xupsRecepCumulativePowerUsageTimer
XUPS-MIB ·
.1.3.6.1.4.1.534.1.12.2.1.10
Object
Time in seconds since the cumulative power usage was last reset.
Context
- MIB
- XUPS-MIB
- OID
.1.3.6.1.4.1.534.1.12.2.1.10- Type
- column
- Access
- readonly
- Status
- current
- Units
- Seconds
- Parent
- xupsRecepEntry
- Table
- xupsRecepTable
- Siblings
- 9
Syntax
Seconds SNMPv2-SMICounter32
- Source
- SNMPv2-SMICounter32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| xupsRecepIndex The number of the Receptacle. Serves as index for Receptacle table. | column | Integer32 | .1.3.6.1.4.1.534.1.12.2.1.1 |
| xupsRecepStatus The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
4=Off w/Pending ON, 5=Unknown, 6=Reserved for future,
7=Failed in Closed position, 8=Failed in Open position. | column | Enumeration | .1.3.6.1.4.1.534.1.12.2.1.2 |
| xupsRecepOffDelaySecs The Delay until the Receptacle is turned Off. Setting
this value to other than -1 will cause the UPS output to
turn off after the number of seconds (0 is immediately).
Settin… | column | seconds Integer32 | .1.3.6.1.4.1.534.1.12.2.1.3 |
| xupsRecepOnDelaySecs The Delay until the Receptacle is turned On. Setting
this value to other than -1 will cause the UPS output to
turn on after the number of seconds (0 is immediately).
Setting … | column | seconds Integer32 | .1.3.6.1.4.1.534.1.12.2.1.4 |
| xupsRecepAutoOffDelay The delay after going On Battery until the Receptacle is
automatically turned Off. A value of -1 means that this Output should
never be turned Off automatically, but must be tu… | column | seconds Integer32 | .1.3.6.1.4.1.534.1.12.2.1.5 |
| xupsRecepAutoOnDelay Seconds delay after the Outlet is signaled to turn On before the Output is
Automatically turned ON. A value of -1 means that this Output should never
be turned On automatically, b… | column | seconds Integer32 | .1.3.6.1.4.1.534.1.12.2.1.6 |
| xupsRecepShedSecsWithRestart Setting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.
Un… | column | seconds Integer32 | .1.3.6.1.4.1.534.1.12.2.1.7 |
| xupsRecepHourlyPowerUsage Units are Watt-hours.This is the energy consumed during the last hour. | column | Wh Integer32 | .1.3.6.1.4.1.534.1.12.2.1.8 |
| xupsRecepCumulativePowerUsage Units are Watt-hours.This is the energy consumed since the last reset.
This object is writable so that it can be reset to 0.
When it is written to 0, the xupsRecepCumulativePowerU… | column | Wh Integer32 | .1.3.6.1.4.1.534.1.12.2.1.9 |