tlpAtsConfigHighVoltageTransferOld
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.1
Object
column
obsolete
r/w
0.1 Volts Unsigned32
The maximum line voltage allowed before the unit disconnects the AC input connection. The maximum value allowed is dictated by tlpAtsInputHighTransferVoltageUpperBound (inclusively). The minimum value allowed is dictated by tlpAtsConfigHighVoltageResetOld. This value may not be configurable on all models. If not supported, this value will return ERROR_NO_SUCH_NAME.
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.4.5.2.1.1- Type
- column
- Access
- readwrite
- Status
- obsolete
- Units
- 0.1 Volts
- Parent
- tlpAtsConfigVoltageRangeOldEntry
Syntax
0.1 Volts Unsigned32
Values & Constraints
No enumerated values or constraints recorded.