tlpAtsConfigLowVoltageReset
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.6
Object
column
r/w
0.1 Volts Unsigned32
If a unit is disconnected due to under-voltage or is not powered up yet, the line voltage has to rise above this value before the unit gets connected to the AC input connection. tlpAtsConfigLowVoltageReset is the same value for both input sources. As such, changing this value on one source will change the value on the other source. The maximum value allowed is dictated by the lesser value of tlpAtsConfigTransferSet.1 and tlpAtsConfigTransferSet.2. The minimum value allowed is dictated by tlpAtsConfigLowVoltageTransfer. If not supported, this value will return ERROR_NO_SUCH_NAME.
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.6- Type
- column
- Access
- readwrite
- Status
- current
- Units
- 0.1 Volts
- Parent
- tlpAtsConfigVoltageRangeEntry
Syntax
0.1 Volts Unsigned32
Values & Constraints
No enumerated values or constraints recorded.