unit3SensorType
RITTAL-CMC-TC-MIB ·
.1.3.6.1.4.1.2606.4.2.5.5.2.1.2
Object
column
mandatory
Enumeration
Type of sensor which is connected to sensor unit 3 to sensor[unit3SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage 18: voltage value 19: fan status 20: cardreader or keypad, connected to I2C port 21: duty cycle of fan, FCS-Unit 22: status of fan, FCS-Unit 23: leakage sensor 24: warning, RittalTopTherm(RTT)-Unit 25: alarm, RittalTopTherm-Unit 26: temperature difference filter monitor, RTT-Unit 27: heatflow RCT-Unit 28: alarm RCT-Unit 29: warning RCT-Unit 30: actual current*10, PSM-Unit 31: status PSM-Unit 32: position PSM-Unit, normal/reversed = circuit 1/2 33: air Flap 34: acoustic sensor 35: DET-AC fault (extinguisher) 36: DET-AC first alarm (extinguisher) 37: DET-AC main alarm (extinguisher) 38: DRC: RFID Tag 40-47: RPM Fan 1.1 - Fan 4.2, LCP 48-55: Air temperature 1.1 - 4.2, LCP 56,57: actual temperature 1,2, LCP 58: water inlet temperature, LCP 59: water outlet temperature, LCP 60: water flow 61: fan speed (desired value) 62: status valve, LCP 63: status LCP 64: temperature difference water temperatures 65: control temperature 1, LCP 66: control temperature 2, LCP 67: condensate pump, duration, LCP 68: condensate pump, cycles, LCP 72: total energy*10 (kWh), PSM 73: total power*10 (kW), PSM 74: frequency*10 (Hz), PSM 75: voltage*10 (V), PSM 76: voltage status, PSM 77: current*10 (A), PSM 78: current status, PSM 79: power*10 (kW) per phase, PSM 80: energy*10 (kWh) per phase, PSM 81: temporary energy*10 (kWh) per phase, PSM 100: temperature sensor, wireless 101: temperature sensor (combi), wireless 102: humidity sensor, wireless 103: access sensor, wireless 104: user sensor with normally opened contact, wireless 105: user sensor with normally closed contact, wireless 106: analog sensor 4..20mA, wireless
Context
- MIB
- RITTAL-CMC-TC-MIB
- OID
.1.3.6.1.4.1.2606.4.2.5.5.2.1.2- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- cmcTcUnit3SensorEntry
- Table
- cmcTcUnit3SensorTable
- Siblings
- 13
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | notAvail |
2 | failure |
3 | overflow |
4 | access |
5 | vibration |
6 | motion |
7 | smoke |
8 | airFlow |
9 | type6 |
10 | temperature |
11 | current4to20 |
12 | humidity |
13 | userNO |
14 | userNC |
15 | lock |
16 | unlock |
17 | voltOK |
18 | voltage |
19 | fanOK |
20 | readerKeypad |
21 | dutyPWM |
22 | fanStatus |
23 | leakage |
24 | warningRTT |
25 | alarmRTT |
26 | filterRTT |
27 | heatflowRCT |
28 | alarmRCT |
29 | warningRCT |
30 | currentPSM |
31 | statusPSM |
32 | positionPSM |
33 | airFlap |
34 | acoustic |
35 | detACfault |
36 | detACfirstAlarm |
37 | detACmainAlarm |
38 | rfidTag |
40 | rpm11LCP |
41 | rpm12LCP |
42 | rpm21LCP |
43 | rpm22LCP |
44 | rpm31LCP |
45 | rpm32LCP |
46 | rpm41LCP |
47 | rpm42LCP |
48 | airTemp11LCP |
49 | airTemp12LCP |
50 | airTemp21LCP |
51 | airTemp22LCP |
52 | airTemp31LCP |
53 | airTemp32LCP |
54 | airTemp41LCP |
55 | airTemp42LCP |
56 | temp1LCP |
57 | temp2LCP |
58 | waterInTemp |
59 | waterOutTemp |
60 | waterFlow |
61 | fanSpeed |
62 | valve |
63 | statusLCP |
64 | waterDelta |
65 | valveActual |
66 | contrTemp2 |
67 | condensateDuration |
68 | condensateCycles |
72 | totalKWhPSM |
73 | totalKWPSM |
74 | frequencyPSM |
75 | voltagePSM |
76 | voltStatusPSM |
77 | amperePSM |
78 | ampStatusPSM |
79 | kWPSM |
80 | kWhPSM |
81 | kWhTempPSM |
100 | temperatureWL |
101 | temperature1WL |
102 | humidityWL |
103 | accessWL |
104 | userNOWL |
105 | userNCWL |
106 | analogWL |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| unit3SensorIndex mandatory Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit3NumberOfSensors. | column | Integer32 | .1.3.6.1.4.1.2606.4.2.5.5.2.1.1 |
| unit3SensorDisplayFactor mandatory Factor of sensor value and setpoints,
devide actual value with this value,
e. g. factor = 10: sensor value = 100, actual value = 10.0 | column | Integer32 | .1.3.6.1.4.1.2606.4.2.5.5.2.1.10 |
| unit3SensorScaleStart mandatory Value for start value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 10,
also valid for… | column | Integer32 | .1.3.6.1.4.1.2606.4.2.5.5.2.1.11 |
| unit3SensorScaleEnd mandatory Value for end value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 60,
also valid for s… | column | Integer32 | .1.3.6.1.4.1.2606.4.2.5.5.2.1.12 |
| unit3SensorUnit mandatory Unit for 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 'A' | column | OctetString | .1.3.6.1.4.1.2606.4.2.5.5.2.1.13 |
| unit3SensorInfo mandatory Additional information to the sensor,
e. g. Serialnumber, Signal Quality.. | column | OctetString | .1.3.6.1.4.1.2606.4.2.5.5.2.1.14 |
| unit3SensorText mandatory Descriptional text for each sensor (entry in the table) | column | OctetString | .1.3.6.1.4.1.2606.4.2.5.5.2.1.3 |
| unit3SensorStatus mandatory Actual status of the sensor | column | Enumeration | .1.3.6.1.4.1.2606.4.2.5.5.2.1.4 |
| unit3SensorValue mandatory Value of sensor | column | Integer32 | .1.3.6.1.4.1.2606.4.2.5.5.2.1.5 |
| unit3SensorSetHigh mandatory Value for high setpoint of sensor | column | Integer32 | .1.3.6.1.4.1.2606.4.2.5.5.2.1.6 |
| unit3SensorSetLow mandatory Value for low setpoint of sensor | column | Integer32 | .1.3.6.1.4.1.2606.4.2.5.5.2.1.7 |
| unit3SensorSetWarn mandatory Value for warning setpoint of sensor,
also used as fan threshold | column | Integer32 | .1.3.6.1.4.1.2606.4.2.5.5.2.1.8 |
| unit3SensorHysteresis mandatory % -Value for hysteresis for High, Low and Warning,
input in % from actual setpoint | column | Integer32 | .1.3.6.1.4.1.2606.4.2.5.5.2.1.9 |