tlpAtsConfigTransferReset
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.3
Object
If input source voltage level is above this value, a unit connected to this other input source will transition to this input source (if it is the preferred source). The maximum value allowed is dictated by tlpAtsConfigHighVoltageReset. The minimum value allowed is dictated by tlpAtsConfigBrownoutSet. If not supported, this value will return ERROR_NO_SUCH_NAME.
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.4.5.5.1.3- Type
- column
- Access
- readwrite
- Status
- current
- Units
- 0.1 Volts
- Parent
- tlpAtsConfigVoltageRangeEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsConfigTransferReset'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRIPPLITE-PRODUCTS::tlpAtsConfigTransferReset.<tlpDeviceIndex>.<tlpAtsInputLineIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'TRIPPLITE-PRODUCTS' -M '/opt/observium/mibs/tripplite:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'TRIPPLITE-PRODUCTS::tlpAtsConfigTransferReset'
Syntax
0.1 VoltsSNMPv2-SMIUnsigned32
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295