pduOutletMeterRealPower
VERTIV-V5-MIB ·
.1.3.6.1.4.1.21239.5.2.3.6.1.12
Object
column
watts Unsigned32
Real power for outlet in watts
Context
- MIB
- VERTIV-V5-MIB
- OID
.1.3.6.1.4.1.21239.5.2.3.6.1.12- Type
- column
- Access
- readonly
- Status
- current
- Units
- watts
- Parent
- pduOutletMeterEntry
- Table
- pduOutletMeterTable
- Siblings
- 10
Syntax
watts Unsigned32
Values & Constraints
Object Constraints
range: 0-9999
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduOutletMeterIndex Table entry index value | column | Integer32 | .1.3.6.1.4.1.21239.5.2.3.6.1.1 |
| pduOutletMeterApparentPower Apparent power for outlet in volt-amps | column | volt-amps Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.6.1.13 |
| pduOutletMeterPowerFactor Power factor for outlet | column | % Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.6.1.14 |
| pduOutletMeterEnergy Accumulated energy for outlet in watt-hours | column | watt-hours Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.6.1.15 |
| pduOutletMeterReset Used to reset energy. If read, the value is none(8). It can be set to
resetEnergy(1), which sets outlet energy to 0 | column | Enumeration | .1.3.6.1.4.1.21239.5.2.3.6.1.16 |
| pduOutletCurrentCrestFactor Current crest factor for outlet, in hundredths | column | Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.6.1.19 |
| pduOutletMeterName PDU outlet name (factory-assigned) | column | OctetString | .1.3.6.1.4.1.21239.5.2.3.6.1.2 |
| pduOutletMeterLabel PDU outlet label (user-defined) | column | OctetString | .1.3.6.1.4.1.21239.5.2.3.6.1.3 |
| pduOutletMeterVoltage PDU outlet voltage in tenths of a volt | column | decivolts (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.6.1.4 |
| pduOutletMeterCurrent PDU outlet current reading in hundredths of an amp | column | centiamps (rms) Unsigned32 | .1.3.6.1.4.1.21239.5.2.3.6.1.8 |