unit4SensorType

RITTAL-CMC-TC-MIB · .1.3.6.1.4.1.2606.4.2.6.5.2.1.2

Object

column mandatory Enumeration
Type of sensor which is connected to sensor unit 4 to sensor[unit4SensorIndex]
1:        no sensor connected
2:        sensor failure
3:        value overflow
4:        sensor type 1, access sensor
5:        sensor type 2, vibration sensor
6:        sensor type 3, motion sensor
7:        sensor type 4, smoke sensor
8:        sensor type 5, air flow sensor
9:        sensor type 6, reserved
10:       sensor type 7, temperature sensor
11:       sensor type 8, 4..20mA sensor
12:       sensor type 9, humidity sensor  
13:       user sensor with normally opened contact
14:       user sensor with normally closed contact
15:       door locked sensor from locking device
16:       remote unlock sensor (e.g. external keypad)
17:       voltage sensor, indicates status of main voltage
18:	voltage value
19:	fan status
20:       cardreader or keypad, connected to I2C port              
21:	duty cycle of fan, FCS-Unit
22:	status of fan, FCS-Unit
23:	leakage sensor
24:	warning, RittalTopTherm(RTT)-Unit
25:	alarm, RittalTopTherm-Unit
26:	temperature difference filter monitor, RTT-Unit
27:	heatflow RCT-Unit
28:	alarm RCT-Unit
29:	warning RCT-Unit
30:	actual current*10, PSM-Unit
31:	status PSM-Unit
32:	position PSM-Unit, normal/reversed = circuit 1/2
33:	air Flap
34:	acoustic sensor
35:	DET-AC fault (extinguisher)
36:	DET-AC first alarm (extinguisher)
37:	DET-AC main alarm (extinguisher)
38:	DRC: RFID Tag
40-47:	RPM Fan 1.1 - Fan 4.2, LCP
48-55:	Air temperature 1.1 - 4.2, LCP
56,57:	actual temperature 1,2, LCP
58:	water inlet temperature, LCP
59:	water outlet temperature, LCP
60:	water flow
61:	fan speed (desired value)
62:	status valve, LCP
63:	status LCP
64:	temperature difference water temperatures
65:	control temperature 1, LCP
66:	control temperature 2, LCP
67:	condensate pump, duration, LCP
68:	condensate pump, cycles, LCP
72:	total energy*10 (kWh), PSM
73:	total power*10 (kW), PSM
74:	frequency*10 (Hz), PSM
75:	voltage*10 (V), PSM
76:	voltage status, PSM
77:	current*10 (A), PSM
78:	current status, PSM
79:	power*10 (kW) per phase, PSM
80:	energy*10 (kWh) per phase, PSM
81:	temporary energy*10 (kWh) per phase, PSM
	 100:	temperature sensor, wireless
	 101:	temperature sensor (combi), wireless
	 102:	humidity sensor, wireless
	 103:	access sensor, wireless
	 104:	user sensor with normally opened contact, wireless
	 105:	user sensor with normally closed contact, wireless
	 106:	analog sensor 4..20mA, wireless

Context

MIB
RITTAL-CMC-TC-MIB
OID
.1.3.6.1.4.1.2606.4.2.6.5.2.1.2
Type
column
Access
readonly
Status
mandatory
Parent
cmcTcUnit4SensorEntry
Table
cmcTcUnit4SensorTable
Siblings
13

Syntax

Enumeration

Values & Constraints

Enumerated Values
1notAvail
2failure
3overflow
4access
5vibration
6motion
7smoke
8airFlow
9type6
10temperature
11current4to20
12humidity
13userNO
14userNC
15lock
16unlock
17voltOK
18voltage
19fanOK
20readerKeypad
21dutyPWM
22fanStatus
23leakage
24warningRTT
25alarmRTT
26filterRTT
27heatflowRCT
28alarmRCT
29warningRCT
30currentPSM
31statusPSM
32positionPSM
33airFlap
34acoustic
35detACfault
36detACfirstAlarm
37detACmainAlarm
38rfidTag
40rpm11LCP
41rpm12LCP
42rpm21LCP
43rpm22LCP
44rpm31LCP
45rpm32LCP
46rpm41LCP
47rpm42LCP
48airTemp11LCP
49airTemp12LCP
50airTemp21LCP
51airTemp22LCP
52airTemp31LCP
53airTemp32LCP
54airTemp41LCP
55airTemp42LCP
56temp1LCP
57temp2LCP
58waterInTemp
59waterOutTemp
60waterFlow
61fanSpeed
62valve
63statusLCP
64waterDelta
65valveActual
66contrTemp2
67condensateDuration
68condensateCycles
72totalKWhPSM
73totalKWPSM
74frequencyPSM
75voltagePSM
76voltStatusPSM
77amperePSM
78ampStatusPSM
79kWPSM
80kWhPSM
81kWhTempPSM
100temperatureWL
101temperature1WL
102humidityWL
103accessWL
104userNOWL
105userNCWL
106analogWL