XUPS-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
6
Rows
6
Columns
40
xupsInputTable
table.1.3.6.1.4.1.534.1.3.4
·
1 row entry
·
7 columns
A list of input table entries. The number of entries is given by the value of xupsInputNumPhases.
The input table entry containing the current,
voltage, etc. readings for one phase.
voltage, etc. readings for one phase.
Indexes
xupsInputPhase
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
xupsInputPhase
The number of the phase. Serves as index for input table.
|
Integer32 Constraints: range: 0-6 |
.1.3.6.1.4.1.534.1.3.4.1.1 |
||||||||||||
|
xupsInputVoltage
The measured input voltage from the UPS meters in volts.
|
RMS VoltsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.3.4.1.2 |
||||||||||||
|
xupsInputCurrent
The measured input current from the UPS meters in amps.
|
RMS AmpsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.3.4.1.3 |
||||||||||||
|
xupsInputWatts
The measured input real power in watts.
|
WattsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.3.4.1.4 |
||||||||||||
|
xupsInputId
value indicates what measurement is being stored in this table row :
phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.1.3.4.1.5 |
||||||||||||
|
xupsInputName
A descriptive name for the phase, example : L1/A for the phase 1.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.534.1.3.4.1.6 |
||||||||||||
|
xupsInputCurrentHighPrecision
The measured input current from the UPS meters in tenth of amps.
|
RMS tenth of AmpsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.3.4.1.7 |
xupsOutputTable
table.1.3.6.1.4.1.534.1.4.4
·
1 row entry
·
9 columns
A list of output table entries. The number of entries is given by the value of xupsOutputNumPhases.
Output Table Entry containing voltage, current, etc.
Indexes
xupsOutputPhase
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
xupsOutputPhase
The number of the phase. Serves as index for output table.
|
Integer32 Constraints: range: 0-6 |
.1.3.6.1.4.1.534.1.4.4.1.1 |
||||||||||||
|
xupsOutputVoltage
The measured output voltage from the UPS metering in volts.
|
RMS VoltsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.4.4.1.2 |
||||||||||||
|
xupsOutputCurrent
The measured UPS output current in amps.
|
RMS AmpsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.4.4.1.3 |
||||||||||||
|
xupsOutputWatts
The measured real output power in watts.
|
WattsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.4.4.1.4 |
||||||||||||
|
xupsOutputId
value indicates what measurement is being stored in this table row :
phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.1.4.4.1.5 |
||||||||||||
|
xupsOutputName
A descriptive name for the phase.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.534.1.4.4.1.6 |
||||||||||||
|
xupsOutputCurrentHighPrecision
The measured output current from the UPS meters in tenth of amps.
|
RMS tenth of AmpsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.4.4.1.7 |
||||||||||||
|
xupsOutputPercentLoad
The percentage of the UPS power capacity presently
being used on this output line |
percentInteger32 Constraints: range: 0-200 |
.1.3.6.1.4.1.534.1.4.4.1.8 |
||||||||||||
|
xupsOutputVA
The measured apparent output power in VA.
|
VAInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.4.4.1.9 |
xupsBypassTable
table.1.3.6.1.4.1.534.1.5.3
·
1 row entry
·
6 columns
A list of bypass table entries. The number of entries is given by the value of xupsBypassNumPhases.
Bypass Table Entry containing voltage for each phase.
Indexes
xupsBypassPhase
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
xupsBypassPhase
The Bypass Phase, index for the table.
|
Integer32 Constraints: range: 0-6 |
.1.3.6.1.4.1.534.1.5.3.1.1 |
||||||||||||
|
xupsBypassVoltage
The measured UPS bypass voltage in volts.
|
RMS VoltsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.5.3.1.2 |
||||||||||||
|
xupsBypassId
value indicates what measurement is being stored in this table row :
phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.1.5.3.1.3 |
||||||||||||
|
xupsBypassName
A descriptive name for the phase.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.534.1.5.3.1.4 |
||||||||||||
|
xupsBypassCurrentHighPrecision
The measured bypass current from the UPS meters in tenth of amps.
|
RMS tenth of AmpsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.5.3.1.5 |
||||||||||||
|
xupsBypassWatts
The measured real bypass power in watts.
|
WattsInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.5.3.1.6 |
xupsAlarmTable
table.1.3.6.1.4.1.534.1.7.2
·
1 row entry
·
3 columns
A list of alarm table entries. The number of entries is given by the value of xupsAlarms. Note that this table is sparsely (non-consecutively) numbered and will be empty if there are no active alarms.
Alarm Table Entry containing descriptive information
for one alarm entry.
for one alarm entry.
Indexes
xupsAlarmID
| Column | Syntax | OID |
|---|---|---|
|
xupsAlarmID
A unique identifier for an alarm condition.
|
Integer32 Constraints: range: 1-2147483647 |
.1.3.6.1.4.1.534.1.7.2.1.1 |
|
xupsAlarmDescr
A reference to an alarm description object. The object
referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. |
ObjectIdentifier | .1.3.6.1.4.1.534.1.7.2.1.2 |
|
xupsAlarmTime
The value of the MIB-II variable sysUpTime when the alarm
condition occurred. |
SNMPv2-SMITimeTicks Textual Convention: SNMPv2-SMITimeTicks Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.534.1.7.2.1.3 |
xupsAlarmEventTable
table.1.3.6.1.4.1.534.1.7.19
·
1 row entry
·
5 columns
A table of the UPS internal event history queue.
One of the entries in the UPS event history queue.
Indexes
xupsAlarmEventID
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
xupsAlarmEventID
A unique number that reflects the order in which the event
occurred. The oldest event in the queue will be number 1. Subsequent events will be numbered 2, 3, 4, etc. |
Integer32 Constraints: range: 1-400 |
.1.3.6.1.4.1.534.1.7.19.1.1 |
||||||
|
xupsAlarmEventDateAndTime
deprecated
The time and date that an event occurred as recorded in the UPS
internal event queue. This string will reflect the time and date as set in the UPS itself and will not be referenced to sysUpTime. The format is MM/DD/YYY… |
OctetString Constraints: range: 0-22 |
.1.3.6.1.4.1.534.1.7.19.1.2 |
||||||
|
xupsAlarmEventKind
deprecated
Enumerated value that tells whether the event is an
occurrence of an alarm condition or a clearing of an alarm condition. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.1.7.19.1.3 |
||||||
|
xupsAlarmEventDescr
deprecated
A description of the event stored in the UPS event queue.
This description will be a sixteen bit integer value representing one of the defined alarms in the Powerware Binary Computer Mode communication specification… |
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.7.19.1.4 |
||||||
|
xupsAlarmEventMsg
A text string describing each entry in the Event Log. The format of this
text message is free (not fixed) for the operator to read; good contents would be a time & date stamp, the event type, and a description of the … |
OctetString Constraints: range: 0-80 |
.1.3.6.1.4.1.534.1.7.19.1.5 |
xupsRecepTable
table.1.3.6.1.4.1.534.1.12.2
·
1 row entry
·
10 columns
A list of receptacle table entries. The number of entries is given by the value of xupsNumReceptacles.
A receptacle table entry containing the status and
control values for one receptacle.
control values for one receptacle.
Indexes
xupsRecepIndex
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
xupsRecepIndex
The number of the Receptacle. Serves as index for Receptacle table.
|
Integer32 Constraints: range: 1-64 |
.1.3.6.1.4.1.534.1.12.2.1.1 |
||||||||||||||||
|
xupsRecepStatus
The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
4=Off w/Pending ON, 5=Unknown, 6=Reserved for future, 7=Failed in Closed position, 8=Failed in Open position. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.1.12.2.1.2 |
||||||||||||||||
|
xupsRecepOffDelaySecs
The Delay until the Receptacle is turned Off. Setting
this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abor… |
secondsInteger32r/w Constraints: range: -1-2147483647 |
.1.3.6.1.4.1.534.1.12.2.1.3 |
||||||||||||||||
|
xupsRecepOnDelaySecs
The Delay until the Receptacle is turned On. Setting
this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort … |
secondsInteger32r/w Constraints: range: -1-2147483647 |
.1.3.6.1.4.1.534.1.12.2.1.4 |
||||||||||||||||
|
xupsRecepAutoOffDelay
The delay after going On Battery until the Receptacle is
automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 … |
secondsInteger32r/w Constraints: range: -1-32767 |
.1.3.6.1.4.1.534.1.12.2.1.5 |
||||||||||||||||
|
xupsRecepAutoOnDelay
Seconds delay after the Outlet is signaled to turn On before the Output is
Automatically turned ON. A value of -1 means that this Output should never be turned On automatically, but only when specifically commanded to d… |
secondsInteger32r/w Constraints: range: -1-32767 |
.1.3.6.1.4.1.534.1.12.2.1.6 |
||||||||||||||||
|
xupsRecepShedSecsWithRestart
Setting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsRecepOffDelaySecs, which might … |
secondsInteger32r/w Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.12.2.1.7 |
||||||||||||||||
|
xupsRecepHourlyPowerUsage
Units are Watt-hours.This is the energy consumed during the last hour.
|
WhInteger32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.12.2.1.8 |
||||||||||||||||
|
xupsRecepCumulativePowerUsage
Units are Watt-hours.This is the energy consumed since the last reset.
This object is writable so that it can be reset to 0. When it is written to 0, the xupsRecepCumulativePowerUsageTimer will be reset to 0 as well. |
WhInteger32r/w Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.534.1.12.2.1.9 |
||||||||||||||||
|
xupsRecepCumulativePowerUsageTimer
Time in seconds since the cumulative power usage was last reset.
|
SecondsSNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.534.1.12.2.1.10 |