XUPS-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
6
Rows
6
Columns
40
.1.3.6.1.4.1.534.1.3.4 · 1 row entry · 7 columns
A list of input table entries.  The number of entries
is given by the value of xupsInputNumPhases.
xupsInputEntry entry .1.3.6.1.4.1.534.1.3.4.1
The input table entry containing the current,
voltage, etc. readings for one phase.
Indexes
xupsInputPhase
Column Syntax OID
xupsInputPhase
The number of the phase. Serves as index for input table.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.534.1.3.4.1.1
xupsInputVoltage
The measured input voltage from the UPS meters in volts.
RMS VoltsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.3.4.1.2
xupsInputCurrent
The measured input current from the UPS meters in amps.
RMS AmpsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.3.4.1.3
xupsInputWatts
The measured input real power in watts.
WattsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.3.4.1.4
xupsInputId
value indicates what measurement is being stored in this table row :
phase1 to neutral, phase2 to neutral, phase3 to neutral,
phase1 to phase2, phase2 to phase3, phase3 to phase1.
Enumeration
Enumerated Values:
1phase1toN
2phase2toN
3phase3toN
4phase1to2
5phase2to3
6phase3to1
.1.3.6.1.4.1.534.1.3.4.1.5
xupsInputName
A descriptive name for the phase, example : L1/A for the phase 1.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.1.3.4.1.6
xupsInputCurrentHighPrecision
The measured input current from the UPS meters in tenth of amps.
RMS tenth of AmpsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.3.4.1.7
.1.3.6.1.4.1.534.1.4.4 · 1 row entry · 9 columns
A list of output table entries.  The number of entries
is given by the value of xupsOutputNumPhases.
xupsOutputEntry entry .1.3.6.1.4.1.534.1.4.4.1
Output Table Entry containing voltage, current, etc.
Indexes
xupsOutputPhase
Column Syntax OID
xupsOutputPhase
The number of the phase. Serves as index for output table.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.534.1.4.4.1.1
xupsOutputVoltage
The measured output voltage from the UPS metering in volts.
RMS VoltsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.4.4.1.2
xupsOutputCurrent
The measured UPS output current in amps.
RMS AmpsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.4.4.1.3
xupsOutputWatts
The measured real output power in watts.
WattsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.4.4.1.4
xupsOutputId
value indicates what measurement is being stored in this table row :
phase1 to neutral, phase2 to neutral, phase3 to neutral,
phase1 to phase2, phase2 to phase3, phase3 to phase1.
Enumeration
Enumerated Values:
1phase1toN
2phase2toN
3phase3toN
4phase1to2
5phase2to3
6phase3to1
.1.3.6.1.4.1.534.1.4.4.1.5
xupsOutputName
A descriptive name for the phase.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.1.4.4.1.6
xupsOutputCurrentHighPrecision
The measured output current from the UPS meters in tenth of amps.
RMS tenth of AmpsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.4.4.1.7
xupsOutputPercentLoad
The percentage of the UPS power capacity presently
being used on this output line
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.534.1.4.4.1.8
xupsOutputVA
The measured apparent output power in VA.
VAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.4.4.1.9
.1.3.6.1.4.1.534.1.5.3 · 1 row entry · 6 columns
A list of bypass table entries.  The number of entries
is given by the value of xupsBypassNumPhases.
xupsBypassEntry entry .1.3.6.1.4.1.534.1.5.3.1
Bypass Table Entry containing voltage for each phase.
Indexes
xupsBypassPhase
Column Syntax OID
xupsBypassPhase
The Bypass Phase, index for the table.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.534.1.5.3.1.1
xupsBypassVoltage
The measured UPS bypass voltage in volts.
RMS VoltsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.5.3.1.2
xupsBypassId
value indicates what measurement is being stored in this table row :
phase1 to neutral, phase2 to neutral, phase3 to neutral,
phase1 to phase2, phase2 to phase3, phase3 to phase1.
Enumeration
Enumerated Values:
1phase1toN
2phase2toN
3phase3toN
4phase1to2
5phase2to3
6phase3to1
.1.3.6.1.4.1.534.1.5.3.1.3
xupsBypassName
A descriptive name for the phase.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.1.5.3.1.4
xupsBypassCurrentHighPrecision
The measured bypass current from the UPS meters in tenth of amps.
RMS tenth of AmpsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.5.3.1.5
xupsBypassWatts
The measured real bypass power in watts.
WattsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.5.3.1.6
.1.3.6.1.4.1.534.1.7.2 · 1 row entry · 3 columns
A list of alarm table entries.  The number of entries
is given by the value of xupsAlarms.
Note that this table is sparsely (non-consecutively)
numbered and will be empty if there are no active alarms.
xupsAlarmEntry entry .1.3.6.1.4.1.534.1.7.2.1
Alarm Table Entry containing descriptive information
for one alarm entry.
Indexes
xupsAlarmID
Column Syntax OID
xupsAlarmID
A unique identifier for an alarm condition.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.534.1.7.2.1.1
xupsAlarmDescr
A reference to an alarm description object. The object
referenced should not be accessible, but rather be used to
provide a unique description of the alarm condition.
ObjectIdentifier .1.3.6.1.4.1.534.1.7.2.1.2
xupsAlarmTime
The value of the MIB-II variable sysUpTime when the alarm
condition occurred.
SNMPv2-SMITimeTicks
Textual Convention: SNMPv2-SMITimeTicks Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.534.1.7.2.1.3
.1.3.6.1.4.1.534.1.7.19 · 1 row entry · 5 columns
A table of the UPS internal event history queue.
xupsAlarmEventEntry entry .1.3.6.1.4.1.534.1.7.19.1
One of the entries in the UPS event history queue.
Indexes
xupsAlarmEventID
Column Syntax OID
xupsAlarmEventID
A unique number that reflects the order in which the event
occurred. The oldest event in the queue will be number 1.
Subsequent events will be numbered 2, 3, 4, etc.
Integer32
Constraints:
range: 1-400
.1.3.6.1.4.1.534.1.7.19.1.1
xupsAlarmEventDateAndTime deprecated
The time and date that an event occurred as recorded in the UPS
internal event queue. This string will reflect the time and
date as set in the UPS itself and will not be referenced to sysUpTime.
The format is MM/DD/YYY…
OctetString
Constraints:
range: 0-22
.1.3.6.1.4.1.534.1.7.19.1.2
xupsAlarmEventKind deprecated
Enumerated value that tells whether the event is an
occurrence of an alarm condition or a clearing of an
alarm condition.
Enumeration
Enumerated Values:
1occurred
2cleared
3unknown
.1.3.6.1.4.1.534.1.7.19.1.3
xupsAlarmEventDescr deprecated
A description of the event stored in the UPS event queue.
This description will be a sixteen bit integer value
representing one of the defined alarms in the Powerware Binary
Computer Mode communication specification…
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.7.19.1.4
xupsAlarmEventMsg
A text string describing each entry in the Event Log. The format of this
text message is free (not fixed) for the operator to read; good contents
would be a time & date stamp, the event type, and a description of the …
OctetString
Constraints:
range: 0-80
.1.3.6.1.4.1.534.1.7.19.1.5
.1.3.6.1.4.1.534.1.12.2 · 1 row entry · 10 columns
A list of receptacle table entries.  The number of entries
is given by the value of xupsNumReceptacles.
xupsRecepEntry entry .1.3.6.1.4.1.534.1.12.2.1
A receptacle table entry containing the status and
control values for one receptacle.
Indexes
xupsRecepIndex
Column Syntax OID
xupsRecepIndex
The number of the Receptacle. Serves as index for Receptacle table.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.534.1.12.2.1.1
xupsRecepStatus
The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
4=Off w/Pending ON, 5=Unknown, 6=Reserved for future,
7=Failed in Closed position, 8=Failed in Open position.
Enumeration
Enumerated Values:
1on
2off
3pendingOff
4pendingOn
5unknown
6reserved
7failedClosed
8failedOpen
.1.3.6.1.4.1.534.1.12.2.1.2
xupsRecepOffDelaySecs
The Delay until the Receptacle is turned Off. Setting
this value to other than -1 will cause the UPS output to
turn off after the number of seconds (0 is immediately).
Setting it to -1 will cause an attempt to abor…
secondsInteger32r/w
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.534.1.12.2.1.3
xupsRecepOnDelaySecs
The Delay until the Receptacle is turned On. Setting
this value to other than -1 will cause the UPS output to
turn on after the number of seconds (0 is immediately).
Setting it to -1 will cause an attempt to abort …
secondsInteger32r/w
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.534.1.12.2.1.4
xupsRecepAutoOffDelay
The delay after going On Battery until the Receptacle is
automatically turned Off. A value of -1 means that this Output should
never be turned Off automatically, but must be turned Off only by command.
Values from 0 …
secondsInteger32r/w
Constraints:
range: -1-32767
.1.3.6.1.4.1.534.1.12.2.1.5
xupsRecepAutoOnDelay
Seconds delay after the Outlet is signaled to turn On before the Output is
Automatically turned ON. A value of -1 means that this Output should never
be turned On automatically, but only when specifically commanded to d…
secondsInteger32r/w
Constraints:
range: -1-32767
.1.3.6.1.4.1.534.1.12.2.1.6
xupsRecepShedSecsWithRestart
Setting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.
Unlike xupsRecepOffDelaySecs, which might …
secondsInteger32r/w
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.12.2.1.7
xupsRecepHourlyPowerUsage
Units are Watt-hours.This is the energy consumed during the last hour.
WhInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.12.2.1.8
xupsRecepCumulativePowerUsage
Units are Watt-hours.This is the energy consumed since the last reset.
This object is writable so that it can be reset to 0.
When it is written to 0, the xupsRecepCumulativePowerUsageTimer will be reset to 0 as well.
WhInteger32r/w
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.12.2.1.9
xupsRecepCumulativePowerUsageTimer
Time in seconds since the cumulative power usage was last reset.
SecondsSNMPv2-SMICounter32
Textual Convention: SNMPv2-SMICounter32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.534.1.12.2.1.10