xupsRecepAutoOffDelay

XUPS-MIB · .1.3.6.1.4.1.534.1.12.2.1.5

Object

column r/w seconds Integer32
The delay after going On Battery until the Receptacle is 
automatically turned Off.  A value of -1 means that this Output should 
never be turned Off automatically, but must be turned Off only by command.
Values from 0 to 30 are valid, but probably innappropriate.
The AutoOffDelay can be used to prioritize loads in the event of a prolonged 
power outage; less critical loads will turn off earlier to extend battery 
time for the more critical loads. If the utility power is restored before the 
AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off.

Context

MIB
XUPS-MIB
OID
.1.3.6.1.4.1.534.1.12.2.1.5
Type
column
Access
readwrite
Status
current
Units
seconds
Parent
xupsRecepEntry
Table
xupsRecepTable
Siblings
9

Syntax

seconds Integer32

Values & Constraints

Object Constraints
range: -1-32767

Related Objects

Sibling Objects