage is tlpAtsInputBadTransferVoltageLowerBound. All
minimum and maximum limits for each voltage point are all exclusive unless
indicated otherwise.
          
This table in its entirety is obsolete and replaced by tlpAtsConfigVoltageRangeTable.
tlpAtsConfigVoltageRangeOldEntry row .1.3.6.1.4.1.850.1.1.3.4.5.2.1
An entry containing voltage range configuration options for a particular ats.
Indexes
Column Syntax OID
The maximum line voltage allowed before the unit disconnects the
AC input connection. The maximum value allowed is dictated by
tlpAtsInputHighTransferVoltageUpperBound (inclusively). The minimum
value allowed is dictate…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.1
If a unit is disconnected due to over-voltage, the line voltage has to
fall below this value before the unit re-connects the AC input connection.
The maximum value allowed is dictated by tlpAtsConfigHighVoltageTransferO…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.2
If input source 1 voltage level is above this value, a unit connected to
source 2 will transition to source 1 (if it is the preferred source). The
maximum value allowed is dictated by tlpAtsConfigHighVoltageResetOld. Th…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.3
This value dictates the voltage level below which source 1 goes into a
brown out condition. The maximum value allowed is dictated by
tlpAtsConfigSource1TransferResetOld. The minimum value allowed is dictated by
tlpAtsCo…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.4
If input source 1 voltage level falls below this value, a unit connected to
source 1 will transition to source 2 (if it is in fair condition as denoted
by tlpAtsConfigSource2TransferSetOld). The maximum value allowed is…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.5
If input source 2 voltage level is above this value, a unit connected to
source 1 will transition to source 2 (if it is the preferred source). The
maximum value allowed is dictated by tlpAtsConfigHighVoltageResetOld. Th…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.6
This value dictates the voltage level below which source 2 goes into a
brown out condition. The maximum value allowed is dictated by
tlpAtsConfigSource2TransferResetOld. The minimum value allowed is dictated by
tlpAtsCo…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.7
If input source 2 voltage level falls below this value, a unit connected to
source 2 will transition to source 1 (if it is in fair condition as denoted
by tlpAtsConfigSource1TransferSetOld). The maximum value allowed is…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.8
If a unit is disconnected due to under-voltage or is not powered up yet, the
line voltage has to rise above this value before the unit gets connected to
the AC input connection. The maximum value allowed is dictated by …
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.9
The minimum line voltage allowed before the unit disconnects the
AC input connection. The maximum value allowed is dictated by
tlpAtsConfigLowVoltageResetOld. The minimum value allowed is dictated by
tlpAtsInputBadTrans…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.10
.1.3.6.1.4.1.850.1.1.3.4.5.3 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsConfigVoltageRangeLimitsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsConfigVoltageRangeLimitsTable'
The voltage range table, as documented by tlpAtsConfigVoltageRangeTable requires
that all changes adhere with stack order, from high transfer voltage down to low
transfer voltage. In addition to stack order, certain voltage range values have
limits defining the absolute minimum and absolute maximum for such values. Any
voltage value violating any respective limit defined herein will be rejected.
tlpAtsConfigVoltageRangeLimitsEntry row .1.3.6.1.4.1.850.1.1.3.4.5.3.1
An entry containing voltage range limits configuration options for a particular ats.
Indexes
Column Syntax OID
This value dictates the absolute lower limit by which tlpAtsConfigSource1BrownoutSet
and tlpAtsConfigSource2BrownoutSet can be set. tlpAtsConfigSource1TransferSet and
tlpAtsConfigSource2TransferSet, respectively, are al…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.3.1.1
This value dictates the absolute upper limit by which tlpAtsConfigSource1BrownoutSet
and tlpAtsConfigSource2BrownoutSet can be set. tlpAtsConfigSource1TransferReset and
tlpAtsConfigSource2TransferReset, respectively, ar…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.3.1.2
This value dictates the absolute lower limit by which tlpAtsConfigSource1TransferSet
and tlpAtsConfigSource2TransferSet can be set. tlpAtsConfigLowVoltageReset is also
used when determining the lowest value a transferse…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.3.1.3
This value dictates the absolute upper limit by which tlpAtsConfigSource1TransferSet
and tlpAtsConfigSource2TransferSet can be set. tlpAtsConfigSource1BrownoutSet and
tlpAtsConfigSource2BrownoutSet, respectively, are al…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.3.1.4
.1.3.6.1.4.1.850.1.1.3.4.5.4 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsConfigThresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsConfigThresholdTable'
The configurable threshold options of each ats in device table. This
is a sparse dependent table, and will contain some subset of devices that
are atss. Not all options are available on all atss.
tlpAtsConfigThresholdEntry row .1.3.6.1.4.1.850.1.1.3.4.5.4.1
An entry containing configurable threshold options for a particular ats.
Indexes
Column Syntax OID
The output current measurement at which an over current condition is reported.
This value may not be supported on all models. If not supported, this value
will return ERROR_NO_SUCH_NAME.
0.1 AmpsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.4.1.1
The system temperature at which an over temperature condition is reported.
This value may not be supported on all models. If not supported, this value
will return ERROR_NO_SUCH_NAME.
0.1 CelsiusSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.4.1.2
The input voltage measurement at which an over voltage condition is reported.
This value may not be supported on all models. If not supported, this value
will return ERROR_NO_SUCH_NAME.
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.4.1.3
The system load at which an overload condition is reported. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME.
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.4.1.4
.1.3.6.1.4.1.850.1.1.3.4.5.5 · 1 row entry · 7 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsConfigVoltageRangeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsConfigVoltageRangeTable'
The voltage range options in this table is intended to configure the
operating voltages of an ats. This is a sparse dependent table, and will
contain some subset of devices that are atss. All voltage points defined
in this table are listed in a specific order from high to low. All voltage
points must satisfy the conditions and ranges defined for each point. Any
point violating any of the relative limits will be rejected.
          
For optimal operation, it is recommended that tlpAtsConfigHighVoltageReset
be set lower than tlpAtsConfigHighVoltageTransfer by a margin no less than 1%
of tlpAtsConfigHighVoltageTransfer; and that tlpAtsConfigSource1TransferReset
(tlpAtsConfigSource2TransferReset) be set higher than
tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet) by a margin no
less than 1% of tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet).
          
*The upper limit of line voltage is tlpAtsInputHighTransferVoltageUpperBound.
The lower limit of line voltage is tlpAtsInputBadTransferVoltageLowerBound. All
minimum and maximum limits for each voltage point are all exclusive unless
indicated otherwise.
tlpAtsConfigVoltageRangeEntry row .1.3.6.1.4.1.850.1.1.3.4.5.5.1
An entry containing voltage range configuration options for a particular ats.
Column Syntax OID
The maximum line voltage allowed on the input source before the unit
disconnects the AC input connection. tlpAtsConfigHighVoltageTransfer is the
same value for both input sources on some units. On such units, changing
t…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.1
If an input connection is disconnected due to over-voltage, the line voltage
on the input source has to fall below this value before the unit re-connects
the AC input connection for the input source. tlpAtsConfigHighVol…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.2
If input source voltage level is above this value, a unit connected to
this other input source will transition to this input source (if it is the
preferred source). The maximum value allowed is dictated by
tlpAtsConfigH…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.3
This value dictates the voltage level below which the input source goes
into a brown out condition. The maximum value allowed is dictated by
tlpAtsConfigTransferReset. The minimum value allowed is dictated by
tlpAtsConf…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.4
If input source voltage level falls below this value, a unit connected to
this input source will transition to other input source (if it is in fair
condition as denoted by tlpAtsConfigTransferSet). The maximum value all…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.5
If a unit is disconnected due to under-voltage or is not powered up yet, the
line voltage has to rise above this value before the unit gets connected to
the AC input connection. tlpAtsConfigLowVoltageReset is the same v…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.6
The minimum line voltage allowed before the unit disconnects the AC input
connection. tlpAtsConfigLowVoltageTransfer is the same value for both input
sources. As such, changing this value on one source will change the v…
0.1 VoltsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.7
.1.3.6.1.4.1.850.1.1.3.4.5.6 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAtsConfigPhaseThresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsConfigPhaseThresholdTable'
The configuration options of each Ats in device table. This
is a sparse dependent table, and will contain some subset of
devices that are Atss. Not all options are available on all
Atss.
tlpAtsConfigPhaseThresholdEntry row .1.3.6.1.4.1.850.1.1.3.4.5.6.1
An entry containing threshold configuration options for a particular Ats.
Column Syntax OID
The table row index for the Ats phase.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.6.1.1
The threshold tolerance value used together with output current high/low
threshold to evaluate output current high/low condition.
0.1 AmpsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.6.1.2
The value at which a output current high condition is declared.
0.1 AmpsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.6.1.3
The value at which a output current low condition is declared.
0.1 AmpsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.4.5.6.1.4
.1.3.6.1.4.1.850.1.1.3.5.3.1.1 · 1 row entry · 8 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingTemperatureFahrenheitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingTemperatureFahrenheitTable'
The temperature details for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling.
tlpCoolingTemperatureFahrenheitEntry row .1.3.6.1.4.1.850.1.1.3.5.3.1.1.1
An entry containing temperature details for a particular cooling device.
Indexes
Column Syntax OID
The ambient temperature in tenths degrees Fahrenheit. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.1
The temperature of the air entering the cooling unit in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.2
The temperature of the air entering the cooling unit in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.3
The temperature of the air entering the condenser in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.4
The temperature of the evaporator surface in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.5
The temperature of the low pressure refrigerant line in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.6
The external remote temperature in tenths degrees Fahrenheit. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.7
The temperature of the air leaving the condenser in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.1.1.8
.1.3.6.1.4.1.850.1.1.3.5.3.1.2 · 1 row entry · 8 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingTemperatureCelsiusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingTemperatureCelsiusTable'
The temperature details for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling.
tlpCoolingTemperatureCelsiusEntry row .1.3.6.1.4.1.850.1.1.3.5.3.1.2.1
An entry containing temperature details for a particular cooling device.
Indexes
Column Syntax OID
The ambient temperature in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.1
The temperature of the air entering the cooling unit in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.2
The temperature of the air entering the cooling unit in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.3
The temperature of the air entering the condenser in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.4
The temperature of the evaporator surface in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.5
The temperature of the low pressure refrigerant line in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.6
The external remote temperature in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.7
The temperature of the air leaving the condenser in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.1.2.1.8
.1.3.6.1.4.1.850.1.1.3.5.3.2.1 · 1 row entry · 2 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingPressureMpaTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingPressureMpaTable'
The pressure detail for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by  tlpCoolingIdentNumCooling.
tlpCoolingPressureMpaEntry row .1.3.6.1.4.1.850.1.1.3.5.3.2.1.1
An entry containing pressure details for a particular cooling device.
Indexes
Column Syntax OID
The pressure of the compressor discharge line in tenths of Mpa. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 MpaSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.2.1.1.1
The pressure of the compressor discharge line in tenths of Mpa. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 MpaSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.2.1.1.2
.1.3.6.1.4.1.850.1.1.3.5.3.2.2 · 1 row entry · 2 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingPressurePsiTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingPressurePsiTable'
The pressure detail for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by  tlpCoolingIdentNumCooling.
tlpCoolingPressurePsiEntry row .1.3.6.1.4.1.850.1.1.3.5.3.2.2.1
An entry containing pressure details for a particular cooling device.
Indexes
Column Syntax OID
The pressure of the compressor discharge line in tenths of Psi. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 PsiSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.2.2.1.1
The pressure of the compressor discharge line in tenths of Psi. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 PsiSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.2.2.1.2
.1.3.6.1.4.1.850.1.1.3.5.3.3 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingCurrentTable'
The input current for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling.
tlpCoolingCurrentEntry row .1.3.6.1.4.1.850.1.1.3.5.3.3.1
An entry containing input current for a particular cooling device.
Indexes
Column Syntax OID
The total current draw of the unit in tenths of Amps. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.3.1.1
The compressor current draw of the unit in tenths of Amps. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.3.1.2
The current draw of the evaporator fan in tenths of Amps. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.3.1.3
The current draw of the condenser fan in tenths of Amps. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.3.1.4
.1.3.6.1.4.1.850.1.1.3.5.3.4 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingDynamicTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingDynamicTable'
The dynamic detail for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by  tlpCoolingIdentNumCooling.
tlpCoolingDynamicEntry row .1.3.6.1.4.1.850.1.1.3.5.3.4.1
An entry dynamic details for a particular cooling device.
Indexes
Column Syntax OID
The current speed of the evaporator fan. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumeration
Enumerated Values:
0off
1low
2mediumLow
3medium
4mediumHigh
5high
6auto
.1.3.6.1.4.1.850.1.1.3.5.3.4.1.1
The current speed of the condenser fan. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumeration
Enumerated Values:
0off
1low
2mediumLow
3medium
4mediumHigh
5high
6auto
.1.3.6.1.4.1.850.1.1.3.5.3.4.1.2
The operating mechanical frequency(Hz) of the compressor. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
HertzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.4.1.3
The current EEV steps. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.3.4.1.4
.1.3.6.1.4.1.850.1.1.3.5.3.5 · 1 row entry · 6 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingRuntimeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingRuntimeTable'
The runtime detail for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by  tlpCoolingIdentNumCooling.
tlpCoolingRuntimeEntry row .1.3.6.1.4.1.850.1.1.3.5.3.5.1
An entry containing runtime for a particular cooling device.
Indexes
Column Syntax OID
Total days the compressor has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
daysSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.5.1.1
Total days the condensate pump has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
daysSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.5.1.2
Total hours the air filter has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
hoursSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.5.1.3
Total days the evaporator fan has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
daysSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.5.1.4
Total days the condenser fan has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
daysSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.5.1.5
Total days the atomizer has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
daysSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.5.1.6
.1.3.6.1.4.1.850.1.1.3.5.3.6 · 1 row entry · 5 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingStatusTable'
The status detail for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling.
tlpCoolingStatusEntry row .1.3.6.1.4.1.850.1.1.3.5.3.6.1
An entry containing status for a particular cooling device.
Indexes
Column Syntax OID
The current operating mode. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumeration
Enumerated Values:
0off
1idle
2cooling
3shuttingDown
4dehumidifying
5defrosting
6notConnected
.1.3.6.1.4.1.850.1.1.3.5.3.6.1.1
The current cooling output of the cooling device in tenth of kilowatt. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
0.1 kilowattsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.3.6.1.2
The current alarm status of the cooling device. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumeration
Enumerated Values:
0noAlarm
1warning
2critical
.1.3.6.1.4.1.850.1.1.3.5.3.6.1.3
The current operating status of compressor. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.850.1.1.3.5.3.6.1.4
The current water status of cooling unit. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumeration
Enumerated Values:
0notFull
1full
.1.3.6.1.4.1.850.1.1.3.5.3.6.1.5
.1.3.6.1.4.1.850.1.1.3.5.4.1 · 1 row entry · 1 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingControlTable'
The actionable controls for each cooling device in device table. This
is a sparse dependent table, and will contain some subset of
devices that are cooling device.
tlpCoolingControlEntry row .1.3.6.1.4.1.850.1.1.3.5.4.1.1
An entry containing controls for a particular cooling device.
Indexes
Column Syntax OID
Turn the unit on or off.
Enumerationr/w
Enumerated Values:
0turnOffUnit
1turnOnUnit
.1.3.6.1.4.1.850.1.1.3.5.4.1.1.1
.1.3.6.1.4.1.850.1.1.3.5.5.1 · 1 row entry · 25 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingConfigTable'
The configuration details for each each cooling device in device table. This
is a sparse dependent table, and will contain some subset of
devices that are cooling device. Not all options are available on all
cooling devices.
tlpCoolingConfigEntry row .1.3.6.1.4.1.850.1.1.3.5.5.1.1
An entry configuration details for a particular cooling device.
Indexes
Column Syntax OID
Specifies if the unit should start automatically on power up.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.1
Specifies the actual speed of the evaporator fan. Setting the fan speed
to auto(6) will enable tlpCoolingAutoFanSpeed; however, on most units getting
the fan speed will return the actual fan speed regardless whether a…
Enumerationr/w
Enumerated Values:
0off
1low
2mediumLow
3medium
4mediumHigh
5high
6auto
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.2
Specifies which temperature is used as a control point. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0returnAirTemperature
1remoteTemperature
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.3
Specifies whether displays output values in Metric or English formats. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0metric
1english
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.4
Specifies whether a beep is emitted when a key is pressed on the unit's display panel. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0noBeep
1beepOn
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.5
The input contact type. If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0normallyClosed
1normallyOpen
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.6
The output contact type. If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0normallyClosed
1normallyOpen
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.7
The alarm level that causes the output relay to activate. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1allAlarmsAndWarnings
2criticalAlarmsOnly
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.8
Type of contact to make when output relay is activated. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0normallyClosed
1normallyOpen
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.9
Indicates if the unit should stop cooling when input contact is activated. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0turnOff
1alarmOnly
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.10
Indicates if the unit should stop cooling when leak input is activated. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0turnOff
1alarmOnly
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.11
The water leak contact type. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0normallyClosed
1normallyOpen
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.12
The number of weeks before the air filter needs to be changed.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
weeksSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.13
When enabled, an alarm should occur when the maximum number of air filter run hours
has been exceeded. If not supported, this value will always return ERROR_NO_SUCH_NAME.
hoursEnumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.14
The maximum interval for air filter run hours before warning is annunciated.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
hoursSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.15
The unit will start operate after the specified timer elapsed. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
minutesSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.16
The unit will switch to standby mode after the specified timer elapsed. If not supported,
this value will always return ERROR_NO_SUCH_NAME.
minutesSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.17
This option enables or disables the energy saving mode.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0normalCooling
1energySaving
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.18
This option enables or disables the defrost mode.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.19
This option enables or disables the remote temperature sensor.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.20
This option enables or disables the dehumidifying mode.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.21
This option enables or disables the fan always on.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.22
This option enables or disables the quiet mode.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.23
This option enables or disables the hot gas bypass.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.24
This option enables or disables the auto fan speed.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.850.1.1.3.5.5.1.1.25
.1.3.6.1.4.1.850.1.1.3.5.5.2 · 1 row entry · 7 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingConfigTemperatureFahrenheitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingConfigTemperatureFahrenheitTable'
The configuration details for each each cooling device in device table. This
is a sparse dependent table, and will contain some subset of
devices that are cooling device. Not all options are available on all
cooling devices.
tlpCoolingConfigTemperatureFahrenheitEntry row .1.3.6.1.4.1.850.1.1.3.5.5.2.1
An entry configuration details for a particular cooling device.
Indexes
Column Syntax OID
The set point temperature the unit will control the temperature in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.2.1.1
Maximum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.2.1.2
Minimum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.2.1.3
Maximum allowed air temperature deviation from set temperature before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.2.1.4
Maximum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.2.1.5
Minimum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.2.1.6
The remote set point temperature the unit will control the temperature in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees FahrenheitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.2.1.7
.1.3.6.1.4.1.850.1.1.3.5.5.3 · 1 row entry · 7 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpCoolingConfigTemperatureCelsiusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpCoolingConfigTemperatureCelsiusTable'
The configuration details for each cooling device in device table. This
is a sparse dependent table, and will contain some subset of
devices that are cooling device. Not all options are available on all
cooling devices.
tlpCoolingConfigTemperatureCelsiusEntry row .1.3.6.1.4.1.850.1.1.3.5.5.3.1
An entry configuration details for a particular cooling device.
Indexes
Column Syntax OID
The set point temperature the unit will control the temperature in tenths degrees Celsius.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.3.1.1
Maximum allowed supply air temperature in tenths degrees Celsius before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.3.1.2
Minimum allowed supply air temperature in tenths degrees Celsius before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.3.1.3
Maximum allowed air temperature deviation from set temperature before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.3.1.4
Maximum allowed return air temperature in tenths degrees Celsius before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.3.1.5
Minimum allowed return air temperature in tenths degrees Celsius before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.3.1.6
The remote set point temperature the unit will control the temperature in tenths degrees Celsius.
If not supported, this value will always return ERROR_NO_SUCH_NAME.
0.1 degrees CelsiusSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.850.1.1.3.5.5.3.1.7
.1.3.6.1.4.1.850.1.2.3.1.2 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAgentEmailContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAgentEmailContactTable'
A list of email contact entries. The number of entries is given by
the value of tlpAgentNumEmailContacts.
tlpAgentEmailContactEntry row .1.3.6.1.4.1.850.1.2.3.1.2.1
An entry containing the details of an email contact.
Column Syntax OID
The table row index for the email contact.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.2.3.1.2.1.1
Row status for the tlpAgentEmailContactTable.
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.850.1.2.3.1.2.1.2
The name of the email contact.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.2.3.1.2.1.3
The address of the email contact.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.2.3.1.2.1.4
.1.3.6.1.4.1.850.1.2.3.2.2 · 1 row entry · 9 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAgentSnmpContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAgentSnmpContactTable'
A list of SNMP contact entries. The number of entries is given by
the value of tlpAgentNumSnmpContacts.
tlpAgentSnmpContactEntry row .1.3.6.1.4.1.850.1.2.3.2.2.1
An entry containing the details of an SNMP contact.
Column Syntax OID
The table row index for the SNMP contact.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.2.3.2.2.1.1
Row status for the tlpAgentSnmpContactTable.
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.850.1.2.3.2.2.1.2
The name of the SNMP contact.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.2.3.2.2.1.3
The IP address of the SNMP contact.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.2.3.2.2.1.4
The port of the SNMP contact.
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.2.3.2.2.1.5
The SNMP contact version to use for sending traps.
Enumerationr/w
Enumerated Values:
1snmpv1
2snmpv2c
3snmpv3
.1.3.6.1.4.1.850.1.2.3.2.2.1.6
The security name for the SNMP contact.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.2.3.2.2.1.7
The privacy password to use for sending V3 traps to the SNMP
contact.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.2.3.2.2.1.8
The authentication password to use for sending V3 traps to the
SNMP contact.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.2.3.2.2.1.9
.1.3.6.1.4.1.850.1.3.2 · 1 row entry · 9 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAlarmTable'
A list of alarm conditions for all devices managed by this agent. This
table contains zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect or conditions not acknowledged.
The agent creates a row in the table each time a condition is detected
and deletes that row when that condition no longer pertains (becomes
inactive and is acknowledged). The agent creates the first row with
tlpAlarmId equal to 1, and increments the value of tlpAlarmId each time
a new row is created, wrapping to the first free value greater than or
equal to 1 when the maximum value of tlpAlarmId would otherwise be
exceeded. Consequently, after multiple operations, the table may become
sparse (e.g., containing entries for rows 95, 100, 101, and 203) and the
entries should not be assumed to be in chronological order because
tlpAlarmId might have wrapped.
          
The number of rows in the table at any given time is reflected by
the value of tlpAlarmsPresent.
tlpAlarmEntry row .1.3.6.1.4.1.850.1.3.2.1
An entry containing information application to a particular
alarm.
Indexes
Column Syntax OID
A unique identifier for an alarm condition. This value will remain
constant for the duration of the alarm condition.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.3.2.1.1
A reference of the alarm description object. The object referenced
should not be accessible, but rather be used to provide a unique
description for the alarm condition. The object referenced will be a
well known alarm o…
ObjectIdentifier .1.3.6.1.4.1.850.1.3.2.1.2
The value of sysUpTime when the alarm condition was detected. If the
alarm condition was detected at the time of agent startup and presumably
existed before agent startup, the value of tlpAlarmsTime shall equal
0.
SNMPv2-TCTimeStamp
Based On: SNMPv2-SMITimeTicks
Description:
The value of the sysUpTime object at which a specific
occurrence happened. The specific occurrence must be

defined in the description of any object defined using this
type.

If sysUpTime is reset t…
.1.3.6.1.4.1.850.1.3.2.1.3
This value references the OID of a table object applicable to the alarm
condition. This, in conjunction with the table row as defined by
tlpAlarmTableRowRef, specifies the object/row within this table to which
the alarm…
ObjectIdentifier .1.3.6.1.4.1.850.1.3.2.1.4
This value is used in conjunction with tlpAlarmTableRef to define the
object associated with this alarm condition. See the description of
tlpAlarmTableRef for more information.
ObjectIdentifier .1.3.6.1.4.1.850.1.3.2.1.5
A textual description of the alarm condition.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.3.2.1.6
The category/group of this alarm.
Enumeration
Enumerated Values:
1critical
2warning
3info
4status
5offline
6custom
.1.3.6.1.4.1.850.1.3.2.1.7
The current state of this alarm condition. An active(1) alarm is a condition
that currently exists. An inactive(2) alarm is a condition that no longer exists
because the alarm either cleared or was resolved. Each alarm …
Enumeration
Enumerated Values:
1active
2inactive
.1.3.6.1.4.1.850.1.3.2.1.8
Denotes whether the alarm condition has been acknowledged. The agent will
return notAcknowledged(1) if the condition has not been acknowledged, or
acknowledged(2) when acknowledged. Writing the value acknowledged(2) for…
Enumerationr/w
Enumerated Values:
1notAcknowledged
2acknowledged
.1.3.6.1.4.1.850.1.3.2.1.9
.1.3.6.1.4.1.850.1.3.4.1 · 1 row entry · 4 columns
Uses the tripplite variant from /opt/observium/mibs/tripplite.
Command help
Walk tlpAlarmControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAlarmControlTable'
A list of alarm conditions supported for each device managed by this
agent. This table contains zero, one, or many rows depending upon the
number of available alarms managed by each device.
tlpAlarmControlEntry row .1.3.6.1.4.1.850.1.3.4.1.1
An entry containing details for a particular alarm condition.
Column Syntax OID
The table row index for this alarm control entry for this device. The
index of any one row represents the index of the alarm entry within the
agent system. As such, the index values for any one device is not
guaranteed …
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.850.1.3.4.1.1.1
A reference of the alarm description object. The object referenced
should not be accessible, but rather be used to provide a unique
description for the alarm condition. The object referenced will be a
well known alarm o…
ObjectIdentifier .1.3.6.1.4.1.850.1.3.4.1.1.2
A textual description of the alarm condition. This will be the same
textual description of an alarm when in alarm as referenced by
tlpAlarmDetail.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.850.1.3.4.1.1.3
The severity of this alarm, which can be configured as desired for
each alarm condition. This will be the same severity used when in alarm
as referenced by tlpAlarmType.
Enumerationr/w
Enumerated Values:
1critical
2warning
3info
.1.3.6.1.4.1.850.1.3.4.1.1.4