vrcSupplyCfgTempSetting
VERTIV-V5-MIB ·
.1.3.6.1.4.1.21239.5.2.30.1.13.1.3
Object
Supply temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 130 to 280 Fahrenheit: 554 to 823
Context
- MIB
- VERTIV-V5-MIB
- OID
.1.3.6.1.4.1.21239.5.2.30.1.13.1.3- Type
- column
- Access
- readwrite
- Status
- current
- Units
- decidegrees
- Parent
- vrcSupplyCfgEntry
- Table
- vrcSupplyCfgTable
- Siblings
- 7
Syntax
decidegrees SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| vrcSupplyCfgIndex Unique id for each entry in the table | column | Integer32 | .1.3.6.1.4.1.21239.5.2.30.1.13.1.1 |
| vrcSupplyCfgTempCalValue Supply temperature calibration value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature un… | column | decidegrees SNMPv2-SMIInteger32 | .1.3.6.1.4.1.21239.5.2.30.1.13.1.2 |
| vrcSupplyCfgLowTempAlarmValue Supply low temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature unit… | column | decidegrees SNMPv2-SMIInteger32 | .1.3.6.1.4.1.21239.5.2.30.1.13.1.4 |
| vrcSupplyCfgHighTempAlarmValue Supply high temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature uni… | column | decidegrees SNMPv2-SMIInteger32 | .1.3.6.1.4.1.21239.5.2.30.1.13.1.5 |
| vrcSupplyCfgLowTempAlmCtrl Supply low temperature alarm control:
1 = close
2 = suspend
3 = open | column | Enumeration | .1.3.6.1.4.1.21239.5.2.30.1.13.1.6 |
| vrcSupplyCfgHighTempAlmCtrl Supply high temperature alarm control:
1 = close
2 = suspend
3 = open | column | Enumeration | .1.3.6.1.4.1.21239.5.2.30.1.13.1.7 |
| vrcSupplyCfgTempSensFailAlmCtrl Supply temperature sensor failure alarm control:
1 = close
2 = suspend
3 = open | column | Enumeration | .1.3.6.1.4.1.21239.5.2.30.1.13.1.8 |