tlpAtsConfigHighVoltageTransferOld

TRIPPLITE-PRODUCTS · .1.3.6.1.4.1.850.1.1.3.4.5.2.1.1

Object

column obsolete r/w 0.1 VoltsSNMPv2-SMIUnsigned32
The maximum line voltage allowed before the unit disconnects the
AC input connection. The maximum value allowed is dictated by
tlpAtsInputHighTransferVoltageUpperBound (inclusively). The minimum
value allowed is dictated by tlpAtsConfigHighVoltageResetOld. This value
may not be configurable on all models. If not supported, this value will
return ERROR_NO_SUCH_NAME.

Context

MIB
TRIPPLITE-PRODUCTS
OID
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.1
Type
column
Access
readwrite
Status
obsolete
Units
0.1 Volts
Parent
tlpAtsConfigVoltageRangeOldEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsConfigHighVoltageTransferOld'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsConfigHighVoltageTransferOld.<tlpDeviceIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'TRIPPLITE-PRODUCTS::tlpAtsConfigHighVoltageTransferOld'

Syntax

Source
SNMPv2-SMIUnsigned32
Base type
Unsigned32

Values & Constraints

Type Constraints
range: 0..4294967295