unit1SensorStatus
RITTAL-CMC-TC-MIB ·
.1.3.6.1.4.1.2606.4.2.3.5.2.1.4
Object
column
mandatory
Enumeration
Actual status of the sensor
Context
- MIB
- RITTAL-CMC-TC-MIB
- OID
.1.3.6.1.4.1.2606.4.2.3.5.2.1.4- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- cmcTcUnit1SensorEntry
- Table
- cmcTcUnit1SensorTable
- Siblings
- 13
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | notAvail |
2 | lost |
3 | changed |
4 | ok |
5 | off |
6 | on |
7 | warning |
8 | tooLow |
9 | tooHigh |
10 | error |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| unit1SensorIndex mandatory Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit1NumberOfSensors. | column | Integer32 | .1.3.6.1.4.1.2606.4.2.3.5.2.1.1 |
| unit1SensorDisplayFactor mandatory Factor of sensor value and setpoints,
devide actual value with this value,
e. g. factor = 10: sensor value = 100, actual value = 10.0 | column | Integer32 | .1.3.6.1.4.1.2606.4.2.3.5.2.1.10 |
| unit1SensorScaleStart mandatory Value for start value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 10,
also valid for… | column | Integer32 | .1.3.6.1.4.1.2606.4.2.3.5.2.1.11 |
| unit1SensorScaleEnd mandatory Value for end value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 60,
also valid for s… | column | Integer32 | .1.3.6.1.4.1.2606.4.2.3.5.2.1.12 |
| unit1SensorUnit mandatory Unit for 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 'A' | column | OctetString | .1.3.6.1.4.1.2606.4.2.3.5.2.1.13 |
| unit1SensorInfo mandatory Additional information to the sensor,
e. g. Serialnumber, Signal Quality.. | column | OctetString | .1.3.6.1.4.1.2606.4.2.3.5.2.1.14 |
| unit1SensorType mandatory Type of sensor which is connected to sensor unit 1 to sensor[unit1SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor typ… | column | Enumeration | .1.3.6.1.4.1.2606.4.2.3.5.2.1.2 |
| unit1SensorText mandatory Descriptional text for each sensor (entry in the table) | column | OctetString | .1.3.6.1.4.1.2606.4.2.3.5.2.1.3 |
| unit1SensorValue mandatory Value of sensor | column | Integer32 | .1.3.6.1.4.1.2606.4.2.3.5.2.1.5 |
| unit1SensorSetHigh mandatory Value for high setpoint of sensor | column | Integer32 | .1.3.6.1.4.1.2606.4.2.3.5.2.1.6 |
| unit1SensorSetLow mandatory Value for low setpoint of sensor,
also used as alarm delay | column | Integer32 | .1.3.6.1.4.1.2606.4.2.3.5.2.1.7 |
| unit1SensorSetWarn mandatory Value for warning setpoint of sensor,
also used as fan threshold | column | Integer32 | .1.3.6.1.4.1.2606.4.2.3.5.2.1.8 |
| unit1SensorHysteresis mandatory % -Value for hysteresis for High, Low and Warning,
input in % from actual setpoint | column | Integer32 | .1.3.6.1.4.1.2606.4.2.3.5.2.1.9 |