RPS-SC300-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
34
Rows
34
Columns
299
dialOutNumberTable
table.1.3.6.1.4.1.1918.2.14.10.30.53.80
·
1 row entry
·
2 columns
Table for dialOutNumber
Entry for dialOutNumber
Indexes
dialOutNumberIndex
| Column | Syntax | OID |
|---|---|---|
|
dialOutNumberIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.30.53.80.1.1 |
|
dialOutNumber
The telephone numbers to be called (via a modem) if alarm reporting is enabled. Consult the modem documentation for appropriate dial modifiers to use with the ATD command. Leave blank to prevent dial-out.
|
OctetStringr/w Constraints: range: 0-30 |
.1.3.6.1.4.1.1918.2.14.10.30.53.80.1.10 |
smsNotificationTable
table.1.3.6.1.4.1.1918.2.14.10.30.53.90
·
1 row entry
·
6 columns
Table for smsNotification
Entry for smsNotification
Indexes
smsNotificationIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
smsNotificationIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.30.53.90.1.1 |
||||||||||
|
smsPhoneName
A name to identify this phone.
|
OctetStringr/w Constraints: range: 0-20 |
.1.3.6.1.4.1.1918.2.14.10.30.53.90.1.10 |
||||||||||
|
smsLevel
Sets the severity of alarms to be reported to this SMS receiver.
|
SeverityLevelr/w Textual Convention: SeverityLevel EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.53.90.1.20 |
||||||||||
|
smsPhoneNumber
The phone number for SMS notifications.
|
OctetStringr/w Constraints: range: 0-30 |
.1.3.6.1.4.1.1918.2.14.10.30.53.90.1.30 |
||||||||||
|
smsPrefix
This string is prepended to every SMS sent to this number, excluding responses to SMS commands.
|
OctetStringr/w Constraints: range: 0-60 |
.1.3.6.1.4.1.1918.2.14.10.30.53.90.1.40 |
||||||||||
|
smsEmailGateway
If a gateway address (e.g. phoneNumber@mms.gateway.com) is present send email to the gateway instead of using the modem.
|
OctetStringr/w Constraints: range: 0-40 |
.1.3.6.1.4.1.1918.2.14.10.30.53.90.1.50 |
snmpTrapReceiverTable
table.1.3.6.1.4.1.1918.2.14.10.30.60.50
·
1 row entry
·
8 columns
Table for snmpTrapReceiver
Entry for snmpTrapReceiver
Indexes
snmpTrapReceiverIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
snmpTrapReceiverIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.30.60.50.1.1 |
||||||||||
|
trapReceiverIpAddress
SNMP notifications of events are sent to this IP address.
|
OctetStringr/w Constraints: range: 1-64 |
.1.3.6.1.4.1.1918.2.14.10.30.60.50.1.20 |
||||||||||
|
trapReceiverPort
SNMP notifications of events are sent to this UDP port.
|
Unsigned16r/w Textual Convention: Unsigned16 Integer32Type Constraints: range: 0..65535 |
.1.3.6.1.4.1.1918.2.14.10.30.60.50.1.30 |
||||||||||
|
trapReceiverName
Name used to identify the receiver.
|
OctetStringr/w Constraints: range: 0-20 |
.1.3.6.1.4.1.1918.2.14.10.30.60.50.1.40 |
||||||||||
|
trapReceiverLevel
Sets the severity of alarms to be reported to this trap receiver.
|
SeverityLevelr/w Textual Convention: SeverityLevel EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.60.50.1.50 |
||||||||||
|
trapReceiverCommunity
Community to use for traps sent to the receiver.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.1918.2.14.10.30.60.50.1.60 |
||||||||||
|
trapReceiverMode
Set to Normal traps to send normal traps to a Network Management System on alarm activation and deactivation. Set to Acknowledged Summary Traps to send summary traps to PowerManagerII. These traps are repeated until Pow…
|
TrapReceiverModer/w Textual Convention: TrapReceiverMode EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.60.50.1.70 |
||||||||||
|
acknowledgeAlarmSummaryTrap
This command will acknowledge reception of the alarm summary trap.
|
NoDatar/w Textual Convention: NoData OctetStringType Constraints: range: 0 |
.1.3.6.1.4.1.1918.2.14.10.30.60.50.1.80 |
emailReceiverTable
table.1.3.6.1.4.1.1918.2.14.10.30.65.60
·
1 row entry
·
6 columns
Table for emailReceiver
Entry for emailReceiver
Indexes
emailReceiverIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
emailReceiverIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.30.65.60.1.1 |
||||||||||
|
emailReceiverAddress
The receiver's email address.
|
OctetStringr/w Constraints: range: 0-100 |
.1.3.6.1.4.1.1918.2.14.10.30.65.60.1.10 |
||||||||||
|
emailReceiverLevel
Sets the severity of alarms to be reported to this email receiver.
|
SeverityLevelr/w Textual Convention: SeverityLevel EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.65.60.1.20 |
||||||||||
|
emailReceiverDelay
The email will be sent after the delay period, even if the original trigger alarm has become de-activated.
|
sTimeIntervalInSecondsr/w Textual Convention: TimeIntervalInSeconds Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.1918.2.14.10.30.65.60.1.30 |
||||||||||
|
sendTestEmail
This will send an email notification to the receiver.
|
NoDatar/w Textual Convention: NoData OctetStringType Constraints: range: 0 |
.1.3.6.1.4.1.1918.2.14.10.30.65.60.1.40 |
||||||||||
|
smtpResult
Result of the last SMTP operation affecting this receiver. The first digit is the state reached (1 GREET, 2 EHLO, 3 MAIL, 4 RCPT, 5 DATA, 6 BODY). The next 3 digits come from the SMTP service. 2xx = Ok, 4xx = Temporary …
|
Unsigned16 Textual Convention: Unsigned16 Integer32Type Constraints: range: 0..65535 |
.1.3.6.1.4.1.1918.2.14.10.30.65.60.1.50 |
webUserTable
table.1.3.6.1.4.1.1918.2.14.10.30.80
·
1 row entry
·
12 columns
Table for webUser
Entry for webUser
Indexes
webUserIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
webUserIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.30.80.1.1 |
||||||
|
userName
The full name of the user. This is for reference only and is not used in the login process.
|
OctetStringr/w Constraints: range: 0-40 |
.1.3.6.1.4.1.1918.2.14.10.30.80.1.10 |
||||||
|
userLogonId
The logon name of a user.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.1918.2.14.10.30.80.1.21 |
||||||
|
userLogonPassword
The password for this user.
|
OctetStringr/w Constraints: range: 0-64 |
.1.3.6.1.4.1.1918.2.14.10.30.80.1.31 |
||||||
|
userActive
Indicates whether this user is enabled or disabled.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.80.1.40 |
||||||
|
userWrite
If checked the user is allowed to modify configurable values.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.80.1.60 |
||||||
|
userRestore
If checked the user is allowed to upload configurations or snapshots.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.80.1.70 |
||||||
|
userBackup
If checked the user is allowed to download configurations or snapshots.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.80.1.80 |
||||||
|
userExecute
If checked the user is allowed to execute commands.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.80.1.90 |
||||||
|
userUpgradeFirmware
If checked the user is allowed to upgrade firmware (including de-installing optional modules).
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.80.1.100 |
||||||
|
userAdministrator
If checked the user is administrator and change security settings.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.80.1.110 |
||||||
|
userSnmp
This user is allowed to modify or only read values. The Password is also used for SNMP authentication.
|
UserSnmpr/w Textual Convention: UserSnmp EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.30.80.1.120 |
rxpTable
table.1.3.6.1.4.1.1918.2.14.10.55.10
·
1 row entry
·
9 columns
Table for rxp
Entry for rxp
Indexes
rxpIndex
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
rxpIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.55.10.1.1 |
||||||||||||||
|
rxpSlaveRegistrationState
Registration state of this device.
|
RcpSlaveState Textual Convention: RcpSlaveState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.55.10.1.10 |
||||||||||||||
|
rxpSlaveName
Name of the RXP device.
|
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.1918.2.14.10.55.10.1.20 |
||||||||||||||
|
rxpSlaveSerialNumber
The serial number of this device.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.55.10.1.30 |
||||||||||||||
|
rxpSlaveType
What type of component (IOB, rectifier etc) this device is.
|
RxpSlaveType Textual Convention: RxpSlaveType EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.55.10.1.40 |
||||||||||||||
|
rxpSlaveCommandSet
The id of the command set the controller is using to communicate with this device.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.55.10.1.50 |
||||||||||||||
|
rxpBomRevision
Hardware Version of the RXP device.
|
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.1918.2.14.10.55.10.1.60 |
||||||||||||||
|
rxpSoftwareVersion
Software Version of the RXP device.
|
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.1918.2.14.10.55.10.1.70 |
||||||||||||||
|
identifyRxpSlave
If supported by the RXP device, this causes it to identify itself by flashing some of its LEDs or similar.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.55.10.1.80 |
iobTable
table.1.3.6.1.4.1.1918.2.14.10.55.20
·
1 row entry
·
10 columns
Table for iob
Entry for iob
Indexes
iobIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
iobIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.55.20.1.1 |
||||||||||||
|
iobRegistrationState
Registration state of this IOB.
|
RcpSlaveState Textual Convention: RcpSlaveState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.55.20.1.10 |
||||||||||||
|
iobSerialNumber
Serial number.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.55.20.1.20 |
||||||||||||
|
iobMapping
Index used in analogue and digitals tables
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.55.20.1.30 |
||||||||||||
|
iobNumberOfVoltages
Number of voltage inputs on this IOB. The controller numbers the analog inputs on an IOB in the order: voltages, currents, temperatures.
|
Unsigned8 Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.55.20.1.40 |
||||||||||||
|
iobNumberOfCurrents
Number of current inputs on this IOB. The controller numbers the analog inputs on an IOB in the order: voltages, currents, temperatures.
|
Unsigned8 Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.55.20.1.50 |
||||||||||||
|
iobNumberOfTemperatures
Number of temperature inputs on this IOB. The controller numbers the analog inputs on an IOB in the order: voltages, currents, temperatures.
|
Unsigned8 Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.55.20.1.60 |
||||||||||||
|
iobNumberOfDigitalInputs
Number of digital inputs on this IOB.
|
Unsigned8 Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.55.20.1.70 |
||||||||||||
|
iobNumberOfRelays
Number of digital outputs on this IOB.
|
Unsigned8 Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.55.20.1.80 |
||||||||||||
|
iobNumberOfLvds
Number of LVD connectors on this IOB.
|
Unsigned8 Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.55.20.1.90 |
rectifierValuesTable
table.1.3.6.1.4.1.1918.2.14.10.60.30
·
1 row entry
·
26 columns
Table for rectifierValues
Entry for rectifierValues
Indexes
rectifierValuesIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
rectifierValuesIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.1 |
||||||||||||
|
rectifierSerialNumber
Rectifier serial number.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.30 |
||||||||||||
|
rectifierType
Rectifier Type.
|
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.40 |
||||||||||||
|
rectifierInputType
Rectifier Input Type, regular rectifier is AC, Solar Charger is MPPT.
|
InputType Textual Convention: InputType EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.60.30.1.50 |
||||||||||||
|
rectifierStatus
The status reported by this rectifier. This value cannot be interpreted without knowing the meaning of the various status bits. This is documented in the RXP command set for rectifiers.
|
Unsigned8 Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.60 |
||||||||||||
|
rectifierMaximumCurrentLimit
The current limit value of the rectifier. Adjust Rectifier Current Limit to set a lower operating current limit.
|
AUnsigned8 Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.70 |
||||||||||||
|
rectifierMaximumPowerLimit
The maximum output power limit value of the rectifier. Adjust Rectifier Current Limit to set a lower operating power limit.
|
WDcPower Textual Convention: DcPower EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.60.30.1.80 |
||||||||||||
|
rectifierMinimumOvsdSetPoint
The minimum OVSD set point that the rectifier accepts.
|
0.01 VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.83 |
||||||||||||
|
rectifierMaximumOvsdSetPoint
The maximum OVSD set point that the rectifier accepts.
|
0.01 VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.86 |
||||||||||||
|
rectifierInputVoltage
The input voltage measured by the rectifier (AC) or Solar (DC).
|
VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.90 |
||||||||||||
|
rectifierReportedVoltage
The output voltage measured by this rectifier. This is measured by the rectifier and reported via the RXP bus.
|
0.01 VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.95 |
||||||||||||
|
rectifierReportedCurrent
The current produced by this rectifier. This is measured by the rectifier and reported via the rectifier comms bus.
|
AFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.100 |
||||||||||||
|
rectifierOutputPowerw
The current rectifier output power as Watts.
|
WDcPower Textual Convention: DcPower EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.60.30.1.103 |
||||||||||||
|
rectifierOutputPower
The current rectifier output power as a percentage of the power limit under the current operating conditions.
|
0.1 %Float Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.105 |
||||||||||||
|
rectifierHeatsinkTemperature
The measured rectifier heatsink temperature.
|
°CFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.110 |
||||||||||||
|
rectifierRegistrationState
Registration state of this rectifier.
|
RcpSlaveState Textual Convention: RcpSlaveState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.60.30.1.120 |
||||||||||||
|
rectifierFailedState
A rectifier's failed state.
|
RectFailState Textual Convention: RectFailState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.60.30.1.130 |
||||||||||||
|
loadBasedRunTime
The time the rectifier has been operating since it was registered.
|
sTimeIntervalInSeconds Textual Convention: TimeIntervalInSeconds Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.140 |
||||||||||||
|
shutdownRectifier
Shuts down the rectifier or restarts it. Use Rectifier Has Been Shutdown to see whether the command has been sent to the rectifier since it can take some seconds.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.60.30.1.150 |
||||||||||||
|
rectifierHasBeenShutdown
Indicates if the rectifier shutdown command has been sent. Once a Shutdown Rectifier command has been issued some time may elapse before the command is sent to the rectifier. Rectifiers that shut themselves down due to …
|
Boolean Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.60.30.1.160 |
||||||||||||
|
rectifierPhase1
Rectifier's AC voltage measured at the input connection for phase 1.
|
VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.170 |
||||||||||||
|
rectifierPhase2
Rectifier's AC voltage measured at the input connection for phase 2.
|
VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.180 |
||||||||||||
|
rectifierPhase3
Rectifier's AC voltage measured at the input connection for phase 3.
|
VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.190 |
||||||||||||
|
rectifierNotes
This text will not be valid if the rectifier is unplugged and is not permanently stored by the controller.
|
OctetStringr/w Constraints: range: 0-60 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.200 |
||||||||||||
|
rectifierInputCurrent
The input current measured by the rectifier (AC) or Solar (DC).
|
AFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.60.30.1.210 |
||||||||||||
|
rectifierPhase
This rectifiers AC phase. The controller is unable to determine which supply is used on a dual feed supply
|
AcPhase Textual Convention: AcPhase EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.60.30.1.220 |
lvdTable
table.1.3.6.1.4.1.1918.2.14.10.70.75.50
·
1 row entry
·
14 columns
Table for lvd
Entry for lvd
Indexes
lvdIndex
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
lvdIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.1 |
||||||||||||||
|
lvdName
The name of this LVD.
|
OctetStringr/w Constraints: range: 0-20 |
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.5 |
||||||||||||||
|
lvdState
The state of this LVD control process.
|
LvdState Textual Convention: LvdState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.10 |
||||||||||||||
|
lvdInhibited
Indicates whether this LVD currently cannot change state due to the inhibit time.
|
Boolean Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.15 |
||||||||||||||
|
enableLvdVoltageDisconnect
If Enabled, the LVD will disconnect when the bus voltage falls below the Disconnect Voltage and will not reconnect until it is above the Reconnect Voltage.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.20 |
||||||||||||||
|
lvdDisconnectVoltage
If voltage based disconnect is enabled, the LVD will disconnect if the bus voltage has been below this voltage for the recognition time.
|
0.01 VFloatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.30 |
||||||||||||||
|
lvdReconnectVoltage
If voltage based disconnect is enabled, the LVD will reconnect only if the bus voltage has been above this voltage for the recognition time.
|
0.01 VFloatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.40 |
||||||||||||||
|
lvdRecognitionPeriod
The time the bus voltage must be below or above the thresholds before the LVD disconnects or connects.
|
sTimeIntervalInSecondsr/w Textual Convention: TimeIntervalInSeconds Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.50 |
||||||||||||||
|
enableLvdAcTimer
If Enabled, during an AC failure the LVD will disconnect after the AC Timer Delay, even if the Disconnect Voltage has not been reached.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.60 |
||||||||||||||
|
lvdAcTimerDisconnectDelay
If Enabled, the LVD will disconnect after this delay following an AC failure, unless the Disconnect Voltage is reached or AC is restored first.
|
minTimeIntervalInMinutesr/w Textual Convention: TimeIntervalInMinutes Integer32Type Constraints: range: 0..2147483646 |
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.70 |
||||||||||||||
|
enableLvdSaDisconnect
If Enabled, the LVD will disconnect immediately when the specified smart alarm becomes active.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.80 |
||||||||||||||
|
lvdSaDisconnectIndex
If Enabled, the LVD will disconnect immediately when this smart alarm becomes active.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.90 |
||||||||||||||
|
enableLvdChainedToPrevious
If Enabled, the LVD will not disconnect until the previous LVD (the LVD numbered one less) has been disconnected for the configured recognition time. This item is ignored by the first LVD and when the previous LVD has n…
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.100 |
||||||||||||||
|
lvdRemoteManualControl
Allows remote manual control of the LVD. Reconnects on remote manual control, remote manual timeout, UI or Smart Alarm manual control or AC-State becomes ok.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.120 |
lvdcTable
table.1.3.6.1.4.1.1918.2.14.10.70.75.60
·
1 row entry
·
7 columns
Table for lvdc
Entry for lvdc
Indexes
lvdcIndex
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
lvdcIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.70.75.60.1.1 |
||||||||||||||
|
lvdcLvdMapping
The LVD that drives this contactor.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.75.60.1.10 |
||||||||||||||
|
lvdcState
The state of this contactor.
|
LvdcState Textual Convention: LvdcState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.75.60.1.20 |
||||||||||||||
|
enableLvdc
If Enabled, the specified physical contactor is driven by the specified LVD.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.75.60.1.30 |
||||||||||||||
|
lvdcIobNumber
The I/O board number to which this LVD contactor is connected.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.75.60.1.40 |
||||||||||||||
|
lvdcIobLvdNumber
The LVD connector on the I/O board that this contactor is connected to.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.75.60.1.50 |
||||||||||||||
|
lvdcType
The type of contactor connected to the I/O board.
|
LvdcTyper/w Textual Convention: LvdcType EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.75.60.1.60 |
energyMeterTable
table.1.3.6.1.4.1.1918.2.14.10.70.87.10
·
1 row entry
·
14 columns
Table for energyMeter
Entry for energyMeter
Indexes
energyMeterIndex
| Column | Syntax | OID |
|---|---|---|
|
energyMeterIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.1 |
|
energyMeterName
The name for this energy meter.
|
OctetStringr/w Constraints: range: 0-20 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.10 |
|
energyMeterGroup
The group tag used by software to group related inputs and outputs for display purposes.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.12 |
|
energyMeter
The energy meter reading for this meter.
|
0.001 kWhFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.15 |
|
resetEnergyMeter
Reset this energy meter to zero.
|
NoDatar/w Textual Convention: NoData OctetStringType Constraints: range: 0 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.20 |
|
energyResetDate
The date when this energy meter was reset.
|
JulianDateUtc25r/w Textual Convention: JulianDateUtc25 OctetStringType Constraints: range: 25 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.25 |
|
currentMeter
The current reading for this meter.
|
0.1 AFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.30 |
|
voltageMeter
The voltage reading for this meter.
|
0.01 VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.35 |
|
powerMeter
The power reading for this meter.
|
0.01 kWFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.40 |
|
powerMeterMin
The min. power reading for this meter.
|
0.01 kWFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.45 |
|
powerMeterMax
The max. power reading for this meter.
|
0.01 kWFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.50 |
|
resetPowerMeterRange
Reset this power meter's min. and max.
|
NoDatar/w Textual Convention: NoData OctetStringType Constraints: range: 0 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.55 |
|
powerMeterGain
The scaling factor applied to the raw power value applied to the energy meter.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.60 |
|
powerMeterOffset
The offset applied to the raw energy value applied to the energy meter.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.87.10.1.65 |
.1.3.6.1.4.1.1918.2.14.10.70.87.20
·
1 row entry
·
4 columns
Table for energyMeterAiMapping
Entry for energyMeterAiMapping
Indexes
energyMeterAiMappingIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
energyMeterAiMappingIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.70.87.20.1.1 |
||||||||
|
energyMeterMeter
This is the mapping into the Energy-Meter-Name. Zero means it is not mapped.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.87.20.1.10 |
||||||||
|
energyMeterAi
This is the mapping into the Analog-Input-Table. Zero means it is not mapped.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.87.20.1.15 |
||||||||
|
energyMeterAiFunction
This analog input is either Current or Voltage.
|
EnergyMeterAiFunctionr/w Textual Convention: EnergyMeterAiFunction EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.87.20.1.20 |
.1.3.6.1.4.1.1918.2.14.10.70.87.30
·
1 row entry
·
4 columns
Table for energyMeterValueMapping
Entry for energyMeterValueMapping
Indexes
energyMeterValueMappingIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
energyMeterValueMappingIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.70.87.30.1.1 |
||||||||||||||||||||||||||||||||||||||||||||
|
energyMeterMeterNumber
This is the mapping into the Energy-Meter-Name. Zero means it is not mapped.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.87.30.1.10 |
||||||||||||||||||||||||||||||||||||||||||||
|
energyMeterSystemValue
This is the mapping to a system calculated value. Zero means it is not mapped.
|
EnergyMeterSystemValuer/w Textual Convention: EnergyMeterSystemValue EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.87.30.1.15 |
||||||||||||||||||||||||||||||||||||||||||||
|
energyMeterSystemValueIndex
The index of the Energy-Meter-System-Value.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.87.30.1.20 |
fanControllerStateTable
table.1.3.6.1.4.1.1918.2.14.10.70.88.30
·
1 row entry
·
7 columns
Table for fanControllerState
Entry for fanControllerState
Indexes
fanControllerStateIndex
| Column | Syntax | OID | ||
|---|---|---|---|---|
|
fanControllerStateIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.30.1.1 |
||
|
fanTemperature
Temperature sensor reading. If AI function mapped its value overrides temperature obtained from Fan Controller.
|
0.1 °CFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.88.30.1.10 |
||
|
fanPower
Power applied to fan output.
|
%Percentile8Nan Textual Convention: Percentile8Nan EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.70.88.30.1.20 |
||
|
setFanPower
Manual set the fan power for the Set-Fan-Power-Period.
|
%Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.30.1.30 |
||
|
fanPoles
The number of poles of each fan group is used to calculate fan speed(rpm).
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.30.1.40 |
||
|
fanSpeedA
Fan Speed. Only fans with pulse outputs can have a measured speed.
|
Unsigned16 Textual Convention: Unsigned16 Integer32Type Constraints: range: 0..65535 |
.1.3.6.1.4.1.1918.2.14.10.70.88.30.1.50 |
||
|
fanSpeedB
Fan Speed. Only fans with pulse outputs can have a measured speed.
|
Unsigned16 Textual Convention: Unsigned16 Integer32Type Constraints: range: 0..65535 |
.1.3.6.1.4.1.1918.2.14.10.70.88.30.1.60 |
.1.3.6.1.4.1.1918.2.14.10.70.88.70
·
1 row entry
·
3 columns
Table for fanController1Primary
Entry for fanController1Primary
Indexes
fanController1PrimaryIndex
| Column | Syntax | OID |
|---|---|---|
|
fanController1PrimaryIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.70.1.1 |
|
fc1pTemperature
A temperature/power point for this controller.
|
0.1 °CFloatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.88.70.1.10 |
|
fc1pPower
A temperature/power point for this controller.
|
%Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.70.1.20 |
.1.3.6.1.4.1.1918.2.14.10.70.88.90
·
1 row entry
·
3 columns
Table for fanController1Secondary
Entry for fanController1Secondary
Indexes
fanController1SecondaryIndex
| Column | Syntax | OID |
|---|---|---|
|
fanController1SecondaryIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.90.1.1 |
|
fc1sTemperature
A temperature/power point for this controller.
|
0.1 °CFloatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.88.90.1.10 |
|
fc1sPower
A temperature/power point for this controller.
|
%Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.90.1.20 |
.1.3.6.1.4.1.1918.2.14.10.70.88.110
·
1 row entry
·
3 columns
Table for fanController2Primary
Entry for fanController2Primary
Indexes
fanController2PrimaryIndex
| Column | Syntax | OID |
|---|---|---|
|
fanController2PrimaryIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.110.1.1 |
|
fc2pTemperature
A temperature/power point for this controller.
|
0.1 °CFloatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.88.110.1.10 |
|
fc2pPower
A temperature/power point for this controller.
|
%Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.110.1.20 |
.1.3.6.1.4.1.1918.2.14.10.70.88.130
·
1 row entry
·
3 columns
Table for fanController2Secondary
Entry for fanController2Secondary
Indexes
fanController2SecondaryIndex
| Column | Syntax | OID |
|---|---|---|
|
fanController2SecondaryIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.130.1.1 |
|
fc2sTemperature
A temperature/power point for this controller.
|
0.1 °CFloatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.70.88.130.1.10 |
|
fc2sPower
A temperature/power point for this controller.
|
%Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.70.88.130.1.20 |
analogInputTable
table.1.3.6.1.4.1.1918.2.14.10.90.10.30
·
1 row entry
·
27 columns
Table for analogInput
Entry for analogInput
Indexes
analogInputIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
analogInputIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiHighState
The state of the selected analog input high alarm.
|
AlarmActiveState Textual Convention: AlarmActiveState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.20 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiLowState
The state of the selected analog input low alarm.
|
AlarmActiveState Textual Convention: AlarmActiveState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiValue
Analog input value.
|
0.01Float Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.40 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiStatus
Enable/disable this analog input channel.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.50 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiName
The name of this analog input channel as it will appear on management software such as DCTools or PowerManagerII. This name is not displayed on the controller.
|
OctetStringr/w Constraints: range: 0-20 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.60 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiFunction
Selects how the value of this analog input is to be used by any control functions, if at all.
|
AiFunctionr/w Textual Convention: AiFunction EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.64 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiFunctionIndex
Select an index for the selected function. Only valid where function is Smart-Analog, Battery-Symmetry-Monitoring and Fan-Temperature.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.66 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiUnits
Units of this analog input (after scaling).
|
MeasurementUnitsr/w Textual Convention: MeasurementUnits EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.70 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiIobNumber
The I/O board number on which this analog input is located.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.80 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inputNumber
The input channel on the I/O board of this analog input.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.90 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
gain
The scaling factor applied to the raw value read from the I/O board.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.100 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
offset
The offset applied to the raw value read from the I/O board.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.110 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hysteresis
The amount of hysteresis applied to the input before an active alarm is deactivated.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.130 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
highSeverity
The severity level associated with the alarm. Control alarms are not displayed, although any configured digital outputs are still activated.
|
AlarmSeverityr/w Textual Convention: AlarmSeverity EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.141 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
highThreshold
An analog input high alarm is activated if the scaled input is greater than or equal to this value.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.150 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
highDoMappingA
Optional digital output activated while this alarm is active.
|
RelayMappingr/w Textual Convention: RelayMapping EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.160 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
highDoMappingB
Optional digital output activated while this alarm is active.
|
RelayMappingr/w Textual Convention: RelayMapping EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.170 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
highTrapSend
If set to true an SNMP trap is sent to every trap receiver with an appropriate trap level whenever this alarm changes state.
|
SendTrapr/w Textual Convention: SendTrap EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.175 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
lowSeverity
The severity level associated with the alarm. Control alarms are not displayed, although any configured digital outputs are still activated.
|
AlarmSeverityr/w Textual Convention: AlarmSeverity EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.181 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
lowThreshold
An analog input low alarm is activated if the scaled input is lower than or equal to this value.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.190 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
lowDoMappingA
Optional digital output activated while this alarm is active.
|
RelayMappingr/w Textual Convention: RelayMapping EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.200 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
lowDoMappingB
Optional digital output activated while this alarm is active.
|
RelayMappingr/w Textual Convention: RelayMapping EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.210 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
lowTrapSend
If set to true an SNMP trap is sent to every trap receiver with an appropriate trap level whenever this alarm changes state.
|
SendTrapr/w Textual Convention: SendTrap EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.215 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiGroup
The group tag used by software to group related inputs and outputs for display purposes.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.220 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiHighNotes
User notes about this alarm. These notes appear in SNMP traps and can be viewed using DCTools or PowerManagerII.
|
OctetStringr/w Constraints: range: 0-60 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.230 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
aiLowNotes
User notes about this alarm. These notes appear in SNMP traps and can be viewed using DCTools or PowerManagerII.
|
OctetStringr/w Constraints: range: 0-60 |
.1.3.6.1.4.1.1918.2.14.10.90.10.30.1.240 |
smartAnalogTable
table.1.3.6.1.4.1.1918.2.14.10.90.10.40
·
1 row entry
·
9 columns
Table for smartAnalog
Entry for smartAnalog
Indexes
smartAnalogIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
smartAnalogIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.40.1.1 |
||||||||||||||||||||||||||||||||
|
name
The name of these smart inputs.
|
OctetStringr/w Constraints: range: 0-20 |
.1.3.6.1.4.1.1918.2.14.10.90.10.40.1.10 |
||||||||||||||||||||||||||||||||
|
group
The group tag used by software to group related inputs and outputs for display purposes.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.40.1.20 |
||||||||||||||||||||||||||||||||
|
value
Value derived from the analog inputs configured as smart analogs.
|
0.01Float Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.90.10.40.1.30 |
||||||||||||||||||||||||||||||||
|
type
How values are derived from the analog inputs.
|
SmartAnalogTyper/w Textual Convention: SmartAnalogType EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.40.1.40 |
||||||||||||||||||||||||||||||||
|
units
The units of the analog inputs. Units for a Smart Analog will be taken from the first configured analog input mapped to it.
|
OctetString Constraints: range: 0-7 |
.1.3.6.1.4.1.1918.2.14.10.90.10.40.1.50 |
||||||||||||||||||||||||||||||||
|
smartAnalogGate
The value can be clipped.
|
SmartAnalogGater/w Textual Convention: SmartAnalogGate EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.40.1.60 |
||||||||||||||||||||||||||||||||
|
saiFunction
Selects how the value of this analog input is to be used by any control functions, if at all.
|
AiFunctionr/w Textual Convention: AiFunction EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.40.1.70 |
||||||||||||||||||||||||||||||||
|
saiFunctionIndex
Select an index for the selected function if required.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.40.1.80 |
smartAnalogMappingTable
table.1.3.6.1.4.1.1918.2.14.10.90.10.45
·
1 row entry
·
6 columns
Table for smartAnalogMapping
Entry for smartAnalogMapping
Indexes
smartAnalogMappingIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
smartAnalogMappingIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.45.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAnalogSystemInputMapping
Index of smart analogue that this system value is mapped to.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.45.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAnalogSystemInputValue
Value derived from the system input configured as smart analogs.
|
0.01Float Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.90.10.45.1.20 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAnalogSystemInput
How values are derived from the analog inputs.
|
SystemInputTyper/w Textual Convention: SystemInputType EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.45.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAnalogSystemInputIndex
If required this, is the system input index.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.10.45.1.40 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAnalogSystemInputInvert
The system input value multiplied by -1 if true.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.10.45.1.50 |
digitalInputTable
table.1.3.6.1.4.1.1918.2.14.10.90.40
·
1 row entry
·
16 columns
Table for digitalInput
Entry for digitalInput
Indexes
digitalInputIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
digitalInputIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.90.40.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diState
The state of this digital input alarm.
|
AlarmActiveState Textual Convention: AlarmActiveState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.40.1.20 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diValue
The state of this digital input.
|
DigitalInputState Textual Convention: DigitalInputState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.40.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diStatus
Enable/disable this digital input channel.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.40.1.40 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diName
The name of the digital input.
|
OctetStringr/w Constraints: range: 0-20 |
.1.3.6.1.4.1.1918.2.14.10.90.40.1.50 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diIobNumber
The I/O board number on which this digital input is located.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.40.1.60 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
digitalInputNumber
The input channel on the I/O board of this digital input.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.40.1.70 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diSeverity
The severity level associated with the alarm. Control alarms are not displayed, although any configured digital outputs are still activated.
|
AlarmSeverityr/w Textual Convention: AlarmSeverity EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.40.1.81 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diRecognitionPeriod
A digital input alarm will become active if the input is in the active state for the recognition time.
|
sTimeIntervalInSecondsr/w Textual Convention: TimeIntervalInSeconds Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.1918.2.14.10.90.40.1.85 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diDeactivationRecognitionPeriod
A digital input alarm will deactivate if the input is in the inactive state for the deactivation recognition time.
|
sTimeIntervalInSecondsr/w Textual Convention: TimeIntervalInSeconds Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.1918.2.14.10.90.40.1.86 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diDoMappingA
Optional digital output activated while this digital input alarm is active.
|
RelayMappingr/w Textual Convention: RelayMapping EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.40.1.90 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diDoMappingB
Optional digital output activated while this digital input alarm is active.
|
RelayMappingr/w Textual Convention: RelayMapping EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.40.1.100 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diTrapSend
If set to true an SNMP trap is sent to every trap receiver with an appropriate trap level whenever this alarm changes state.
|
SendTrapr/w Textual Convention: SendTrap EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.40.1.105 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diActiveState
Selects whether the input should be considered active when closed or open.
|
ActiveStater/w Textual Convention: ActiveState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.40.1.110 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diGroup
The group tag used by software to group related inputs and outputs for display purposes.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.40.1.120 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
diNotes
User notes about this alarm. These notes appear in SNMP traps and can be viewed using DCTools or PowerManagerII.
|
OctetStringr/w Constraints: range: 0-60 |
.1.3.6.1.4.1.1918.2.14.10.90.40.1.130 |
digitalOutputTable
table.1.3.6.1.4.1.1918.2.14.10.90.50
·
1 row entry
·
9 columns
Table for digitalOutput
Entry for digitalOutput
Indexes
digitalOutputIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
digitalOutputIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.90.50.1.1 |
||||||||||
|
doState
The state of this digital output. Active digital outputs may be energized or de-energized depending on their configuration.
|
ExternalRelayState Textual Convention: ExternalRelayState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.50.1.20 |
||||||||||
|
remoteControlState
Allows manual control of the digital output.
|
RelayControlStater/w Textual Convention: RelayControlState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.50.1.40 |
||||||||||
|
doStatus
Enable or disable this digital output. If disabled, the digital output is not driven.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.50.1.50 |
||||||||||
|
doName
The name of the digital output.
|
OctetStringr/w Constraints: range: 0-20 |
.1.3.6.1.4.1.1918.2.14.10.90.50.1.60 |
||||||||||
|
doIobNumber
The I/O board number on which this digital output is located.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.50.1.70 |
||||||||||
|
doIobDoNumber
The number of the digital output channel on the I/O board.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.50.1.80 |
||||||||||
|
doActiveState
Active state of the digital output.
|
EnergizeStater/w Textual Convention: EnergizeState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.90.50.1.90 |
||||||||||
|
doGroup
The group tag used by software to group related inputs and outputs for display purposes.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.90.50.1.100 |
.1.3.6.1.4.1.1918.2.14.10.100.50.70
·
1 row entry
·
7 columns
Table for midpointMonitoringString
Entry for midpointMonitoringString
Indexes
midpointMonitoringStringIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
midpointMonitoringStringIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.100.50.70.1.1 |
||||||||||
|
stringName
Name of the battery string.
|
OctetString Constraints: range: 0-20 |
.1.3.6.1.4.1.1918.2.14.10.100.50.70.1.10 |
||||||||||
|
stringState
Indicates the current state of a battery string.
|
BsmBatteryState Textual Convention: BsmBatteryState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.100.50.70.1.20 |
||||||||||
|
firstQuarterPointVoltage
1/4 point voltage reading for the battery string.
|
0.01 VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.100.50.70.1.25 |
||||||||||
|
midPointVoltage
Midpoint voltage reading for the battery string.
|
0.01 VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.100.50.70.1.30 |
||||||||||
|
thirdQuarterPointVoltage
3/4 point voltage reading for the battery string.
|
0.01 VFloat Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.100.50.70.1.35 |
||||||||||
|
imbalancePercent
The voltage difference between the first half of the string and the second half of the string expressed in percent of the Bus Voltage.
|
0.1 %Float Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.100.50.70.1.40 |
.1.3.6.1.4.1.1918.2.14.10.100.62
·
1 row entry
·
3 columns
Table for batteryCharacterizationData
Entry for batteryCharacterizationData
Indexes
batteryCharacterizationDataIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryCharacterizationDataIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.100.62.1.1 |
|
batteryCharacterizationSample
Stores battery specific data necessary to predict the time remaining during a discharge. It is possible to transfer this data to a different system with the same type of battery, but it may not be as accurate as charact…
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.100.62.1.10 |
|
batteryCharacterizationTime
Stores battery specific data necessary to predict the time remaining during a discharge. It is possible to transfer this data to a different system with the same type of battery, but it may not be as accurate as charact…
|
minTimeIntervalInMinutesr/w Textual Convention: TimeIntervalInMinutes Integer32Type Constraints: range: 0..2147483646 |
.1.3.6.1.4.1.1918.2.14.10.100.62.1.20 |
logItemsTable
table.1.3.6.1.4.1.1918.2.14.10.107.40
·
1 row entry
·
4 columns
Table for logItems
Entry for logItems
Indexes
logItemsIndex
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
logItemsIndex
Automatically generated index object.
|
LogItems Textual Convention: LogItems EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.107.40.1.1 |
||||||||||||||||
|
logInterval
The time between each log record.
|
sTimeIntervalInSecondsr/w Textual Convention: TimeIntervalInSeconds Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.1918.2.14.10.107.40.1.10 |
||||||||||||||||
|
useOffNormal
While off normal use the When-Off-Normal interval.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.107.40.1.20 |
||||||||||||||||
|
logNumberOfEntries
The number of log entries of this type since power was applied.
|
Unsigned16 Textual Convention: Unsigned16 Integer32Type Constraints: range: 0..65535 |
.1.3.6.1.4.1.1918.2.14.10.107.40.1.30 |
threadLoadingTable
table.1.3.6.1.4.1.1918.2.14.10.108.10
·
1 row entry
·
7 columns
Table for threadLoading
Entry for threadLoading
Indexes
threadLoadingIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
threadLoadingIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.108.10.1.1 |
||||||||
|
threadName
Name of this thread.
|
OctetString Constraints: range: 0-64 |
.1.3.6.1.4.1.1918.2.14.10.108.10.1.20 |
||||||||
|
threadLoading
The percentage of CPU loading caused by this thread.
|
0.1 %Float Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.108.10.1.30 |
||||||||
|
threadPriority
Thread priority. Expect to see high priority thread use least cpu time.
|
ThreadPriority Textual Convention: ThreadPriority EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.108.10.1.40 |
||||||||
|
threadStack
The amount of stack used by this thread.
|
BSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.108.10.1.50 |
||||||||
|
threadHeap
The amount of heap used by this thread.
|
BSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.108.10.1.60 |
||||||||
|
threadHighWaterMark
The maximum heap used by this thread.
|
BSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.108.10.1.70 |
alarmTable
table.1.3.6.1.4.1.1918.2.14.10.110.10
·
1 row entry
·
9 columns
Table for alarm
Entry for alarm
Indexes
alarmIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
alarmIndex
Automatically generated index object.
|
SystemAlarm Textual Convention: SystemAlarm EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.10.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
alarmName
The name of the Alarm.
|
OctetString Constraints: range: 0-40 |
.1.3.6.1.4.1.1918.2.14.10.110.10.1.20 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
alarmSeverity
The severity level associated with the alarm. Control alarms are not displayed, although any configured digital outputs are still activated.
|
AlarmSeverityr/w Textual Convention: AlarmSeverity EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.10.1.31 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
alarmState
The state of this alarm.
|
AlarmActiveState Textual Convention: AlarmActiveState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.10.1.40 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
alarmNotes
User notes about this alarm. These notes appear in SNMP traps and can be viewed using DCTools or PowerManagerII.
|
OctetStringr/w Constraints: range: 0-60 |
.1.3.6.1.4.1.1918.2.14.10.110.10.1.50 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
alarmDoMappingA
Optional digital output activated while this alarm is active.
|
RelayMappingr/w Textual Convention: RelayMapping EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.10.1.60 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
alarmDoMappingB
Optional second digital output activated while this alarm is active.
|
RelayMappingr/w Textual Convention: RelayMapping EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.10.1.70 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
alarmTrapSend
If set to true an SNMP trap is sent to every trap receiver with an appropriate trap level whenever this alarm changes state.
|
SendTrapr/w Textual Convention: SendTrap EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.10.1.80 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
alarmStateChangeTime
The time when this alarm last changed state.
|
JulianDateUtc25 Textual Convention: JulianDateUtc25 OctetStringType Constraints: range: 25 |
.1.3.6.1.4.1.1918.2.14.10.110.10.1.90 |
smartAlarmTable
table.1.3.6.1.4.1.1918.2.14.10.110.20
·
1 row entry
·
14 columns
Table for smartAlarm
Entry for smartAlarm
Indexes
smartAlarmIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
smartAlarmIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.110.20.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmTrapSend
If set to true an SNMP trap is sent to every trap receiver with an appropriate trap level whenever this alarm changes state.
|
SendTrapr/w Textual Convention: SendTrap EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.20.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmName
Alarm name.
|
OctetStringr/w Constraints: range: 0-20 |
.1.3.6.1.4.1.1918.2.14.10.110.20.1.20 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSeverity
The severity level associated with the alarm. Control alarms are not displayed, although any configured digital outputs are still activated.
|
AlarmSeverityr/w Textual Convention: AlarmSeverity EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.20.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmGroup
The group number used by SiteManager. The group only affects the display of this item in SiteManager. It does not affect controller operation.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.110.20.1.35 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmNotes
User notes about this alarm.
|
OctetStringr/w Constraints: range: 0-60 |
.1.3.6.1.4.1.1918.2.14.10.110.20.1.40 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmOperator
The logic operator used to combine the states of all sources mapped to this smart alarm.
|
AlarmOperatorr/w Textual Convention: AlarmOperator EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.20.1.50 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmRecognitionPeriod
A smart alarm will become active if the logic for this alarm is continuously true for the recognition time.
|
sTimeIntervalInSecondsr/w Textual Convention: TimeIntervalInSeconds Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.1918.2.14.10.110.20.1.60 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmDeactivationRecognitionPeriod
A smart alarm will deactivate if the logic for this alarm is continuously false for the deactivation recognition time.
|
sTimeIntervalInSecondsr/w Textual Convention: TimeIntervalInSeconds Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.1918.2.14.10.110.20.1.61 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmDoMappingA
Optional digital output activated while this alarm is active.
|
RelayMappingr/w Textual Convention: RelayMapping EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.20.1.70 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmDoMappingB
Optional digital output activated while this alarm is active.
|
RelayMappingr/w Textual Convention: RelayMapping EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.20.1.80 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmState
The state of this alarm.
|
AlarmActiveState Textual Convention: AlarmActiveState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.20.1.100 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
clearSmartAlarm
This will temporarily override the alarm logic and force the alarm to deactivate. If this does not cause the trigger conditions for the alarm to change (for instance through a circular dependency), the alarm will reacti…
|
NoDatar/w Textual Convention: NoData OctetStringType Constraints: range: 0 |
.1.3.6.1.4.1.1918.2.14.10.110.20.1.110 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSendEmail
Send email on activation. It is treated as having Critical severity. This is not affected by the actual Smart alarm severity.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.20.1.120 |
sourceAlarmTable
table.1.3.6.1.4.1.1918.2.14.10.110.30
·
1 row entry
·
10 columns
Table for sourceAlarm
Entry for sourceAlarm
Indexes
sourceAlarmIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
sourceAlarmIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.110.30.1.1 |
||||||||||||
|
smartAlarmAlarmSourceTriggerState
Indicates the trigger state of this source alarm.
|
SourceState Textual Convention: SourceState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.30.1.10 |
||||||||||||
|
smartAlarmAlarmSourceStatus
Enable or disable this smart alarm source.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.30.1.20 |
||||||||||||
|
smartAlarmAlarmSourceMapping
Index of smart alarm that this source is mapped to.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.110.30.1.30 |
||||||||||||
|
smartAlarmAlarmSourceTrigger
Determines whether the source alarm's recognition time (if any) is taken into account. If the source alarm is itself a smart alarm and the sources of one or more smart alarms form a cyclic dependency, then at least one …
|
SourceTriggerr/w Textual Convention: SourceTrigger EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.30.1.41 |
||||||||||||
|
smartAlarmAlarmSourceType
The alarm table this source alarm is taken from.
|
AlarmTyper/w Textual Convention: AlarmType EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.30.1.50 |
||||||||||||
|
smartAlarmAlarmSourceIndex
The index of the source alarm.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.110.30.1.60 |
||||||||||||
|
smartAlarmAlarmSourceActiveCount
Count of edge transitions required to make this output become active. 1 = output follows input.
|
Unsigned16r/w Textual Convention: Unsigned16 Integer32Type Constraints: range: 0..65535 |
.1.3.6.1.4.1.1918.2.14.10.110.30.1.70 |
||||||||||||
|
smartAlarmAlarmSourceInactiveCount
Count of edge transitions required to make this output become inactive. 1 = output follows input.
|
Unsigned16r/w Textual Convention: Unsigned16 Integer32Type Constraints: range: 0..65535 |
.1.3.6.1.4.1.1918.2.14.10.110.30.1.80 |
||||||||||||
|
smartAlarmAlarmSourceCount
Transition count.
|
Signed16 Textual Convention: Signed16 Integer32Type Constraints: range: -32768..32767 |
.1.3.6.1.4.1.1918.2.14.10.110.30.1.90 |
sourceScheduleTable
table.1.3.6.1.4.1.1918.2.14.10.110.40
·
1 row entry
·
10 columns
Table for sourceSchedule
Entry for sourceSchedule
Indexes
sourceScheduleIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
sourceScheduleIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.110.40.1.1 |
||||||||||||
|
smartAlarmScheduleSourceIsTriggered
Indicates whether or not this schedule is currently considered true or false.
|
SourceState Textual Convention: SourceState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.40.1.10 |
||||||||||||
|
smartAlarmScheduleSourceStatus
Enable or disable this smart alarm schedule.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.40.1.20 |
||||||||||||
|
smartAlarmScheduleSourceMapping
Index of smart alarm that this schedule is mapped to.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.110.40.1.30 |
||||||||||||
|
smartAlarmScheduleSourceFirstActivation
The date and time at which this schedule will activate for the first time.
|
JulianDateUtc25r/w Textual Convention: JulianDateUtc25 OctetStringType Constraints: range: 25 |
.1.3.6.1.4.1.1918.2.14.10.110.40.1.50 |
||||||||||||
|
smartAlarmScheduleSourceDuration
This source will become active every Interval after the First Activation and remain active for Duration each time.
|
minTimeIntervalInMinutesr/w Textual Convention: TimeIntervalInMinutes Integer32Type Constraints: range: 0..2147483646 |
.1.3.6.1.4.1.1918.2.14.10.110.40.1.60 |
||||||||||||
|
smartAlarmScheduleSourceInterval
This source will become active every Interval after the First Activation and remain active for Duration each time.
|
minTimeIntervalInMinutesr/w Textual Convention: TimeIntervalInMinutes Integer32Type Constraints: range: 0..2147483646 |
.1.3.6.1.4.1.1918.2.14.10.110.40.1.70 |
||||||||||||
|
smartAlarmScheduleSourceRepetitions
The number of times this schedule should activate. After the last activation period, this schedule will remain inactive indefinitely. If set to zero, there is no limit on the number of activations.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.110.40.1.80 |
||||||||||||
|
smartAlarmScheduleSourceNext
The date and time at which this schedule will activate next.
|
JulianDateUtc25 Textual Convention: JulianDateUtc25 OctetStringType Constraints: range: 25 |
.1.3.6.1.4.1.1918.2.14.10.110.40.1.90 |
||||||||||||
|
smartAlarmScheduleSourceEnd
The date and time at which this schedule will deactivate for the last time.
|
JulianDateUtc25 Textual Convention: JulianDateUtc25 OctetStringType Constraints: range: 25 |
.1.3.6.1.4.1.1918.2.14.10.110.40.1.100 |
systemValueSourceTable
table.1.3.6.1.4.1.1918.2.14.10.110.50
·
1 row entry
·
13 columns
Table for systemValueSource
Entry for systemValueSource
Indexes
systemValueSourceIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
systemValueSourceIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.110.50.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceIsTriggered
Indicates whether or not this analog source is currently considered true or false.
|
SourceState Textual Convention: SourceState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.50.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceStatus
Enable or disable this smart alarm analog source.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.50.1.20 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueAlarmMapping
Index of smart alarm that this analog source is mapped to.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.110.50.1.30 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceValue
The system value that is compared with the threshold.
|
SystemValueSourceValuer/w Textual Convention: SystemValueSourceValue EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.50.1.40 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceValueIndex
The index of the selected system value.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.110.50.1.42 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceInput
Shows the actual value of the selected system value that is compared against the threshold.
|
0.01Float Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.110.50.1.45 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceThresholdType
Determines whether the threshold is an upper or lower threshold to the system value.
|
ThresholdTyper/w Textual Convention: ThresholdType EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.50.1.50 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceThreshold
The threshold, the system value is compared to.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.110.50.1.60 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceHysteresis
If non-zero, the system value must exceed the threshold +/- this value before the source becomes false again.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.110.50.1.65 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceActiveCount
Count of edge transitions required to make this output become active. 1 = output follows input.
|
Unsigned16r/w Textual Convention: Unsigned16 Integer32Type Constraints: range: 0..65535 |
.1.3.6.1.4.1.1918.2.14.10.110.50.1.70 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceInactiveCount
Count of edge transitions required to make this output become inactive. 1 = output follows input.
|
Unsigned16r/w Textual Convention: Unsigned16 Integer32Type Constraints: range: 0..65535 |
.1.3.6.1.4.1.1918.2.14.10.110.50.1.80 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
smartAlarmSystemValueSourceCount
Transition count.
|
Signed16 Textual Convention: Signed16 Integer32Type Constraints: range: -32768..32767 |
.1.3.6.1.4.1.1918.2.14.10.110.50.1.90 |
sourceManualTable
table.1.3.6.1.4.1.1918.2.14.10.110.60
·
1 row entry
·
6 columns
Table for sourceManual
Entry for sourceManual
Indexes
sourceManualIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
sourceManualIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.110.60.1.1 |
||||||||||||
|
smartAlarmIsManualSourceTriggered
Indicates whether or not this manual source is currently considered true or false.
|
SourceState Textual Convention: SourceState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.60.1.10 |
||||||||||||
|
smartAlarmSourceManualStatus
Enable or disable this smart alarm manual.
|
EnableStater/w Textual Convention: EnableState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.60.1.20 |
||||||||||||
|
smartAlarmSourceManualTrigger
Trigger input for this manual Alarm.
|
Booleanr/w Textual Convention: Boolean EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.60.1.30 |
||||||||||||
|
smartAlarmSourceManualMapping
Index of smart alarm that this manual is mapped to.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.110.60.1.40 |
||||||||||||
|
smartAlarmSourceManualPeriod
When non-zero, this source will oscillate at this period. Alarm deactivation and activation recognition times affect on/off time (duty ratio).
|
sTimeIntervalInSecondsr/w Textual Convention: TimeIntervalInSeconds Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.1918.2.14.10.110.60.1.50 |
.1.3.6.1.4.1.1918.2.14.10.110.70
·
1 row entry
·
8 columns
Table for smartAlarmNamedItems
Entry for smartAlarmNamedItems
Indexes
smartAlarmNamedItemsIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
smartAlarmNamedItemsIndex
Automatically generated index object.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.1918.2.14.10.110.70.1.1 |
||||||||||||
|
smartAlarmItemMapping
Index of smart alarm that this item is mapped to.
|
Unsigned8r/w Textual Convention: Unsigned8 Integer32Type Constraints: range: 0..255 |
.1.3.6.1.4.1.1918.2.14.10.110.70.1.10 |
||||||||||||
|
smartAlarmItemValue
Value derived from the item.
|
0.01Float Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.110.70.1.20 |
||||||||||||
|
smartAlarmItemName
The name of the item. Optionally append ':' then the index.
|
OctetStringr/w Constraints: range: 0-40 |
.1.3.6.1.4.1.1918.2.14.10.110.70.1.30 |
||||||||||||
|
smartAlarmItemTriggerState
Indicates the trigger state of this source alarm after comparing its value with its zero value.
|
SourceState Textual Convention: SourceState EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.70.1.50 |
||||||||||||
|
smartAlarmItemThresholdType
Determines whether the threshold is an upper or lower threshold to the system value.
|
ThresholdTyper/w Textual Convention: ThresholdType EnumerationType Values:
|
.1.3.6.1.4.1.1918.2.14.10.110.70.1.60 |
||||||||||||
|
smartAlarmItemThreshold
The threshold, the system value is compared to.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.110.70.1.70 |
||||||||||||
|
smartAlarmItemHysteresis
If non-zero, the system value must exceed the threshold +/- this value before the source becomes false again.
|
0.01Floatr/w Textual Convention: Float Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.1918.2.14.10.110.70.1.80 |