RITTAL-CMC-TC-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
15
Rows
15
Columns
153

cmcTcUnit1SensorTable

table mandatory
.1.3.6.1.4.1.2606.4.2.3.5.2 · 1 row entry · 14 columns
Headline of sensor table
cmcTcUnit1SensorEntry entry .1.3.6.1.4.1.2606.4.2.3.5.2.1
Entries of sensor table
Indexes
unit1SensorIndex
Column Syntax OID
unit1SensorIndex mandatory
Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit1NumberOfSensors.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.3.5.2.1.1
unit1SensorType mandatory
Type of sensor which is connected to sensor unit 1 to sensor[unit1SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type…
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4access
5vibration
6motion
7smoke
8airFlow
9type6
10temperature
11current4to20
12humidity
13userNO
14userNC
15lock
16unlock
17voltOK
18voltage
19fanOK
20readerKeypad
21dutyPWM
22fanStatus
23leakage
24warningRTT
25alarmRTT
26filterRTT
27heatflowRCT
28alarmRCT
29warningRCT
30currentPSM
31statusPSM
32positionPSM
33airFlap
34acoustic
35detACfault
36detACfirstAlarm
37detACmainAlarm
38rfidTag
40rpm11LCP
41rpm12LCP
42rpm21LCP
43rpm22LCP
44rpm31LCP
45rpm32LCP
46rpm41LCP
47rpm42LCP
48airTemp11LCP
49airTemp12LCP
50airTemp21LCP
51airTemp22LCP
52airTemp31LCP
53airTemp32LCP
54airTemp41LCP
55airTemp42LCP
56temp1LCP
57temp2LCP
58waterInTemp
59waterOutTemp
60waterFlow
61fanSpeed
62valve
63statusLCP
64waterDelta
65valveActual
66contrTemp2
67condensateDuration
68condensateCycles
72totalKWhPSM
73totalKWPSM
74frequencyPSM
75voltagePSM
76voltStatusPSM
77amperePSM
78ampStatusPSM
79kWPSM
80kWhPSM
81kWhTempPSM
100temperatureWL
101temperature1WL
102humidityWL
103accessWL
104userNOWL
105userNCWL
106analogWL
.1.3.6.1.4.1.2606.4.2.3.5.2.1.2
unit1SensorText mandatory
Descriptional text for each sensor (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.3.5.2.1.3
unit1SensorStatus mandatory
Actual status of the sensor
Enumeration
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7warning
8tooLow
9tooHigh
10error
.1.3.6.1.4.1.2606.4.2.3.5.2.1.4
unit1SensorValue mandatory
Value of sensor
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.5.2.1.5
unit1SensorSetHigh mandatory
Value for high setpoint of sensor
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.5.2.1.6
unit1SensorSetLow mandatory
Value for low setpoint of sensor,
also used as alarm delay
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.5.2.1.7
unit1SensorSetWarn mandatory
Value for warning setpoint of sensor,
also used as fan threshold
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.5.2.1.8
unit1SensorHysteresis mandatory
% -Value for hysteresis for High, Low and Warning,
input in % from actual setpoint
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.5.2.1.9
unit1SensorDisplayFactor mandatory
Factor of sensor value and setpoints,
devide actual value with this value,
e. g. factor = 10: sensor value = 100, actual value = 10.0
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.5.2.1.10
unit1SensorScaleStart mandatory
Value for start value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 10,
also valid for setpoints
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.5.2.1.11
unit1SensorScaleEnd mandatory
Value for end value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 60,
also valid for setpoints
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.5.2.1.12
unit1SensorUnit mandatory
Unit for 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 'A'
OctetStringr/w
Constraints:
range: 0-10
.1.3.6.1.4.1.2606.4.2.3.5.2.1.13
unit1SensorInfo mandatory
Additional information to the sensor,
e. g. Serialnumber, Signal Quality..
OctetString
Constraints:
range: 0-50
.1.3.6.1.4.1.2606.4.2.3.5.2.1.14

cmcTcUnit1OutputTable

table mandatory
.1.3.6.1.4.1.2606.4.2.3.6.2 · 1 row entry · 9 columns
Headline of output table
cmcTcUnit1OutputEntry entry .1.3.6.1.4.1.2606.4.2.3.6.2.1
Entries of output table
Indexes
unit1OutputIndex
Column Syntax OID
unit1OutputIndex mandatory
Index for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit1NumberOfOutputs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.3.6.2.1.1
unit1OutputType mandatory
Type of output which is connected to sensor unit 1 to output[unit1OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: …
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4doorLock
5univLock1
6univLock2
7fan
8fanSpeedContr
9universalOut
10roomLock
11powerOut
12doorLockMaster
13doorLockFRi
14setpoint
15setpointTimax
16hysteresisRCT
17commandRCT
18relayPSM
19setHighPSM
20setLowPSM
21setpointRTT
22setTimaxRTT
23powerOut1
24doorMagnet
30controlModeLCP
31minFanSpeedLCP
32minDeltaTLCP
33maxDeltaTLCP
34kPLCP
35kILCP
36kDLCP
37flowRateLCP
38cwValueLCP
39deltaTLCP
40ctrModLCP
42voltHighPSM
43voltLowPSM
44ampHighPSM
45ampLowPSM
46commandPSM
.1.3.6.1.4.1.2606.4.2.3.6.2.1.2
unit1OutputText mandatory
Descriptional text for each output (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.3.6.2.1.3
unit1OutputStatus mandatory
Actual status of the output
Enumerationr/w
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7setOff
8setOn
.1.3.6.1.4.1.2606.4.2.3.6.2.1.4
unit1OutputValue mandatory
Value for output
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.6.2.1.5
unit1OutputSet mandatory
Command for output
Enumerationr/w
Enumerated Values:
1off
2on
3lock
4unlock
5unlockDelay
.1.3.6.1.4.1.2606.4.2.3.6.2.1.6
unit1OutputConfig mandatory
Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control
Enumerationr/w
Enumerated Values:
1disRemote
2enRemote
.1.3.6.1.4.1.2606.4.2.3.6.2.1.7
unit1OutputDelay mandatory
Unsigned Value for delay,
after this time the output will fall into the previous state
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.6.2.1.8
unit1OutputTimeoutAction mandatory
State for output if timeout (RS422) occurs
Enumerationr/w
Enumerated Values:
1stay
2off
3on
.1.3.6.1.4.1.2606.4.2.3.6.2.1.9

cmcTcUnit1MsgTable

table mandatory
.1.3.6.1.4.1.2606.4.2.3.7.2 · 1 row entry · 11 columns
Headline of message table
cmcTcUnit1MsgEntry entry .1.3.6.1.4.1.2606.4.2.3.7.2.1
Entries of message table
Indexes
unit1MsgIndex
Column Syntax OID
unit1MsgIndex mandatory
Index for the list of message entries. Its value ranges
between 1 and the value of cmcTcUnit1NumberOfMsgs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.3.7.2.1.1
unit1MsgText mandatory
Descriptional text for each message (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.3.7.2.1.2
unit1MsgStatus mandatory
Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog val…
Enumeration
Enumerated Values:
1notAvail
2configChanged
3error
4ok
5alarm
6warning
7tooLow
8tooHigh
9setOff
10setOn
11open
12closed
13locked
14unlRemote
15unlReaderKeypad
16unlSNMP
17unlWEB
18unlTimer
19noAccess
20circuit1
21circuit2
22lowBatt
.1.3.6.1.4.1.2606.4.2.3.7.2.1.3
unit1MsgRelay mandatory
Setup of Alarm relay for this message/alarm
1: no switching of alarm relay
2: switching of alarm relay
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.3.7.2.1.4
unit1MsgBeeper mandatory
Setup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarm
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.3.7.2.1.5
unit1MsgTrap1 mandatory
Trap receiver 1 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.3.7.2.1.6
unit1MsgTrap2 mandatory
Trap receiver 2 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.3.7.2.1.7
unit1MsgTrap3 mandatory
Trap receiver 3 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.3.7.2.1.8
unit1MsgTrap4 mandatory
Trap receiver 4 and Event Logging activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.3.7.2.1.9
unit1MsgQuit mandatory
Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key
Enumerationr/w
Enumerated Values:
1auto
2manual
.1.3.6.1.4.1.2606.4.2.3.7.2.1.10
unit1MsgDelay mandatory
Delay of alarm condition
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.3.7.2.1.11

cmcTcUnit2SensorTable

table mandatory
.1.3.6.1.4.1.2606.4.2.4.5.2 · 1 row entry · 14 columns
Headline of sensor table
cmcTcUnit2SensorEntry entry .1.3.6.1.4.1.2606.4.2.4.5.2.1
Entries of sensor table
Indexes
unit2SensorIndex
Column Syntax OID
unit2SensorIndex mandatory
Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit2NumberOfSensors.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.4.5.2.1.1
unit2SensorType mandatory
Type of sensor which is connected to sensor unit 2 to sensor[unit2SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type…
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4access
5vibration
6motion
7smoke
8airFlow
9type6
10temperature
11current4to20
12humidity
13userNO
14userNC
15lock
16unlock
17voltOK
18voltage
19fanOK
20readerKeypad
21dutyPWM
22fanStatus
23leakage
24warningRTT
25alarmRTT
26filterRTT
27heatflowRCT
28alarmRCT
29warningRCT
30currentPSM
31statusPSM
32positionPSM
33airFlap
34acoustic
35detACfault
36detACfirstAlarm
37detACmainAlarm
38rfidTag
40rpm11LCP
41rpm12LCP
42rpm21LCP
43rpm22LCP
44rpm31LCP
45rpm32LCP
46rpm41LCP
47rpm42LCP
48airTemp11LCP
49airTemp12LCP
50airTemp21LCP
51airTemp22LCP
52airTemp31LCP
53airTemp32LCP
54airTemp41LCP
55airTemp42LCP
56temp1LCP
57temp2LCP
58waterInTemp
59waterOutTemp
60waterFlow
61fanSpeed
62valve
63statusLCP
64waterDelta
65valveActual
66contrTemp2
67condensateDuration
68condensateCycles
72totalKWhPSM
73totalKWPSM
74frequencyPSM
75voltagePSM
76voltStatusPSM
77amperePSM
78ampStatusPSM
79kWPSM
80kWhPSM
81kWhTempPSM
100temperatureWL
101temperature1WL
102humidityWL
103accessWL
104userNOWL
105userNCWL
106analogWL
.1.3.6.1.4.1.2606.4.2.4.5.2.1.2
unit2SensorText mandatory
Descriptional text for each sensor (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.4.5.2.1.3
unit2SensorStatus mandatory
Actual status of the sensor
Enumeration
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7warning
8tooLow
9tooHigh
10error
.1.3.6.1.4.1.2606.4.2.4.5.2.1.4
unit2SensorValue mandatory
Value of sensor
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.5.2.1.5
unit2SensorSetHigh mandatory
Value for high setpoint of sensor
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.5.2.1.6
unit2SensorSetLow mandatory
Value for low setpoint of sensor,
also used as alarm delay
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.5.2.1.7
unit2SensorSetWarn mandatory
Value for warning setpoint of sensor,
also used as fan threshold
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.5.2.1.8
unit2SensorHysteresis mandatory
% -Value for hysteresis for High, Low and Warning,
input in % from actual setpoint
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.5.2.1.9
unit2SensorDisplayFactor mandatory
Factor of sensor value and setpoints,
devide actual value with this value,
e. g. factor = 10: sensor value = 100, actual value = 10.0
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.5.2.1.10
unit2SensorScaleStart mandatory
Value for start value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 10,
also valid for setpoints
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.5.2.1.11
unit2SensorScaleEnd mandatory
Value for end value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 60,
also valid for setpoints
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.5.2.1.12
unit2SensorUnit mandatory
Unit for 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 'A'
OctetStringr/w
Constraints:
range: 0-10
.1.3.6.1.4.1.2606.4.2.4.5.2.1.13
unit2SensorInfo mandatory
Additional information to the sensor,
e. g. Serialnumber, Signal Quality..
OctetString
Constraints:
range: 0-50
.1.3.6.1.4.1.2606.4.2.4.5.2.1.14

cmcTcUnit2OutputTable

table mandatory
.1.3.6.1.4.1.2606.4.2.4.6.2 · 1 row entry · 9 columns
Headline of output table
cmcTcUnit2OutputEntry entry .1.3.6.1.4.1.2606.4.2.4.6.2.1
Entries of output table
Indexes
unit2OutputIndex
Column Syntax OID
unit2OutputIndex mandatory
Index for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit2NumberOfOutputs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.4.6.2.1.1
unit2OutputType mandatory
Type of output which is connected to sensor unit 2 to output[unit2OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locki…
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4doorLock
5univLock1
6univLock2
7fan
8fanSpeedContr
9universalOut
10roomLock
11powerOut
12doorLockMaster
13doorLockFRi
14setpoint
15setpointTimax
16hysteresisRCT
17commandRCT
18relayPSM
19setHighPSM
20setLowPSM
21setpointRTT
22setTimaxRTT
23powerOut1
24doorMagnet
30controlModeLCP
31minFanSpeedLCP
32minDeltaTLCP
33maxDeltaTLCP
34kPLCP
35kILCP
36kDLCP
37flowRateLCP
38cwValueLCP
39deltaTLCP
40ctrModLCP
42voltHighPSM
43voltLowPSM
44ampHighPSM
45ampLowPSM
46commandPSM
.1.3.6.1.4.1.2606.4.2.4.6.2.1.2
unit2OutputText mandatory
Descriptional text for each output (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.4.6.2.1.3
unit2OutputStatus mandatory
Actual status of the output
Enumerationr/w
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7setOff
8setOn
.1.3.6.1.4.1.2606.4.2.4.6.2.1.4
unit2OutputValue mandatory
Signed value for output
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.6.2.1.5
unit2OutputSet mandatory
Command for output
Enumerationr/w
Enumerated Values:
1off
2on
3lock
4unlock
5unlockDelay
.1.3.6.1.4.1.2606.4.2.4.6.2.1.6
unit2OutputConfig mandatory
Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control
Enumerationr/w
Enumerated Values:
1disRemote
2enRemote
.1.3.6.1.4.1.2606.4.2.4.6.2.1.7
unit2OutputDelay mandatory
Unsigned Value for delay,
after this time the output will fall into the previous state
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.6.2.1.8
unit2OutputTimeoutAction mandatory
State for output if timeout (RS422) occurs
Enumerationr/w
Enumerated Values:
1stay
2off
3on
.1.3.6.1.4.1.2606.4.2.4.6.2.1.9

cmcTcUnit2MsgTable

table mandatory
.1.3.6.1.4.1.2606.4.2.4.7.2 · 1 row entry · 11 columns
Headline of message table
cmcTcUnit2MsgEntry entry .1.3.6.1.4.1.2606.4.2.4.7.2.1
Entries of message table
Indexes
unit2MsgIndex
Column Syntax OID
unit2MsgIndex mandatory
Index for the list of alarm entries. Its value ranges
between 1 and the value of cmcTcUnit2NumberOfMsgs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.4.7.2.1.1
unit2MsgText mandatory
Descriptional text for each message (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.4.7.2.1.2
unit2MsgStatus mandatory
Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog val…
Enumeration
Enumerated Values:
1notAvail
2configChanged
3error
4ok
5alarm
6warning
7tooLow
8tooHigh
9setOff
10setOn
11open
12closed
13locked
14unlRemote
15unlReaderKeypad
16unlSNMP
17unlWEB
18unlTimer
19noAccess
20circuit1
21circuit2
22lowBatt
.1.3.6.1.4.1.2606.4.2.4.7.2.1.3
unit2MsgRelay mandatory
Setup of Alarm relay for this alarm
2: no switching of alarm relay
1: switching of alarm relay
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.4.7.2.1.4
unit2MsgBeeper mandatory
Setup of Alarm beeper for this alarm
2: no audible alarm
1: audible alarm
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.4.7.2.1.5
unit2MsgTrap1 mandatory
Trap receiver 1 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.4.7.2.1.6
unit2MsgTrap2 mandatory
Trap receiver 2 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.4.7.2.1.7
unit2MsgTrap3 mandatory
Trap receiver 3 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.4.7.2.1.8
unit2MsgTrap4 mandatory
Trap receiver 4 and Event Logging activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.4.7.2.1.9
unit2MsgQuit mandatory
Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key
Enumerationr/w
Enumerated Values:
1auto
2manual
.1.3.6.1.4.1.2606.4.2.4.7.2.1.10
unit2MsgDelay mandatory
Delay of alarm condition
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.4.7.2.1.11

cmcTcUnit3SensorTable

table mandatory
.1.3.6.1.4.1.2606.4.2.5.5.2 · 1 row entry · 14 columns
Headline of sensor table
cmcTcUnit3SensorEntry entry .1.3.6.1.4.1.2606.4.2.5.5.2.1
Entries of sensor table
Indexes
unit3SensorIndex
Column Syntax OID
unit3SensorIndex mandatory
Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit3NumberOfSensors.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.5.5.2.1.1
unit3SensorType mandatory
Type of sensor which is connected to sensor unit 3 to sensor[unit3SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type…
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4access
5vibration
6motion
7smoke
8airFlow
9type6
10temperature
11current4to20
12humidity
13userNO
14userNC
15lock
16unlock
17voltOK
18voltage
19fanOK
20readerKeypad
21dutyPWM
22fanStatus
23leakage
24warningRTT
25alarmRTT
26filterRTT
27heatflowRCT
28alarmRCT
29warningRCT
30currentPSM
31statusPSM
32positionPSM
33airFlap
34acoustic
35detACfault
36detACfirstAlarm
37detACmainAlarm
38rfidTag
40rpm11LCP
41rpm12LCP
42rpm21LCP
43rpm22LCP
44rpm31LCP
45rpm32LCP
46rpm41LCP
47rpm42LCP
48airTemp11LCP
49airTemp12LCP
50airTemp21LCP
51airTemp22LCP
52airTemp31LCP
53airTemp32LCP
54airTemp41LCP
55airTemp42LCP
56temp1LCP
57temp2LCP
58waterInTemp
59waterOutTemp
60waterFlow
61fanSpeed
62valve
63statusLCP
64waterDelta
65valveActual
66contrTemp2
67condensateDuration
68condensateCycles
72totalKWhPSM
73totalKWPSM
74frequencyPSM
75voltagePSM
76voltStatusPSM
77amperePSM
78ampStatusPSM
79kWPSM
80kWhPSM
81kWhTempPSM
100temperatureWL
101temperature1WL
102humidityWL
103accessWL
104userNOWL
105userNCWL
106analogWL
.1.3.6.1.4.1.2606.4.2.5.5.2.1.2
unit3SensorText mandatory
Descriptional text for each sensor (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.5.5.2.1.3
unit3SensorStatus mandatory
Actual status of the sensor
Enumeration
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7warning
8tooLow
9tooHigh
10error
.1.3.6.1.4.1.2606.4.2.5.5.2.1.4
unit3SensorValue mandatory
Value of sensor
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.5.2.1.5
unit3SensorSetHigh mandatory
Value for high setpoint of sensor
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.5.2.1.6
unit3SensorSetLow mandatory
Value for low setpoint of sensor
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.5.2.1.7
unit3SensorSetWarn mandatory
Value for warning setpoint of sensor,
also used as fan threshold
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.5.2.1.8
unit3SensorHysteresis mandatory
% -Value for hysteresis for High, Low and Warning,
input in % from actual setpoint
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.5.2.1.9
unit3SensorDisplayFactor mandatory
Factor of sensor value and setpoints,
devide actual value with this value,
e. g. factor = 10: sensor value = 100, actual value = 10.0
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.5.2.1.10
unit3SensorScaleStart mandatory
Value for start value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 10,
also valid for setpoints
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.5.2.1.11
unit3SensorScaleEnd mandatory
Value for end value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 60,
also valid for setpoints
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.5.2.1.12
unit3SensorUnit mandatory
Unit for 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 'A'
OctetStringr/w
Constraints:
range: 0-10
.1.3.6.1.4.1.2606.4.2.5.5.2.1.13
unit3SensorInfo mandatory
Additional information to the sensor,
e. g. Serialnumber, Signal Quality..
OctetString
Constraints:
range: 0-50
.1.3.6.1.4.1.2606.4.2.5.5.2.1.14

cmcTcUnit3OutputTable

table mandatory
.1.3.6.1.4.1.2606.4.2.5.6.2 · 1 row entry · 9 columns
Headline of output table
cmcTcUnit3OutputEntry entry .1.3.6.1.4.1.2606.4.2.5.6.2.1
Entries of output table
Indexes
unit3OutputIndex
Column Syntax OID
unit3OutputIndex mandatory
Index for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit3NumberOfOutputs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.5.6.2.1.1
unit3OutputType mandatory
Type of output which is connected to sensor unit 3 to output[unit3OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: …
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4doorLock
5univLock1
6univLock2
7fan
8fanSpeedContr
9universalOut
10roomLock
11powerOut
12doorLockMaster
13doorLockFRi
14setpoint
15setpointTimax
16hysteresisRCT
17commandRCT
18relayPSM
19setHighPSM
20setLowPSM
21setpointRTT
22setTimaxRTT
23powerOut1
24doorMagnet
30controlModeLCP
31minFanSpeedLCP
32minDeltaTLCP
33maxDeltaTLCP
34kPLCP
35kILCP
36kDLCP
37flowRateLCP
38cwValueLCP
39deltaTLCP
40ctrModLCP
42voltHighPSM
43voltLowPSM
44ampHighPSM
45ampLowPSM
46commandPSM
.1.3.6.1.4.1.2606.4.2.5.6.2.1.2
unit3OutputText mandatory
Descriptional text for each output (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.5.6.2.1.3
unit3OutputStatus mandatory
Actual status of the output
Enumerationr/w
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7setOff
8setOn
.1.3.6.1.4.1.2606.4.2.5.6.2.1.4
unit3OutputValue mandatory
Value for output
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.6.2.1.5
unit3OutputSet mandatory
Command for output
Enumerationr/w
Enumerated Values:
1off
2on
3lock
4unlock
5unlockDelay
.1.3.6.1.4.1.2606.4.2.5.6.2.1.6
unit3OutputConfig mandatory
Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control
Enumerationr/w
Enumerated Values:
1disRemote
2enRemote
.1.3.6.1.4.1.2606.4.2.5.6.2.1.7
unit3OutputDelay mandatory
Unsigned Value for delay,
after this time the output will fall into the previous state
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.6.2.1.8
unit3OutputTimeoutAction mandatory
State for output if timeout (RS422) occurs
Enumerationr/w
Enumerated Values:
1stay
2off
3on
.1.3.6.1.4.1.2606.4.2.5.6.2.1.9

cmcTcUnit3MsgTable

table mandatory
.1.3.6.1.4.1.2606.4.2.5.7.2 · 1 row entry · 11 columns
Headline of message table
cmcTcUnit3MsgEntry entry .1.3.6.1.4.1.2606.4.2.5.7.2.1
Entries of message table
Indexes
unit3MsgIndex
Column Syntax OID
unit3MsgIndex mandatory
Index for the list of alarm entries. Its value ranges
between 1 and the value of cmcTcUnit3NumberOfMsgs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.5.7.2.1.1
unit3MsgText mandatory
Descriptional text for each message (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.5.7.2.1.2
unit3MsgStatus mandatory
Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog val…
Enumeration
Enumerated Values:
1notAvail
2configChanged
3error
4ok
5alarm
6warning
7tooLow
8tooHigh
9setOff
10setOn
11open
12closed
13locked
14unlRemote
15unlReaderKeypad
16unlSNMP
17unlWEB
18unlTimer
19noAccess
20circuit1
21circuit2
22lowBatt
.1.3.6.1.4.1.2606.4.2.5.7.2.1.3
unit3MsgRelay mandatory
Setup of Alarm relay for this alarm
1: no switching of alarm relay
2: switching of alarm relay
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.5.7.2.1.4
unit3MsgBeeper mandatory
Setup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarm
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.5.7.2.1.5
unit3MsgTrap1 mandatory
Trap receiver 1 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.5.7.2.1.6
unit3MsgTrap2 mandatory
Trap receiver 2 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.5.7.2.1.7
unit3MsgTrap3 mandatory
Trap receiver 3 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.5.7.2.1.8
unit3MsgTrap4 mandatory
Trap receiver 4 and Event Logging activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.5.7.2.1.9
unit3MsgQuit mandatory
Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key
Enumerationr/w
Enumerated Values:
1auto
2manual
.1.3.6.1.4.1.2606.4.2.5.7.2.1.10
unit3MsgDelay mandatory
Delay of alarm condition
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.5.7.2.1.11

cmcTcUnit4SensorTable

table mandatory
.1.3.6.1.4.1.2606.4.2.6.5.2 · 1 row entry · 14 columns
Headline of sensor table
cmcTcUnit4SensorEntry entry .1.3.6.1.4.1.2606.4.2.6.5.2.1
Entries of sensor table
Indexes
unit4SensorIndex
Column Syntax OID
unit4SensorIndex mandatory
Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit4NumberOfSensors.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.6.5.2.1.1
unit4SensorType mandatory
Type of sensor which is connected to sensor unit 4 to sensor[unit4SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type…
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4access
5vibration
6motion
7smoke
8airFlow
9type6
10temperature
11current4to20
12humidity
13userNO
14userNC
15lock
16unlock
17voltOK
18voltage
19fanOK
20readerKeypad
21dutyPWM
22fanStatus
23leakage
24warningRTT
25alarmRTT
26filterRTT
27heatflowRCT
28alarmRCT
29warningRCT
30currentPSM
31statusPSM
32positionPSM
33airFlap
34acoustic
35detACfault
36detACfirstAlarm
37detACmainAlarm
38rfidTag
40rpm11LCP
41rpm12LCP
42rpm21LCP
43rpm22LCP
44rpm31LCP
45rpm32LCP
46rpm41LCP
47rpm42LCP
48airTemp11LCP
49airTemp12LCP
50airTemp21LCP
51airTemp22LCP
52airTemp31LCP
53airTemp32LCP
54airTemp41LCP
55airTemp42LCP
56temp1LCP
57temp2LCP
58waterInTemp
59waterOutTemp
60waterFlow
61fanSpeed
62valve
63statusLCP
64waterDelta
65valveActual
66contrTemp2
67condensateDuration
68condensateCycles
72totalKWhPSM
73totalKWPSM
74frequencyPSM
75voltagePSM
76voltStatusPSM
77amperePSM
78ampStatusPSM
79kWPSM
80kWhPSM
81kWhTempPSM
100temperatureWL
101temperature1WL
102humidityWL
103accessWL
104userNOWL
105userNCWL
106analogWL
.1.3.6.1.4.1.2606.4.2.6.5.2.1.2
unit4SensorText mandatory
Descriptional text for each sensor (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.6.5.2.1.3
unit4SensorStatus mandatory
Actual status of the sensor
Enumeration
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7warning
8tooLow
9tooHigh
10error
.1.3.6.1.4.1.2606.4.2.6.5.2.1.4
unit4SensorValue mandatory
Value of sensor
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.5.2.1.5
unit4SensorSetHigh mandatory
Value for high setpoint of sensor
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.5.2.1.6
unit4SensorSetLow mandatory
Value for low setpoint of sensor
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.5.2.1.7
unit4SensorSetWarn mandatory
Value for warning setpoint of sensor,
also used as fan threshold
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.5.2.1.8
unit4SensorHysteresis mandatory
% -Value for hysteresis for High, Low and Warning,
input in % from actual setpoint
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.5.2.1.9
unit4SensorDisplayFactor mandatory
Factor of sensor value and setpoints,
devide actual value with this value,
e. g. factor = 10: sensor value = 100, actual value = 10.0
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.5.2.1.10
unit4SensorScaleStart mandatory
Value for start value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 10,
also valid for setpoints
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.5.2.1.11
unit4SensorScaleEnd mandatory
Value for end value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 60,
also valid for setpoints
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.5.2.1.12
unit4SensorUnit mandatory
Unit for 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 'A'
OctetStringr/w
Constraints:
range: 0-10
.1.3.6.1.4.1.2606.4.2.6.5.2.1.13
unit4SensorInfo mandatory
Additional information to the sensor,
e. g. Serialnumber, Signal Quality..
OctetString
Constraints:
range: 0-50
.1.3.6.1.4.1.2606.4.2.6.5.2.1.14

cmcTcUnit4OutputTable

table mandatory
.1.3.6.1.4.1.2606.4.2.6.6.2 · 1 row entry · 9 columns
Headline of output table
cmcTcUnit4OutputEntry entry .1.3.6.1.4.1.2606.4.2.6.6.2.1
Entries of output table
Indexes
unit4OutputIndex
Column Syntax OID
unit4OutputIndex mandatory
Index for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit4NumberOfOutputs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.6.6.2.1.1
unit4OutputType mandatory
Type of output which is connected to sensor unit 4 to output[unit4OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: …
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4doorLock
5univLock1
6univLock2
7fan
8fanSpeedContr
9universalOut
10roomLock
11powerOut
12doorLockMaster
13doorLockFRi
14setpoint
15setpointTimax
16hysteresisRCT
17commandRCT
18relayPSM
19setHighPSM
20setLowPSM
21setpointRTT
22setTimaxRTT
23powerOut1
24doorMagnet
30controlModeLCP
31minFanSpeedLCP
32minDeltaTLCP
33maxDeltaTLCP
34kPLCP
35kILCP
36kDLCP
37flowRateLCP
38cwValueLCP
39deltaTLCP
40ctrModLCP
42voltHighPSM
43voltLowPSM
44ampHighPSM
45ampLowPSM
46commandPSM
.1.3.6.1.4.1.2606.4.2.6.6.2.1.2
unit4OutputText mandatory
Descriptional text for each output (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.6.6.2.1.3
unit4OutputStatus mandatory
Actual status of the output
Enumerationr/w
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7setOff
8setOn
.1.3.6.1.4.1.2606.4.2.6.6.2.1.4
unit4OutputValue mandatory
Value for output
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.6.2.1.5
unit4OutputSet mandatory
Command for output
Enumerationr/w
Enumerated Values:
1off
2on
3lock
4unlock
5unlockDelay
.1.3.6.1.4.1.2606.4.2.6.6.2.1.6
unit4OutputConfig mandatory
Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control
Enumerationr/w
Enumerated Values:
1disRemote
2enRemote
.1.3.6.1.4.1.2606.4.2.6.6.2.1.7
unit4OutputDelay mandatory
Unsigned Value for delay,
after this time the output will fall into the previous state
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.6.2.1.8
unit4OutputTimeoutAction mandatory
State for output if timeout (RS422) occurs
Enumerationr/w
Enumerated Values:
1stay
2off
3on
.1.3.6.1.4.1.2606.4.2.6.6.2.1.9

cmcTcUnit4MsgTable

table mandatory
.1.3.6.1.4.1.2606.4.2.6.7.2 · 1 row entry · 11 columns
Headline of message table
cmcTcUnit4MsgEntry entry .1.3.6.1.4.1.2606.4.2.6.7.2.1
Entries of message table
Indexes
unit4MsgIndex
Column Syntax OID
unit4MsgIndex mandatory
Index for the list of alarm entries. Its value ranges
between 1 and the value of cmcTcUnit4NumberOfMsgs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.6.7.2.1.1
unit4MsgText mandatory
Descriptional text for each message (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.6.7.2.1.2
unit4MsgStatus mandatory
Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog val…
Enumeration
Enumerated Values:
1notAvail
2configChanged
3error
4ok
5alarm
6warning
7tooLow
8tooHigh
9setOff
10setOn
11open
12closed
13locked
14unlRemote
15unlReaderKeypad
16unlSNMP
17unlWEB
18unlTimer
19noAccess
20circuit1
21circuit2
22lowBatt
.1.3.6.1.4.1.2606.4.2.6.7.2.1.3
unit4MsgRelay mandatory
Setup of Alarm relay for this alarm
1: no switching of alarm relay
2: switching of alarm relay
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.6.7.2.1.4
unit4MsgBeeper mandatory
Setup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarm
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.6.7.2.1.5
unit4MsgTrap1 mandatory
Trap receiver 1 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.6.7.2.1.6
unit4MsgTrap2 mandatory
Trap receiver 2 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.6.7.2.1.7
unit4MsgTrap3 mandatory
Trap receiver 3 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.6.7.2.1.8
unit4MsgTrap4 mandatory
Trap receiver 4 and Event Logging activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2606.4.2.6.7.2.1.9
unit4MsgQuit mandatory
Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key
Enumerationr/w
Enumerated Values:
1auto
2manual
.1.3.6.1.4.1.2606.4.2.6.7.2.1.10
unit4MsgDelay mandatory
Delay of alarm condition
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.6.7.2.1.11

cmcTcValuesTable

table mandatory
.1.3.6.1.4.1.2606.4.2.7.8 · 1 row entry · 7 columns
Headline of values-table
cmcTcValuesEntry entry .1.3.6.1.4.1.2606.4.2.7.8.1
Entries of values-table
Indexes
valuesIndex
Column Syntax OID
valuesIndex mandatory
Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcNumberOfValues.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.2.7.8.1.1
valuesText mandatory
Descriptional text for each value (entry in the table)
of the extension card
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.2606.4.2.7.8.1.2
valuesStatus mandatory
Actual status of the value of the extension card
Enumeration
Enumerated Values:
1notAvail
2lost
3changed
4ok
5tooLow
6tooHigh
7error
.1.3.6.1.4.1.2606.4.2.7.8.1.3
valuesValue mandatory
Value of sensor
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.7.8.1.4
valuesSetHigh mandatory
Value for high setpoint of sensor
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.7.8.1.5
valuesSetLow mandatory
Value for low setpoint of sensor
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.7.8.1.6
valuesHysteresis mandatory
% -Value for hysteresis for High and Low setpoints,
input in % from actual setpoint
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2606.4.2.7.8.1.7

cmcTcTimerTable

table mandatory
.1.3.6.1.4.1.2606.4.3.1.8.2 · 1 row entry · 7 columns
Headline of status-table
cmcTcTimerEntry entry .1.3.6.1.4.1.2606.4.3.1.8.2.1
Entries of timer-table
Indexes
cmcTcTimerIndex
Column Syntax OID
cmcTcTimerIndex mandatory
Index for the list of timer entries. Its value ranges
between 1 and the value of cmcTcTimerNumber.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.3.1.8.2.1.1
cmcTcTimerStatus mandatory
Actual status of the timer
Enumeration
Enumerated Values:
1switchedOff
2switchedOn
3noTime
.1.3.6.1.4.1.2606.4.3.1.8.2.1.2
cmcTcTimerDayOfWeek mandatory
Selection of day of week for timer to switch
Enumerationr/w
Enumerated Values:
1sun
2mon
3tue
4wed
5thu
6fri
7sat
8sat-sun
9mon-fri
10mon-sun
.1.3.6.1.4.1.2606.4.3.1.8.2.1.3
cmcTcTimeOn mandatory
Time to switch on current function,
Format: HH:MM
OctetStringr/w
Constraints:
range: 0-5
.1.3.6.1.4.1.2606.4.3.1.8.2.1.4
cmcTcTimeOff mandatory
Time to switch off current function,
Format: HH:MM
OctetStringr/w
Constraints:
range: 0-5
.1.3.6.1.4.1.2606.4.3.1.8.2.1.5
cmcTcTimeControl mandatory
Control via RTC
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.2606.4.3.1.8.2.1.6
cmcTcTimerFunction mandatory
Function which is controlled via timer
1: unlock via keypad 1 on unit 1 or remote input lock 1 is disabled
2: unlock via keypad 2 on unit 1 or remote input lock 2 is disabled
3 unlock via keypad 1 on unit 2 or remote in…
Enumerationr/w
Enumerated Values:
1disKeypad1-1
2disKeypad2-1
3disKeypad1-2
4disKeypad2-2
5disKeypad1-3
6disKeypad2-3
7disKeypad1-4
8disKeypad2-4
9unlDoor1-1
10unlDoor2-1
11unlDoor1-2
12unlDoor2-2
13unlDoor1-3
14unlDoor2-3
15unlDoor1-4
16unlDoor2-5
17disTrapRec1
18disTrapRec2
19disTrapRec3
20disTrapRec4
21disSMS
22schedule1
23schedule2
24schedule3
25schedule4
26disSMS1
27disSMS2
28disSMS3
29disSMS4
.1.3.6.1.4.1.2606.4.3.1.8.2.1.7

cmcTcTrapTableTable

table mandatory
.1.3.6.1.4.1.2606.4.4.7.2 · 1 row entry · 3 columns
A list of trap-receiver entries
cmcTcTrapTableEntry entry .1.3.6.1.4.1.2606.4.4.7.2.1
Entries of trapTable
Indexes
trapIndex
Column Syntax OID
trapIndex mandatory
Index for the trap-receiver-table. Its value ranges between
1 and the value of traptableNumber
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2606.4.4.7.2.1.1
trapStatus mandatory
Enable or disable trap receiver
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.2606.4.4.7.2.1.2
trapIPaddress mandatory
IP-address of trap-receiver
OctetStringr/w
Constraints:
range: 0-15