tlpAtsConfigLowVoltageReset

TRIPPLITE-PRODUCTS · .1.3.6.1.4.1.850.1.1.3.4.5.5.1.6

Object

column r/w 0.1 Volts Unsigned32
If a unit is disconnected due to under-voltage or is not powered up yet, the
line voltage has to rise above this value before the unit gets connected to
the AC input connection. tlpAtsConfigLowVoltageReset is the same value for both
input sources. As such, changing this value on one source will change the value
on the other source. The maximum value allowed is dictated by the lesser value
of tlpAtsConfigTransferSet.1 and tlpAtsConfigTransferSet.2. The minimum value
allowed is dictated by tlpAtsConfigLowVoltageTransfer. If not supported, this
value will return ERROR_NO_SUCH_NAME.

Context

MIB
TRIPPLITE-PRODUCTS
OID
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.6
Type
column
Access
readwrite
Status
current
Units
0.1 Volts
Parent
tlpAtsConfigVoltageRangeEntry

Syntax

0.1 Volts Unsigned32

Values & Constraints

No enumerated values or constraints recorded.