vrcReturnCfgTempSetting
VERTIV-V5-MIB ·
.1.3.6.1.4.1.21239.5.2.30.1.11.1.6
Object
Return temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 250 to 350 Fahrenheit: 770 to 949
Context
- MIB
- VERTIV-V5-MIB
- OID
.1.3.6.1.4.1.21239.5.2.30.1.11.1.6- Type
- column
- Access
- readwrite
- Status
- current
- Units
- decidegrees
- Parent
- vrcReturnCfgEntry
- Table
- vrcReturnCfgTable
- Siblings
- 8
Syntax
decidegrees SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| vrcReturnCfgIndex Unique id for each entry in the table | column | Integer32 | .1.3.6.1.4.1.21239.5.2.30.1.11.1.1 |
| vrcReturnCfgOilCycle Return oil cycle in tenths of an hour | column | decihours Integer32 | .1.3.6.1.4.1.21239.5.2.30.1.11.1.2 |
| vrcReturnCfgOilRunCapacity Return Oil run capacity (percent) | column | % Integer32 | .1.3.6.1.4.1.21239.5.2.30.1.11.1.3 |
| vrcReturnCfgOilRunTime Return oil run time in minutes | column | minutes Integer32 | .1.3.6.1.4.1.21239.5.2.30.1.11.1.4 |
| vrcReturnCfgTempCalValue Return temperature calibration value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature un… | column | decidegrees SNMPv2-SMIInteger32 | .1.3.6.1.4.1.21239.5.2.30.1.11.1.5 |
| vrcReturnCfgHighTempAlarmValue Return high temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature uni… | column | decidegrees SNMPv2-SMIInteger32 | .1.3.6.1.4.1.21239.5.2.30.1.11.1.7 |
| vrcReturnCfgHighTempAlarmCtrl Return high temperature alarm control:
1 = close
2 = suspend
3 = open | column | Enumeration | .1.3.6.1.4.1.21239.5.2.30.1.11.1.8 |
| vrcReturnCfgTempSensFailAlmCtrl Return temperature sensor failure alarm control:
1 = close
2 = suspend
3 = open | column | Enumeration | .1.3.6.1.4.1.21239.5.2.30.1.11.1.9 |