enableLvdAcTimer
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.60
Object
column
r/w
EnableState
If Enabled, during an AC failure the LVD will disconnect after the AC Timer Delay, even if the Disconnect Voltage has not been reached.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.70.75.50.1.60- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- lvdEntry
- Table
- lvdTable
- Siblings
- 13
Syntax
EnableState
- Source
- EnableState
- Base type
Enumeration
Values & Constraints
Type Values
0 | disabled |
1 | enabled |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| lvdIndex Automatically generated index object. | column | Integer32 | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.1 |
| lvdState The state of this LVD control process. | column | LvdState | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.10 |
| enableLvdChainedToPrevious If Enabled, the LVD will not disconnect until the previous LVD (the LVD numbered one less) has been disconnected for the configured recognition time. This item is ignored by the f… | column | EnableState | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.100 |
| lvdRemoteManualControl Allows remote manual control of the LVD. Reconnects on remote manual control, remote manual timeout, UI or Smart Alarm manual control or AC-State becomes ok. | column | Boolean | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.120 |
| lvdInhibited Indicates whether this LVD currently cannot change state due to the inhibit time. | column | Boolean | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.15 |
| enableLvdVoltageDisconnect If Enabled, the LVD will disconnect when the bus voltage falls below the Disconnect Voltage and will not reconnect until it is above the Reconnect Voltage. | column | EnableState | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.20 |
| lvdDisconnectVoltage If voltage based disconnect is enabled, the LVD will disconnect if the bus voltage has been below this voltage for the recognition time. | column | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.30 |
| lvdReconnectVoltage If voltage based disconnect is enabled, the LVD will reconnect only if the bus voltage has been above this voltage for the recognition time. | column | 0.01 V Float | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.40 |
| lvdName The name of this LVD. | column | OctetString | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.5 |
| lvdRecognitionPeriod The time the bus voltage must be below or above the thresholds before the LVD disconnects or connects. | column | s TimeIntervalInSeconds | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.50 |
| lvdAcTimerDisconnectDelay If Enabled, the LVD will disconnect after this delay following an AC failure, unless the Disconnect Voltage is reached or AC is restored first. | column | min TimeIntervalInMinutes | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.70 |
| enableLvdSaDisconnect If Enabled, the LVD will disconnect immediately when the specified smart alarm becomes active. | column | EnableState | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.80 |
| lvdSaDisconnectIndex If Enabled, the LVD will disconnect immediately when this smart alarm becomes active. | column | Unsigned8 | .1.3.6.1.4.1.1918.2.14.10.70.75.50.1.90 |