tlpUpsConfigEconomicMode
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.15
Object
column
r/w
Enumeration
The configurable economic mode options for the ups. The online(0) mode is the default configuration of most upss, which is synonymous as having the economic mode disabled. The economy(1) mode is the typical configuration to run in economy mode, which is synonymous as having the economic mode enabled. Constant50Hz(2) is a power strategy, which fixes the output frequency at 50Hz. Constant60Hz(3) is a power strategy, which fixes the output frequency at 60Hz. ConstantAuto(4) regulates the output frequency at nominal input frequency. AutoAdaptive(5) mode will cause the ups to automatically switch between online(0), maximum quality, and economy(1), maximum efficiency, to improve efficiency during stable utility periods and improve output regulation during unstable utility periods. Not all values are supported by all upss. Most upss, if supportive of economic mode, only supports online(0) and economy(1). If the ups does not support economic mode, then this value will always return ERROR_NO_SUCH_NAME.
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.1.5.1.1.15- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- tlpUpsConfigEntry
Syntax
Enumeration
Values & Constraints
Enumerated Values
0 | online |
1 | economy |
2 | constant50Hz |
3 | constant60Hz |
4 | constantAuto |
5 | autoAdaptive |