VERTIV-V5-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
34
Rows
34
Columns
355
.1.3.6.1.4.1.21239.5.2.3.1 · 1 row entry · 12 columns
PDU general information
pduMainEntry entry .1.3.6.1.4.1.21239.5.2.3.1.1
Entry in the pduMainTable table: each entry contains an index and
other sensor details
Indexes
pduMainIndex
Column Syntax OID
pduMainIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.1.1.1
pduMainSerial
Serial number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.2.3.1.1.2
pduMainName
PDU name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.1.1.3
pduMainLabel
PDU label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.1.1.4
pduMainAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.3.1.1.5
pduMeterType
Current meter type:
0 = Wye
1 = Delta
Enumeration
Enumerated Values:
0wye
1delta
.1.3.6.1.4.1.21239.5.2.3.1.1.6
pduTotalName
Total name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.1.1.7
pduTotalLabel
Total label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.1.1.8
pduTotalRealPower
PDU total real power
wattsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.1.1.9
pduTotalApparentPower
PDU total apparent power
volt-ampsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.1.1.10
pduTotalPowerFactor
PDU total power factor
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.1.1.11
pduTotalEnergy
PDU total accumulated energy in watt-hours
watt-hoursUnsigned32
Constraints:
range: 0-9999000
.1.3.6.1.4.1.21239.5.2.3.1.1.12
.1.3.6.1.4.1.21239.5.2.3.2 · 1 row entry · 12 columns
PDU phases information
pduPhaseEntry entry .1.3.6.1.4.1.21239.5.2.3.2.1
Entry in the pduPhaseTable table: each entry contains an index and
other sensor details
Indexes
pduPhaseIndex
Column Syntax OID
pduPhaseIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.2.1.1
pduPhaseName
PDU phase name (factory-assigned)
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.2.1.2
pduPhaseLabel
PDU phase label (user-defined)
OctetStringr/w
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.2.1.3
pduPhaseVoltage
PDU phase voltage in tenths of a volt
decivolts (rms)Unsigned32
Constraints:
range: 0-3100
.1.3.6.1.4.1.21239.5.2.3.2.1.4
pduPhaseCurrent
PDU phase current reading in hundredths of an amp
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.2.1.8
pduPhaseRealPower
Real power for phase in watts
wattsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.2.1.12
pduPhaseApparentPower
Apparent power for phase in volt-amps
volt-ampsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.2.1.13
pduPhasePowerFactor
Power factor for phase
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.2.1.14
pduPhaseEnergy
Accumulated energy for phase in watt-hours
watt-hoursUnsigned32
Constraints:
range: 0-9999000
.1.3.6.1.4.1.21239.5.2.3.2.1.15
pduPhaseBalance
Phase balance as percent
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.2.1.17
pduPhaseCurrentCrestFactor
Current crest factor for phase, in hundredths
Unsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.2.1.19
pduPhaseResCurrentDetected
Tells if residual current was detected. In normal operation, the value
will be false(2).
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.3.2.1.20
.1.3.6.1.4.1.21239.5.2.3.3 · 1 row entry · 11 columns
PDU breaker information
pduBreakerEntry entry .1.3.6.1.4.1.21239.5.2.3.3.1
Entry in the pduBreakerTable table: each entry contains an index and
other sensor details
Indexes
pduBreakerIndex
Column Syntax OID
pduBreakerIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.3.1.1
pduBreakerName
PDU breaker name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.3.1.2
pduBreakerLabel
PDU breaker label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.3.1.3
pduBreakerCurrent
PDU breaker current reading in hundredths of an amp
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.3.1.4
pduBreakerVoltage
PDU breaker voltage in tenths of a volt. This object may not exist on
all platforms, due to hardware differences.
decivolts (rms)Unsigned32
Constraints:
range: 0-3100
.1.3.6.1.4.1.21239.5.2.3.3.1.8
pduBreakerRealPower
Real power for breaker in watts. This object may not exist on all
platforms, due to hardware differences.
wattsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.3.1.12
pduBreakerApparentPower
Apparent power for breaker in volt-amps. This object may not exist on
all platforms, due to hardware differences.
volt-ampsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.3.1.13
pduBreakerPowerFactor
Power factor for breaker. This object may not exist on all platforms,
due to hardware differences.
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.3.1.14
pduBreakerEnergy
Accumulated energy for breaker in watt-hours. This object may not
exist on all platforms, due to hardware differences.
watt-hoursUnsigned32
Constraints:
range: 0-9999000
.1.3.6.1.4.1.21239.5.2.3.3.1.15
pduBreakerResCurrentDetected
Tells if residual current was detected. In normal operation, the value
will be false(2).
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.3.3.1.20
pduBreakerLossOfLoadDetected
Tells if a loss of load was detected. In normal operation, the value
will be false(2).
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.3.3.1.21
.1.3.6.1.4.1.21239.5.2.3.4 · 1 row entry · 4 columns
PDU line current information
pduLineEntry entry .1.3.6.1.4.1.21239.5.2.3.4.1
Entry in the pduLineTable table: each entry contains an index and
other sensor details
Indexes
pduLineIndex
Column Syntax OID
pduLineIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.4.1.1
pduLineName
PDU line name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.4.1.2
pduLineLabel
PDU line label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.4.1.3
pduLineCurrent
PDU line current reading in hundredths of an amp
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.4.1.4
.1.3.6.1.4.1.21239.5.2.3.5 · 1 row entry · 13 columns
Data, config and control for outlets with switching
pduOutletSwitchEntry entry .1.3.6.1.4.1.21239.5.2.3.5.1
Entry in the pduOutletSwitchTable table: each entry contains an index
and other sensor details
Indexes
pduOutletSwitchIndex
Column Syntax OID
pduOutletSwitchIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.5.1.1
pduOutletSwitchName
PDU outlet name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.5.1.2
pduOutletSwitchLabel
PDU outlet label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.5.1.3
pduOutletSwitchState
Switch state of the outlet:
1 = Outlet is on
2 = Outlet is off
3 = Outlet is on, but will turn off after a delay
4 = Outlet is off, but will turn on after a delay
5 = Starting reboot cycle, outlet is on, but will go to …
Enumeration
Enumerated Values:
1on
2off
3on2off
4off2on
5rebootOn
6rebootOff
7unavailable
.1.3.6.1.4.1.21239.5.2.3.5.1.4
pduOutletSwitchRelayFailure
Tells if the outlet relay has failed. In normal operation, the value
will be false(2).
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.3.5.1.5
pduOutletSwitchControl
Used for manual control of the outlet. If the outlet is in manual
mode, this field can be set to one of the following values:
1 = Cancel pending operation
2 = Turn outlet on
3 = After delay (pduOutletSwitchOnDelay), tur…
Enumerationr/w
Enumerated Values:
1cancel
2on
3onAfterDelay
4off
5offAfterDelay
6reboot
7rebootAfterDelay
8none
.1.3.6.1.4.1.21239.5.2.3.5.1.6
pduOutletSwitchTimeToAction
Seconds until an outlet state change. The value of
pduOutletSwitchState tells what state the outlet will be set, after
the delay.
Integer32
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.7
pduOutletSwitchOnDelay
Seconds to wait before powering on the outlet, during onAfterDelay(3)
operation. Changing this value has no effect on pending actions.
Integer32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.8
pduOutletSwitchOffDelay
Seconds to wait before powering off the outlet, during
offAfterDelay(5) operation. Changing this value has no effect on
pending actions.
Integer32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.9
pduOutletSwitchRebootDelay
Seconds to wait before powering off the outlet, during
rebootAfterDelay(7) operation. Changing this value has no effect on
pending actions. See pduOutletSwitchControl for more info.
Integer32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.10
pduOutletSwitchRebootHoldDelay
Seconds to hold the outlet off, before powering on the outlet, during
rebootAfterDelay(7) operation. Changing this value has no effect on
pending actions. See pduOutletSwitchControl for more info.
Integer32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.11
pduOutletSwitchPoaAction
The outlet is set to this state during power-up. The action can be
have one the following values:
1 = Outlet will be turned on
2 = Outlet will stay off
3 = Outlet will be set to last known state
Enumerationr/w
Enumerated Values:
1on
2off
3last
.1.3.6.1.4.1.21239.5.2.3.5.1.12
pduOutletSwitchPoaDelay
Seconds to wait before setting the outlet to the
pduOutletSwitchPoaAction state. The delay starts at power-up.
Integer32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.21239.5.2.3.5.1.13
.1.3.6.1.4.1.21239.5.2.3.6 · 1 row entry · 11 columns
Metering data for outlets that support this feature
pduOutletMeterEntry entry .1.3.6.1.4.1.21239.5.2.3.6.1
Entry in the pduOutletMeterTable table: each entry contains an index
and other sensor details
Indexes
pduOutletMeterIndex
Column Syntax OID
pduOutletMeterIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.6.1.1
pduOutletMeterName
PDU outlet name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.6.1.2
pduOutletMeterLabel
PDU outlet label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.6.1.3
pduOutletMeterVoltage
PDU outlet voltage in tenths of a volt
decivolts (rms)Unsigned32
Constraints:
range: 0-3100
.1.3.6.1.4.1.21239.5.2.3.6.1.4
pduOutletMeterCurrent
PDU outlet current reading in hundredths of an amp
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.6.1.8
pduOutletMeterRealPower
Real power for outlet in watts
wattsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.6.1.12
pduOutletMeterApparentPower
Apparent power for outlet in volt-amps
volt-ampsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.6.1.13
pduOutletMeterPowerFactor
Power factor for outlet
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.6.1.14
pduOutletMeterEnergy
Accumulated energy for outlet in watt-hours
watt-hoursUnsigned32
Constraints:
range: 0-9999000
.1.3.6.1.4.1.21239.5.2.3.6.1.15
pduOutletMeterReset
Used to reset energy. If read, the value is none(8). It can be set to
resetEnergy(1), which sets outlet energy to 0
Enumerationr/w
Enumerated Values:
1resetEnergy
8none
.1.3.6.1.4.1.21239.5.2.3.6.1.16
pduOutletCurrentCrestFactor
Current crest factor for outlet, in hundredths
Unsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.6.1.19
.1.3.6.1.4.1.21239.5.2.3.7 · 1 row entry · 5 columns
Residual current data for PDUs that support this feature
pduResidualCurrentEntry entry .1.3.6.1.4.1.21239.5.2.3.7.1
Entry in the pduResidualCurrentTable table: each entry contains an
index and other sensor details
Indexes
pduResidualCurrentIndex
Column Syntax OID
pduResidualCurrentIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.7.1.1
pduResidualCurrentName
PDU residual current name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.7.1.2
pduResidualCurrentLabel
PDU residual current label
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.7.1.3
pduResidualCurrentAggregate
PDU residual current aggregate value in milliamps
milliampsUnsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.3.7.1.4
pduResidualCurrentDc
PDU residual current DC value in milliamps
milliampsUnsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.3.7.1.5
.1.3.6.1.4.1.21239.5.2.4 · 1 row entry · 5 columns
Remote Temperature (RT) sensor
tempSensorEntry entry .1.3.6.1.4.1.21239.5.2.4.1
Entry in the tempSensorTable table: each entry contains an index and
other sensor details
Indexes
tempSensorIndex
Column Syntax OID
tempSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.4.1.1
tempSensorSerial
Serial number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.2.4.1.2
tempSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.4.1.3
tempSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.4.1.4
tempSensorTemp
Temperature in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.4.1.5
.1.3.6.1.4.1.21239.5.2.5 · 1 row entry · 8 columns
Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor
airFlowSensorEntry entry .1.3.6.1.4.1.21239.5.2.5.1
Entry in the airFlowSensorTable table: each entry contains an index
and other sensor details
Indexes
airFlowSensorIndex
Column Syntax OID
airFlowSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.5.1.1
airFlowSensorSerial
Serial number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.2.5.1.2
airFlowSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.5.1.3
airFlowSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.5.1.4
airFlowSensorTemp
Temperature reading in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.5.1.5
airFlowSensorFlow
Airflow reading. Still air will be less than 20, while rushing air
will be around 100.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.5.1.6
airFlowSensorHumidity
Humidity reading
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.5.1.7
airFlowSensorDewPoint
Dewpoint reading in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.5.1.8
.1.3.6.1.4.1.21239.5.2.8 · 1 row entry · 14 columns
Remote Temperature x 3, Humidity and Dewpoint Sensor
t3hdSensorEntry entry .1.3.6.1.4.1.21239.5.2.8.1
Entry in the t3hdSensorTable table: each entry contains an index and
other sensor details
Indexes
t3hdSensorIndex
Column Syntax OID
t3hdSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.8.1.1
t3hdSensorSerial
Serial number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.2.8.1.2
t3hdSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.3
t3hdSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.8.1.4
t3hdSensorIntLabel
Internal label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.5
t3hdSensorIntTemp
Internal temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.6
t3hdSensorIntHumidity
Internal humidity
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.8.1.7
t3hdSensorIntDewPoint
Internal dewpoint in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.8
t3hdSensorExtAAvail
External A status:
0 = Unavailable
1 = Available
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.8.1.9
t3hdSensorExtALabel
External A label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.10
t3hdSensorExtATemp
External A temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.11
t3hdSensorExtBAvail
External B status:
0 = Unavailable
1 = Available
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.8.1.12
t3hdSensorExtBLabel
External B label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.13
t3hdSensorExtBTemp
External B temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.14
.1.3.6.1.4.1.21239.5.2.9 · 1 row entry · 7 columns
Remote Temperature, Humidity, and Dewpoint (THD) Sensor
thdSensorEntry entry .1.3.6.1.4.1.21239.5.2.9.1
Entry in the thdSensorTable table: each entry contains an index and
other sensor details
Indexes
thdSensorIndex
Column Syntax OID
thdSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.9.1.1
thdSensorSerial
Serial number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.2.9.1.2
thdSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.9.1.3
thdSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.9.1.4
thdSensorTemp
Temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.9.1.5
thdSensorHumidity
Humidity value
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.9.1.6
thdSensorDewPoint
Dewpoint value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.9.1.7
.1.3.6.1.4.1.21239.5.2.11 · 1 row entry · 13 columns
Analog measurement (A2D) sensor (voltage, current, or dry-contact)
a2dSensorEntry entry .1.3.6.1.4.1.21239.5.2.11.1
Entry in the a2dSensorTable table: each entry contains an index and
other sensor details
Indexes
a2dSensorIndex
Column Syntax OID
a2dSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.11.1.1
a2dSensorSerial
Serial number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.2.11.1.2
a2dSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.3
a2dSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.11.1.4
a2dSensorValue
Analog measurement value, within either a user-defined or preset
range, depending on a2dSensorMode.
Integer32
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.2.11.1.5
a2dSensorDisplayValue
For current/voltage modes, the analog value is given as a string. In
binary modes, the value is either a2dSensorLowLabel or
a2dSensorHighLabel, based on a2dSensorValue.
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.6
a2dSensorMode
Binary modes have two states represented by the values 0 (low) or 1
(high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel.
Current and voltage modes provide a scaled value from a2dSensorMin to
a2dSensorMa…
Enumerationr/w
Enumerated Values:
1door
2powerFailure
3flood
4wscLeak
5wscFault
6smoke
7ivsNegGnd
8ivsPosGnd
9customVoltage
10customBinary
11customCurrent
.1.3.6.1.4.1.21239.5.2.11.1.7
a2dSensorUnits
The units for the analog value. If a2dSensorMode is customVoltage(9)
or customCurrent(11), then this field has a user-defined value.
Otherwise, the value is fixed, based on mode.
OctetStringr/w
Constraints:
range: 0-7
.1.3.6.1.4.1.21239.5.2.11.1.8
a2dSensorMin
Minimum analog value, given as an integer. The analog measurement is
scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is
customVoltage(9) or customCurrent(11), then this field has a user-
defined value…
Integer32r/w
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.2.11.1.9
a2dSensorMax
Maximum analog value, given as an integer. The analog measurement is
scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is
customVoltage(9) or customCurrent(11), then this field has a user-
defined value…
Integer32r/w
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.2.11.1.10
a2dSensorLowLabel
Label for 0 (low) binary value. This field is only applicable if
a2dSensorMode is one of the binary modes. If a2dSensorMode is
customBinary(10), then this field is user-defined. Otherwise, it has a
pre-defined value bas…
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.11
a2dSensorHighLabel
Label for 1 (high) binary value. The field is only applicable if
a2dSensorMode is one of the binary modes. If a2dSensorMode is
customBinary(10), then this field is user-defined. Otherwise, it has a
pre-defined value bas…
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.12
a2dSensorAnalogLabel
Label for the analog measurement
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.13
.1.3.6.1.4.1.21239.5.2.12 · 1 row entry · 5 columns
Remote humidity sensor
humiditySensorEntry entry .1.3.6.1.4.1.21239.5.2.12.1
Entry in the humiditySensorTable table: each entry contains an index
and other sensor details
Indexes
humiditySensorIndex
Column Syntax OID
humiditySensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.12.1.1
humiditySensorSerial
Serial number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.2.12.1.2
humiditySensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.12.1.3
humiditySensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.12.1.4
humiditySensorValue
Humidity value
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.12.1.5
.1.3.6.1.4.1.21239.5.2.13 · 1 row entry · 10 columns
2 Door Switch Sensor (SN-2D)
sn2dSensorEntry entry .1.3.6.1.4.1.21239.5.2.13.1
Entry in the sn2dSensorTable table: each entry contains an index and
other sensor details
Indexes
sn2dSensorIndex
Column Syntax OID
sn2dSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.13.1.1
sn2dSensorSerial
Serial number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.2.13.1.2
sn2dSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.13.1.3
sn2dSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.13.1.4
sn2dSensorDoor1Label
Door switch 1 label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.13.1.5
sn2dSensorDoor1State
Door switch 1 state:
1 = open
2 = closed
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.21239.5.2.13.1.6
sn2dSensorDoor1DisplayState
Door switch 1 state given as a string
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.13.1.7
sn2dSensorDoor2Label
Door switch 2 label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.13.1.8
sn2dSensorDoor2State
Door switch 2 state:
1 = open
2 = closed
Enumeration
Enumerated Values:
1open
2closed
.1.3.6.1.4.1.21239.5.2.13.1.9
sn2dSensorDoor2DisplayState
Door switch 2 state given as a string
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.13.1.10
.1.3.6.1.4.1.21239.5.2.30.1.1 · 1 row entry · 5 columns
Table that contains general VRC information
vrcMainEntry entry .1.3.6.1.4.1.21239.5.2.30.1.1.1
Entry in the vrcMainTable: each entry represents a VRC device
Indexes
vrcMainIndex
Column Syntax OID
vrcMainIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.1.1.1
vrcMainSerial
Serial number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.2.30.1.1.1.2
vrcMainName
VRC name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.1.1.3
vrcMainLabel
VRC label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.30.1.1.1.4
vrcMainAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.30.1.1.1.5
.1.3.6.1.4.1.21239.5.2.30.1.2 · 1 row entry · 29 columns
Table that contains general VRC status
vrcMainPtEntry entry .1.3.6.1.4.1.21239.5.2.30.1.2.1
Entry in the vrcMainPtTable: each entry contains status data for a VRC
device
Indexes
vrcMainPtIndex
Column Syntax OID
vrcMainPtIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.2.1.1
vrcMainPtRunState
VRC run state:
1 = on
2 = off
Enumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.21239.5.2.30.1.2.1.2
vrcMainPtEevOpened
Eev opened value (percent)
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.2.1.3
vrcMainPtAlarmNumbers
Alarm numbers value
Integer32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.2.1.4
vrcMainPtHistoryAlarmNumbers
History alarm numbers value
Integer32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.2.1.5
vrcMainPtHpAbnRecordCnt
Hp Abnormal record count
Integer32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.2.1.6
vrcMainPtMonitorBaudrate
Monitor baud rate:
1 = error
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200
Enumeration
Enumerated Values:
1error
2baud1200
3baud2400
4baud4800
5baud9600
6baud19200
.1.3.6.1.4.1.21239.5.2.30.1.2.1.7
vrcMainPtMonitorAddress
Monitor address
Integer32
Constraints:
range: 1-247
.1.3.6.1.4.1.21239.5.2.30.1.2.1.8
vrcMainPtLp
Lp status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.9
vrcMainPtFilterMaintRemind
Filter maintenance reminder status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.10
vrcMainPtCoolingFlag
Cooling flag
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.11
vrcMainPtFirstOnFlag
First on flag
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.12
vrcMainPtNewAlarmFlag
New alarm flag
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.13
vrcMainPtComAlarmOutState
Common alarm output state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.14
vrcMainPtHighWaterInput
High water input
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.15
vrcMainPtHighWaterAlarm
High water alarm status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.16
vrcMainPtWaterUnderFloorAlarm
Water under floor alarm status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.17
vrcMainPtSwShutDownStatus
Software shutdown status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.18
vrcMainPtRemoteShutdown
Remote shutdown status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.19
vrcMainPtRemoteShutDownFlag
Remote shutdown flag
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.20
vrcMainPtRemoteShutDownAlarm
Remote shutdown alarm status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.21
vrcMainPtHmiShutDownFlag
Hmi shutdown flag
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.22
vrcMainPtLpAlarm
Low pressure alarm status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.23
vrcMainPtHpAlarm
High pressure alarm status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.24
vrcMainPtLpFreqAlarm
Low pressure frequently alarm status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.25
vrcMainPtHpFreqAlarm
High pressure frequently alarm status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.26
vrcMainPtLpSensorFailAlarm
Low pressure sensor failure alarm status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.27
vrcMainPtHpSensorFailAlarm
High pressure sensor failure alarm status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.28
vrcMainPtEevCommFailAlarm
Eev communication failure alarm status
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.2.1.29
.1.3.6.1.4.1.21239.5.2.30.1.3 · 1 row entry · 35 columns
Table that contains general VRC configuration
vrcMainCfgEntry entry .1.3.6.1.4.1.21239.5.2.30.1.3.1
Entry in the vrcMainCfgTable: each entry contains general config
fields for a VRC device
Indexes
vrcMainCfgIndex
Column Syntax OID
vrcMainCfgIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.3.1.1
vrcMainCfgModelSelect
Model Selection:
1 = TMM-Local 220V 50/60HZ
2 = TMM-Global 208/230V 50/60HZ
3 = TMM-Global 120V 50/60HZ
4 = SC 220V 50/60HZ
5 = 0U 220V 50/60HZ
6 = SS 208/230V 50/60HZ
7 = SS 120V 50/60HZ
Enumerationr/w
Enumerated Values:
1tmLoc
2r035Ap
3r035Ak
4scLoc
5zeroULoc
6r035Ep
7r035Ek
.1.3.6.1.4.1.21239.5.2.30.1.3.1.2
vrcMainCfgSystemTimeYear
System time - year
Integer32r/w
Constraints:
range: 2000-2099
.1.3.6.1.4.1.21239.5.2.30.1.3.1.3
vrcMainCfgSystemTimeMonth
System time - month
Integer32r/w
Constraints:
range: 1-12
.1.3.6.1.4.1.21239.5.2.30.1.3.1.4
vrcMainCfgSystemTimeDay
System time - day
Integer32r/w
Constraints:
range: 1-31
.1.3.6.1.4.1.21239.5.2.30.1.3.1.5
vrcMainCfgSystemTimeHour
System time - hour
Integer32r/w
Constraints:
range: 0-23
.1.3.6.1.4.1.21239.5.2.30.1.3.1.6
vrcMainCfgSystemTimeMin
System time - minutes
Integer32r/w
Constraints:
range: 0-59
.1.3.6.1.4.1.21239.5.2.30.1.3.1.7
vrcMainCfgSystemTimeSec
System time - seconds
Integer32r/w
Constraints:
range: 0-59
.1.3.6.1.4.1.21239.5.2.30.1.3.1.8
vrcMainCfgEevShtSettingMin
Min Eev sht in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo. The settable range is determined by the current
temperature units.
Celsius: 50 to 200
Fahrenheit: 90 to 359
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.3.1.9
vrcMainCfgEevShtSettingMax
Max Eev sht in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo. The settable range is determined by the current
temperature units.
Celsius: 50 to 200
Fahrenheit: 90 to 359
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.3.1.10
vrcMainCfgEevValveCloseSht
Eev valve close sht in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 0 to 100
Fahrenheit: 0 to 179
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.3.1.11
vrcMainCfgEevMopPressSetting
Eev mop pressure setting in tenths of a bar.
decibarsInteger32r/w
Constraints:
range: 0-200
.1.3.6.1.4.1.21239.5.2.30.1.3.1.12
vrcMainCfgLpdt
Low pressure dt in seconds
secondsInteger32r/w
Constraints:
range: 30-600
.1.3.6.1.4.1.21239.5.2.30.1.3.1.13
vrcMainCfgDeadBand
Dead band in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo. The settable range is determined by the current
temperature units.
Celsius: 0 to 20
Fahrenheit: 0 to 35
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.3.1.14
vrcMainCfgOnOffSwitch
On-off switch
SNMPv2-TCTruthValuer/w
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.3.1.15
vrcMainCfgVacuumState
Vacuum state
SNMPv2-TCTruthValuer/w
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.3.1.16
vrcMainCfgControlMode
Control mode:
1 = supply
2 = return
Enumerationr/w
Enumerated Values:
1supply
2return
.1.3.6.1.4.1.21239.5.2.30.1.3.1.17
vrcMainCfgManualRunEnable
Manual run enable
SNMPv2-TCTruthValuer/w
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.3.1.18
vrcMainCfgRemShutdownInput
Remote shutdown input
SNMPv2-TCTruthValuer/w
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.3.1.19
vrcMainCfgMonitorShutDownFlag
Monitor shutdown flag
SNMPv2-TCTruthValuer/w
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.3.1.20
vrcMainCfgFirstOnPassword
First on password value
Integer32r/w
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.3.1.21
vrcMainCfgFilterMaintSetting
Filter maintenance setting
SNMPv2-TCTruthValuer/w
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.3.1.22
vrcMainCfgFilterMaintRemindTime
Time between filter maintenance reminders in days
daysInteger32r/w
Constraints:
range: 30-360
.1.3.6.1.4.1.21239.5.2.30.1.3.1.23
vrcMainCfgFilterMaintRemindCtrl
Filter maintenance reminder:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.24
vrcMainCfgCommonAlarmOutputDir
Common alarm output direction
SNMPv2-TCTruthValuer/w
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.3.1.25
vrcMainCfgHpAbnAlarmSetting
Abnormal high pressure alarm value in tenths of a bar
decibarsInteger32r/w
Constraints:
range: 300-360
.1.3.6.1.4.1.21239.5.2.30.1.3.1.26
vrcMainCfgLpAlarmCtrl
Low pressure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.27
vrcMainCfgHpAlarmCtrl
High pressure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.28
vrcMainCfgLpFreqAlarmCtrl
Low pressure frequently alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.29
vrcMainCfgHpFreqAlarmCtrl
High pressure frequently alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.30
vrcMainCfgLpSensorFailAlarmCtrl
Low pressure sensor failure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.31
vrcMainCfgHpSensorFailAlarmCtrl
High pressure sensor failure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.32
vrcMainCfgHighWaterAlarmCtrl
High water alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.33
vrcMainCfgRemShutdownAlarmCtrl
Remote shutdown alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.34
vrcMainCfgEevCommFailAlarmCtrl
Eev communication failure alarm:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.3.1.35
.1.3.6.1.4.1.21239.5.2.30.1.4 · 1 row entry · 3 columns
Table that contains VRC out-fan status
vrcOutFanPtEntry entry .1.3.6.1.4.1.21239.5.2.30.1.4.1
Entry in the vrcOutFanPtTable: each entry represents data for a VRC
out-fan
Indexes
vrcOutFanPtIndex
Column Syntax OID
vrcOutFanPtIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.4.1.1
vrcOutFanPtName
Out-fan name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.4.1.2
vrcOutFanPtSpeed
Fan speed (percent)
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.4.1.3
.1.3.6.1.4.1.21239.5.2.30.1.5 · 1 row entry · 6 columns
Table used for VRC out-fan configuration
vrcOutFanCfgEntry entry .1.3.6.1.4.1.21239.5.2.30.1.5.1
Entry in the vrcOutFanCfgTable: each entry contains config fields for
a VRC out-fan
Indexes
vrcOutFanCfgIndex
Column Syntax OID
vrcOutFanCfgIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.5.1.1
vrcOutFanCfgStartPress
Out-fan start pressure in tenths of a bar
decibarsInteger32r/w
Constraints:
range: 190-250
.1.3.6.1.4.1.21239.5.2.30.1.5.1.2
vrcOutFanCfgPressSetting
Out-fan pressure setting in tenths of a bar
decibarsInteger32r/w
Constraints:
range: 50-80
.1.3.6.1.4.1.21239.5.2.30.1.5.1.3
vrcOutFanCfgMinPowerVoltage
Min out-fan voltage (percent)
%Integer32r/w
Constraints:
range: 30-50
.1.3.6.1.4.1.21239.5.2.30.1.5.1.4
vrcOutFanCfgMaxPowerVoltage
Max out-fan voltage (percent)
%Integer32r/w
Constraints:
range: 60-100
.1.3.6.1.4.1.21239.5.2.30.1.5.1.5
vrcOutFanCfgSpeed
Out-fan speed (percent)
%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.5.1.6
.1.3.6.1.4.1.21239.5.2.30.1.6 · 1 row entry · 4 columns
Table that contains VRC in-fan status
vrcInFanPtEntry entry .1.3.6.1.4.1.21239.5.2.30.1.6.1
Entry in the vrcInFanPtTable: each entry represents data for a VRC in-
fan
Indexes
vrcInFanPtIndex
Column Syntax OID
vrcInFanPtIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.6.1.1
vrcInFanPtName
In-fan name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.6.1.2
vrcInFanPtRunTimeHours
In-fan run time in hours
hoursInteger32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.6.1.3
vrcInFanPtStartStopCount
In-fan start/stop count
Integer32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.6.1.4
.1.3.6.1.4.1.21239.5.2.30.1.7 · 1 row entry · 24 columns
Table used for VRC in-fan configuration
vrcInFanCfgEntry entry .1.3.6.1.4.1.21239.5.2.30.1.7.1
Entry in the vrcInFanCfgTable: each entry contains config fields for a
VRC in-fan
Indexes
vrcInFanCfgIndex
Column Syntax OID
vrcInFanCfgIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.1
vrcInFanCfgOutputStatus
In-fan output status
SNMPv2-TCTruthValuer/w
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.7.1.2
vrcInFanCfgLowSpeedStep
In-fan low speed step in tenths of a percent per second
0.1%/sInteger32r/w
Constraints:
range: 1-20
.1.3.6.1.4.1.21239.5.2.30.1.7.1.3
vrcInFanCfgHighSpeedStep
In-fan high speed step in tenths of a percent per second
0.1%/sInteger32r/w
Constraints:
range: 1-50
.1.3.6.1.4.1.21239.5.2.30.1.7.1.4
vrcInFanCfgMinSpeed
Min in-fan speed (percent)
%Integer32r/w
Constraints:
range: 30-80
.1.3.6.1.4.1.21239.5.2.30.1.7.1.5
vrcInFanCfgStandardSpeed
Standard in-fan speed (percent)
%Integer32r/w
Constraints:
range: 80-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.6
vrcInFanCfgMinCfc
Min in-fan cfc (percent)
%Integer32r/w
Constraints:
range: 0-30
.1.3.6.1.4.1.21239.5.2.30.1.7.1.7
vrcInFanCfgStandardCfc
Standard in-fan cfc (percent)
%Integer32r/w
Constraints:
range: 85-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.8
vrcInFanCfgStartDelay
In-fan start delay in seconds
secondsInteger32r/w
Constraints:
range: 10-600
.1.3.6.1.4.1.21239.5.2.30.1.7.1.9
vrcInFanCfgStopDelay
In-fan stop delay in seconds
secondsInteger32r/w
Constraints:
range: 10-300
.1.3.6.1.4.1.21239.5.2.30.1.7.1.10
vrcInFanCfgReduceSpeedDelay
In-fan reduce speed delay in seconds
secondsInteger32r/w
Constraints:
range: 0-300
.1.3.6.1.4.1.21239.5.2.30.1.7.1.11
vrcInFanCfgJumpBand1
In-fan jump band 1 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.12
vrcInFanCfgJumpBand2
In-fan jump band 2 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.13
vrcInFanCfgJumpBand3
In-fan jump band 3 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.14
vrcInFanCfgJumpBand4
In-fan jump band 4 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.15
vrcInFanCfgJumpBand5
In-fan jump band 5 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.7.1.16
vrcInFanCfgJumpFreq1
In-fan jump frequency 1 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.7.1.17
vrcInFanCfgJumpFreq2
In-fan jump frequency 2 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.7.1.18
vrcInFanCfgJumpFreq3
In-fan jump frequency 3 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.7.1.19
vrcInFanCfgJumpFreq4
In-fan jump frequency 4 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.7.1.20
vrcInFanCfgJumpFreq5
In-fan jump frequency 5 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.7.1.21
vrcInFanCfgTempP
In-fan temperature P in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo.
decidegreesInteger32r/w
Constraints:
range: 10-150
.1.3.6.1.4.1.21239.5.2.30.1.7.1.22
vrcInFanCfgTempI
In-fan temperature I in seconds
secondsInteger32r/w
Constraints:
range: 0-900
.1.3.6.1.4.1.21239.5.2.30.1.7.1.23
vrcInFanCfgTempD
In-fan temperature D in seconds
secondsInteger32r/w
Constraints:
range: 0-900
.1.3.6.1.4.1.21239.5.2.30.1.7.1.24
.1.3.6.1.4.1.21239.5.2.30.1.8 · 1 row entry · 23 columns
Table that contains VRC compressor status
vrcCompPtEntry entry .1.3.6.1.4.1.21239.5.2.30.1.8.1
Entry in the vrcCompPtTable: each entry represents data for a VRC
compressor
Indexes
vrcCompPtIndex
Column Syntax OID
vrcCompPtIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.8.1.1
vrcCompPtName
Compressor name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.8.1.2
vrcCompPtCapacity
Compressor capacity value (percent)
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.8.1.3
vrcCompPtRunTimeHours
Compressor run time in hours
hoursInteger32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.8.1.4
vrcCompPtStartStopCount
Compressor start/stop count
Integer32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.8.1.5
vrcCompPtDriverFaultU00
Compressor driver fault alarm U00 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.6
vrcCompPtDriverFaultU01
Compressor driver fault alarm U01 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.7
vrcCompPtDriverFaultU02
Compressor driver fault alarm U02 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.8
vrcCompPtDriverFaultU03
Compressor driver fault alarm U03 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.9
vrcCompPtDriverFaultU04
Compressor driver fault alarm U04 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.10
vrcCompPtDriverFaultU05
Compressor driver fault alarm U05 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.11
vrcCompPtDriverFaultU06
Compressor driver fault alarm U06 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.12
vrcCompPtDriverFaultU07
Compressor driver fault alarm U07 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.13
vrcCompPtDriverFaultU08
Compressor driver fault alarm U08 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.14
vrcCompPtDriverFaultU09
Compressor driver fault alarm U09 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.15
vrcCompPtDriverFaultU10
Compressor driver fault alarm U10 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.16
vrcCompPtDriverFaultU11
Compressor driver fault alarm U11 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.17
vrcCompPtDriverFaultU12
Compressor driver fault alarm U12 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.18
vrcCompPtDriverFaultU13
Compressor driver fault alarm U13 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.19
vrcCompPtDriverFaultU14
Compressor driver fault alarm U14 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.20
vrcCompPtDriverFaultU15
Compressor driver fault alarm U15 state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.21
vrcCompPtDriverCommFailAlarm
Compressor driver communication failure alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.22
vrcCompPtFaultLockAlarm
Compressor fault lock alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.8.1.23
.1.3.6.1.4.1.21239.5.2.30.1.9 · 1 row entry · 27 columns
Table used for VRC compressor configuration
vrcCompCfgEntry entry .1.3.6.1.4.1.21239.5.2.30.1.9.1
Entry in the vrcCompCfgTable: each entry contains config fields for a
VRC compressor
Indexes
vrcCompCfgIndex
Column Syntax OID
vrcCompCfgIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.1
vrcCompCfgOutputStatus
Compressor output status
SNMPv2-TCTruthValuer/w
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.9.1.2
vrcCompCfgOutputDeadBand
Compressor output dead band in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-50
.1.3.6.1.4.1.21239.5.2.30.1.9.1.3
vrcCompCfgCapacityOutputValue
Compressor capacity output (percent)
%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.4
vrcCompCfgMinCapacity
Compressor min capacity (percent)
%Integer32r/w
Constraints:
range: 15-50
.1.3.6.1.4.1.21239.5.2.30.1.9.1.5
vrcCompCfgStartCapacity
Compressor start capacity (percent)
%Integer32r/w
Constraints:
range: 40-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.6
vrcCompCfgStandardCapacity
Compressor standard capacity (percent)
%Integer32r/w
Constraints:
range: 80-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.7
vrcCompCfgStartCfc
Compressor start cfc (percent)
%Integer32r/w
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.8
vrcCompCfgStopCfc
Compressor stop cfc (percent)
%Integer32r/w
Constraints:
range: -200--50
.1.3.6.1.4.1.21239.5.2.30.1.9.1.9
vrcCompCfgMinRunTime
Compressor min run time in minutes
minutesInteger32r/w
Constraints:
range: 0-30
.1.3.6.1.4.1.21239.5.2.30.1.9.1.10
vrcCompCfgMinStopTime
Compressor min stop time in minutes
minutesInteger32r/w
Constraints:
range: 0-10
.1.3.6.1.4.1.21239.5.2.30.1.9.1.11
vrcCompCfgJumpBand1
Compressor jump band 1 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.12
vrcCompCfgJumpBand2
Compressor jump band 2 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.13
vrcCompCfgJumpBand3
Compressor jump band 3 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.14
vrcCompCfgJumpBand4
Compressor jump band 4 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.15
vrcCompCfgJumpBand5
Compressor jump band 5 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.30.1.9.1.16
vrcCompCfgJumpFreq1
Compressor jump frequency 1 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.9.1.17
vrcCompCfgJumpFreq2
Compressor jump frequency 2 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.9.1.18
vrcCompCfgJumpFreq3
Compressor jump frequency 3 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.9.1.19
vrcCompCfgJumpFreq4
Compressor jump frequency 4 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.9.1.20
vrcCompCfgJumpFreq5
Compressor jump frequency 5 in tenths of a percent
0.1%Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.21239.5.2.30.1.9.1.21
vrcCompCfgTempP
Compressor temperature P in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 10 to 150
Fahrenheit: 18 to 269
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.9.1.22
vrcCompCfgTempI
Compressor temperature I in seconds
secondsInteger32r/w
Constraints:
range: 0-900
.1.3.6.1.4.1.21239.5.2.30.1.9.1.23
vrcCompCfgTempD
Compressor temperature D in seconds
secondsInteger32r/w
Constraints:
range: 0-900
.1.3.6.1.4.1.21239.5.2.30.1.9.1.24
vrcCompCfgDriverFaultAlmCtrl
Compressor driver fault alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.9.1.25
vrcCompCfgDriverCommFailAlmCtrl
Compressor driver communication failure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.9.1.26
vrcCompCfgFaultLockAlmCtrl
Compressor fault lock alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.9.1.27
.1.3.6.1.4.1.21239.5.2.30.1.10 · 1 row entry · 5 columns
Table that contains VRC return status
vrcReturnPtEntry entry .1.3.6.1.4.1.21239.5.2.30.1.10.1
Entry in the vrcReturnPtTable: each entry represents return data for a
VRC
Indexes
vrcReturnPtIndex
Column Syntax OID
vrcReturnPtIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.10.1.1
vrcReturnPtName
Return name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.10.1.2
vrcReturnPtTemp
Return temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120
decidegreesSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.10.1.3
vrcReturnPtHighTempAlarm
Return high temperature alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.10.1.4
vrcReturnPtTempSensorFailAlarm
Return temperature sensor failure alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.10.1.5
.1.3.6.1.4.1.21239.5.2.30.1.11 · 1 row entry · 9 columns
Table used for VRC return configuration
vrcReturnCfgEntry entry .1.3.6.1.4.1.21239.5.2.30.1.11.1
Entry in the vrcReturnCfgTable: each entry contains config fields for
VRC return
Indexes
vrcReturnCfgIndex
Column Syntax OID
vrcReturnCfgIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.11.1.1
vrcReturnCfgOilCycle
Return oil cycle in tenths of an hour
decihoursInteger32r/w
Constraints:
range: 5-50
.1.3.6.1.4.1.21239.5.2.30.1.11.1.2
vrcReturnCfgOilRunCapacity
Return Oil run capacity (percent)
%Integer32r/w
Constraints:
range: 50-100
.1.3.6.1.4.1.21239.5.2.30.1.11.1.3
vrcReturnCfgOilRunTime
Return oil run time in minutes
minutesInteger32r/w
Constraints:
range: 0-10
.1.3.6.1.4.1.21239.5.2.30.1.11.1.4
vrcReturnCfgTempCalValue
Return temperature calibration value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: -100 to 100
Fahrenheit:…
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.11.1.5
vrcReturnCfgTempSetting
Return temperature setting in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 250 to 350
Fahrenheit: 770 to 949
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.11.1.6
vrcReturnCfgHighTempAlarmValue
Return high temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: 300 to 450
Fahrenheit: 8…
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.11.1.7
vrcReturnCfgHighTempAlarmCtrl
Return high temperature alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.11.1.8
vrcReturnCfgTempSensFailAlmCtrl
Return temperature sensor failure alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.11.1.9
.1.3.6.1.4.1.21239.5.2.30.1.12 · 1 row entry · 6 columns
Table that contains VRC supply status
vrcSupplyPtEntry entry .1.3.6.1.4.1.21239.5.2.30.1.12.1
Entry in the vrcSupplyPtTable: each entry represents supply data for a
VRC
Indexes
vrcSupplyPtIndex
Column Syntax OID
vrcSupplyPtIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.12.1.1
vrcSupplyPtName
Supply name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.12.1.2
vrcSupplyPtTemp
Supply temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120
decidegreesSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.12.1.3
vrcSupplyPtLowTempAlarm
Supply low temperature alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.12.1.4
vrcSupplyPtHighTempAlarm
Supply high temperature alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.12.1.5
vrcSupplyPtTempSensorFailAlarm
Supply temperature sensor failure alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.12.1.6
.1.3.6.1.4.1.21239.5.2.30.1.13 · 1 row entry · 8 columns
Table used for VRC supply configuration
vrcSupplyCfgEntry entry .1.3.6.1.4.1.21239.5.2.30.1.13.1
Entry in the vrcSupplyCfgTable: each entry contains config fields for
a VRC supply
Indexes
vrcSupplyCfgIndex
Column Syntax OID
vrcSupplyCfgIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.13.1.1
vrcSupplyCfgTempCalValue
Supply temperature calibration value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: -100 to 100
Fahrenheit:…
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.13.1.2
vrcSupplyCfgTempSetting
Supply temperature setting in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 130 to 280
Fahrenheit: 554 to 823
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.13.1.3
vrcSupplyCfgLowTempAlarmValue
Supply low temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: 50 to 200
Fahrenheit: 410…
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.13.1.4
vrcSupplyCfgHighTempAlarmValue
Supply high temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: 200 to 350
Fahrenheit: 6…
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.13.1.5
vrcSupplyCfgLowTempAlmCtrl
Supply low temperature alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.13.1.6
vrcSupplyCfgHighTempAlmCtrl
Supply high temperature alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.13.1.7
vrcSupplyCfgTempSensFailAlmCtrl
Supply temperature sensor failure alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.13.1.8
.1.3.6.1.4.1.21239.5.2.30.1.14 · 1 row entry · 9 columns
Table that contains VRC power status
vrcPowerPtEntry entry .1.3.6.1.4.1.21239.5.2.30.1.14.1
Entry in the vrcPowerPtTable: each entry represents power data for a
VRC
Indexes
vrcPowerPtIndex
Column Syntax OID
vrcPowerPtIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.14.1.1
vrcPowerPtName
Power name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.14.1.2
vrcPowerPtVoltage
Power voltage measurement in tenths of a volt
decivoltsInteger32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.14.1.3
vrcPowerPtFrequency
Power frequency measurement in tenths of hertz
decihertzInteger32
Constraints:
range: -32768-32767
.1.3.6.1.4.1.21239.5.2.30.1.14.1.4
vrcPowerPtLowVoltageAlarm
Power low voltage alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.14.1.5
vrcPowerPtHighVoltageAlarm
Power high voltage alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.14.1.6
vrcPowerPtLossOfPhasePowerAlarm
Phase power loss alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.14.1.7
vrcPowerPtLossOfPowerAlarm
Power loss alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.14.1.8
vrcPowerPtFrequencyErrorAlarm
Power frequency error alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.14.1.9
.1.3.6.1.4.1.21239.5.2.30.1.15 · 1 row entry · 7 columns
Table used for VRC power configuration
vrcPowerCfgEntry entry .1.3.6.1.4.1.21239.5.2.30.1.15.1
Entry in the vrcPowerCfgTable: each entry contains config fields for
VRC power
Indexes
vrcPowerCfgIndex
Column Syntax OID
vrcPowerCfgIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.15.1.1
vrcPowerCfgLowVoltageSetting
Power low voltage setting in volts
voltsInteger32r/w
Constraints:
range: 100-230
.1.3.6.1.4.1.21239.5.2.30.1.15.1.2
vrcPowerCfgHighVoltageSetting
Power high voltage setting in volts
voltsInteger32r/w
Constraints:
range: 100-300
.1.3.6.1.4.1.21239.5.2.30.1.15.1.3
vrcPowerCfgLowVoltageAlarmCtrl
Power low voltage alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.15.1.4
vrcPowerCfgHighVoltageAlarmCtrl
Power high voltage alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.15.1.5
vrcPowerCfgLossOfPowerAlarmCtrl
Power loss alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.15.1.6
vrcPowerCfgFreqErrorAlarmCtrl
Power frequency error alarm control:
1 = close
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
1close
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.15.1.7
.1.3.6.1.4.1.21239.5.2.30.1.16 · 1 row entry · 3 columns
Table that contains VRC outdoor status
vrcOutdoorPtEntry entry .1.3.6.1.4.1.21239.5.2.30.1.16.1
Entry in the vrcOutdoorPtTable: each entry represents data for a VRC
outdoor
Indexes
vrcOutdoorPtIndex
Column Syntax OID
vrcOutdoorPtIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.16.1.1
vrcOutdoorPtName
Outdoor name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.16.1.2
vrcOutdoorPtTemp
Outdoor temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120
decidegreesSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.16.1.3
.1.3.6.1.4.1.21239.5.2.30.1.18 · 1 row entry · 7 columns
Table that contains VRC discharge status
vrcDischPtEntry entry .1.3.6.1.4.1.21239.5.2.30.1.18.1
Entry in the vrcDischPtTable: each entry represents discharge data for
a VRC
Indexes
vrcDischPtIndex
Column Syntax OID
vrcDischPtIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.18.1.1
vrcDischPtName
Discharge name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.18.1.2
vrcDischPtTemp
Discharge temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1560
Fahrenheit: -400 to 3128
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.18.1.3
vrcDischPtPressure
Discharge air pressure value in tenths of a bar
decibarsInteger32r/w
Constraints:
range: 0-460
.1.3.6.1.4.1.21239.5.2.30.1.18.1.4
vrcDischPtHighTempAlarm
Discharge high temperature alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.18.1.5
vrcDischPtHighTempFreqAlarm
Discharge high temperature frequently alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.18.1.6
vrcDischPtTempSensorFailAlarm
Discharge temperature sensor failure alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.18.1.7
.1.3.6.1.4.1.21239.5.2.30.1.19 · 1 row entry · 6 columns
Table used for VRC discharge configuration
vrcDischCfgEntry entry .1.3.6.1.4.1.21239.5.2.30.1.19.1
Entry in the vrcDischCfgTable: each entry contains config fields for
VRC discharge
Indexes
vrcDischCfgIndex
Column Syntax OID
vrcDischCfgIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.19.1.1
vrcDischCfgTempCalValue
Discharge temperature calibration value in tenths of a degree. Units
are given by temperatureUnits field in deviceInfo. The settable range
is determined by the current temperature units.
Celsius: -100 to 100
Fahrenhe…
decidegreesSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.19.1.2
vrcDischCfgPressCalValue
Discharge pressure calibration value in tenths of a bar
decibarsInteger32r/w
Constraints:
range: -100-100
.1.3.6.1.4.1.21239.5.2.30.1.19.1.3
vrcDischCfgHighTempAlmCtrl
Discharge high temperature alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.19.1.4
vrcDischCfgHighTempFreqAlmCtrl
Discharge high temperature frequenctly alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.19.1.5
vrcDischCfgTempSensFailAlmCtrl
Discharge temperature sensor failure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.19.1.6
.1.3.6.1.4.1.21239.5.2.30.1.20 · 1 row entry · 6 columns
Table that contains VRC suction status
vrcSuctPtEntry entry .1.3.6.1.4.1.21239.5.2.30.1.20.1
Entry in the vrcSuctPtTable: each entry represents suction data for a
VRC
Indexes
vrcSuctPtIndex
Column Syntax OID
vrcSuctPtIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.20.1.1
vrcSuctPtName
Suction name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.30.1.20.1.2
vrcSuctPtTemp
Suction temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120
decidegreesSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.20.1.3
vrcSuctPtPressure
Suction air pressure in tenths of a bar
decibarsInteger32
Constraints:
range: 0-173
.1.3.6.1.4.1.21239.5.2.30.1.20.1.4
vrcSuctPtSuperHeatTemp
Suction super heat temperature in tenths of a degree. Units are given
by temperatureUnits field in deviceInfo. The range is determined by
the current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120
decidegreesSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21239.5.2.30.1.20.1.5
vrcSuctPtTempSensorFailAlarm
Suction temperature sensor failure alarm state
SNMPv2-TCTruthValue
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.21239.5.2.30.1.20.1.6
.1.3.6.1.4.1.21239.5.2.30.1.21 · 1 row entry · 3 columns
Table used for VRC suction configuration
vrcSuctCfgEntry entry .1.3.6.1.4.1.21239.5.2.30.1.21.1
Entry in the vrcSuctCfgTable: each entry contains config fields for
VRC suction
Indexes
vrcSuctCfgIndex
Column Syntax OID
vrcSuctCfgIndex
Unique id for each entry in the table
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.30.1.21.1.1
vrcSuctCfgPressCalValue
Suction pressure calibration value in tenths of a bar
decibarsInteger32r/w
Constraints:
range: -100-100
.1.3.6.1.4.1.21239.5.2.30.1.21.1.2
vrcSuctCfgTempSensFailAlmCtrl
Suction temperature sensor failure alarm control:
2 = suspend
3 = open
Enumerationr/w
Enumerated Values:
2suspend
3open
.1.3.6.1.4.1.21239.5.2.30.1.21.1.3