cpiPduTable
table.1.3.6.1.4.1.30932.1.10.1.2.10
·
1 row entry
·
18 columns
This table contains a list of PDU entries that are being monitored
by the PDU.
The table contains one, or many rows, depending upon the
number of PDUs being monitored. Each row in the table represents a PDU
in the daisy chain.
This table always contains at least one entry and a maximum of 32 entries.
The MAC address is used as an index on the table to allow data collectors
to ensure that information can be retrieved for a specific PDU.
This entry defines the columns to be populated in the
'cpiPduTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU MAC that is globally unique.
'cpiPduTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU MAC that is globally unique.
Indexes
cpiPduMac
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
cpiPduMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.1 |
||||||
|
cpiPduModel
Get the model number of the PDU.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.2 |
||||||
|
cpiPduName
Set or get the user assigned name of the PDU.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.3 |
||||||
|
cpiPduDescription
Set or get the user assigned description of the PDU.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.4 |
||||||
|
cpiPduHasBranchMonitor
An indicator if the PDU supports monitoring voltage, and current on branches in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.5 |
||||||
|
cpiPduHasOutletMonitor
An indicator if the PDU supports monitoring current on the individual outlets in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.6 |
||||||
|
cpiPduHasOutletControl
An indicator if the PDU supports control (turn on/off) individual outlets in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.7 |
||||||
|
cpiPduNumberBranches
Get the number of branches (breakers) in the PDU.
|
Integer32 Constraints: range: 0-12 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.8 |
||||||
|
cpiPduNumberOutlets
Get the number of outlets in the PDU.
|
Integer32 Constraints: range: 0-72 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.9 |
||||||
|
cpiPduOutOfService
Set or get whether the PDU is in-service.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.10 |
||||||
|
cpiPduVersion
Get the firmware version number of the PDU.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.11 |
||||||
|
cpiPduUpgrade
An indicator if the PDU firmware is being upgraded.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.12 |
||||||
|
cpiPduChainRole
Get the role of the PDU in a daisy chain.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.13 |
||||||
|
cpiPduIp
Get IP address of the PDU.
|
SNMPv2-SMIIpAddress Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.14 |
||||||
|
cpiPduIpv6
Get the IPv6 address of the PDU.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.15 |
||||||
|
cpiPduTotalPower
Get the power in volt-amps for the entire PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.16 |
||||||
|
cpiPduCabinetId
Get/set the name of the cabinet the PDU is in.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.17 |
||||||
|
cpiPduSerialNum
Get the serial number of the PDU.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.18 |
cpiPduLineTable
table.1.3.6.1.4.1.30932.1.10.1.3.10
·
1 row entry
·
3 columns
This table contains a list of PDU line entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of input lines. Each row
in the table represents a PDU line in the daisy chain.
The table is indexed based on the corresponding Line Input ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'cpiPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
cpiPduLineId cpiPduLineMac
| Column | Syntax | OID |
|---|---|---|
|
cpiPduLineMac
Get the MAC address of the PDU that owns the input line.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.3.10.1.1 |
|
cpiPduLineId
Get the ID of the input line on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.10.1.2 |
|
cpiPduLineCurrent
Get current draw in 1/100 amp of the line on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.10.1.3 |
cpiPduBranchTable
table.1.3.6.1.4.1.30932.1.10.1.3.110
·
1 row entry
·
9 columns
This table contains a list of PDU branch entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row
in the table represents a PDU branch in the daisy chain.
The table is indexed based on the corresponding Branch ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduBranchTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'cpiPduBranchTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
cpiPduBranchId cpiPduBranchMac
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
cpiPduBranchMac
Get the MAC address of the PDU that owns the branch.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.1 |
||||||
|
cpiPduBranchId
Get the ID of the branch on the owning PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.2 |
||||||
|
cpiPduBranchCurrent
Get the current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.3 |
||||||
|
cpiPduBranchMaxCurrent
Get the maximum current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.4 |
||||||
|
cpiPduBranchVoltage
Get the voltage in 1/10 volts of the branch on the PDU. Convert the value by dividing by 10.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.5 |
||||||
|
cpiPduBranchPower
Get the power in volt-amps for the branch.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.6 |
||||||
|
cpiPduBranchPowerFactor
Get the power factor for the branch.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.7 |
||||||
|
cpiPduBranchStatus
Get the alarm status of the branch.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.3.110.1.8 |
||||||
|
cpiPduBranchEnergy
Get the branch energy accumulated in decaVA-secs, divide by 360 to obtain VA-hr.
|
SNMPv2-SMICounter64 Textual Convention: SNMPv2-SMICounter64 Unsigned64Type Constraints: range: 0..18446744073709551615 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.9 |
cpiPduBranchAlertTable
table.1.3.6.1.4.1.30932.1.10.1.3.210
·
1 row entry
·
12 columns
This table contains a list of PDU branch alert entries that are
being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row
in the table represents a PDU branch in the daisy chain.
The table is indexed based on the corresponding Branch ID and the
source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'cpiPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
cpiPduBranchAlertIndex
| Column | Syntax | OID |
|---|---|---|
|
cpiPduBranchAlertMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.1 |
|
cpiPduBranchAlertBranchId
Get the branch ID on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.2 |
|
cpiPduBranchAlertWarnLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.3 |
|
cpiPduBranchAlertWarnHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.4 |
|
cpiPduBranchAlertLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.5 |
|
cpiPduBranchAlertHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.6 |
|
cpiPduBranchAlertCriticalCurrent
Set or get the critical current draw in 1/100 amp of the
branch on the PDU. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.7 |
|
cpiPduBranchAlertWarnLoVolt
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.8 |
|
cpiPduBranchAlertWarnHiVolt
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.9 |
|
cpiPduBranchAlertLoVolt
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.10 |
|
cpiPduBranchAlertHiVolt
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.11 |
|
cpiPduBranchAlertIndex
Index for branch alert.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.12 |
cpiPduOutletTable
table.1.3.6.1.4.1.30932.1.10.1.4.10
·
1 row entry
·
12 columns
This table contains a list of PDU outlet entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets on each PDU.
Each row in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU.
'cpiPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU.
Indexes
cpiPduOutletId cpiPduOutletMac
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
cpiPduOutletMac
Get the MAC address of the source PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.1 |
||||||
|
cpiPduOutletId
Get the ID of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.2 |
||||||
|
cpiPduOutletBranchId
Get the ID of the branch the outlet is associated with on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.3 |
||||||
|
cpiPduOutletName
Set or get the user supplied name of the outlet on the PDU.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.4 |
||||||
|
cpiPduOutletDescription
Set or get the user supplied description of the outlet on the PDU.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.5 |
||||||
|
cpiPduOutletCurrent
Get the current draw in 1/100 amp of the outlet on the PDU. Convert
the value by dividing by 100. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.6 |
||||||
|
cpiPduOutletVoltage
Get the voltage in 1/10 volts of the outlet on the PDU. Convert the
value by dividing by 10. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.7 |
||||||
|
cpiPduOutletPower
The power in Volt-Amps of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.8 |
||||||
|
cpiPduOutletStatus
Get the alarm status of the outlet.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.4.10.1.9 |
||||||
|
cpiPduOutletEnergy
Get the outlet energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.
|
SNMPv2-SMICounter64 Textual Convention: SNMPv2-SMICounter64 Unsigned64Type Constraints: range: 0..18446744073709551615 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.10 |
||||||
|
cpiPduOutletControl
Set or get power control to the outlet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.4.10.1.11 |
||||||
|
cpiPduOutletReset
Set or get reset power to the outlet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.4.10.1.12 |
cpiPduOutletConfigTable
table.1.3.6.1.4.1.30932.1.10.1.4.210
·
1 row entry
·
4 columns
This table contains a list of PDU outlet configuration entries
that are being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets per PDU. Each row
in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
uni…
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
uni…
Indexes
cpiPduOutletConfigOutletId cpiPduOutletConfigMac
| Column | Syntax | OID |
|---|---|---|
|
cpiPduOutletConfigMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.4.210.1.1 |
|
cpiPduOutletConfigOutletId
Get the ID of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.210.1.2 |
|
cpiPduOutletConfigOnDelay
Set or get the outlet power-on delay in seconds.
|
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.30932.1.10.1.4.210.1.3 |
|
cpiPduOutletConfigResetDelay
Set or get the outlet reset delay in seconds.
|
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.30932.1.10.1.4.210.1.4 |
cpiPduOutletAlertTable
table.1.3.6.1.4.1.30932.1.10.1.4.310
·
1 row entry
·
7 columns
This table contains a list of PDU outlet alert entries that are
being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets per PDU. Each row
in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and the
source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'cpiPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
cpiPduOutletAlertOutletId cpiPduOutletAlertMac
| Column | Syntax | OID |
|---|---|---|
|
cpiPduOutletAlertMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.1 |
|
cpiPduOutletAlertOutletId
Get the outlet ID on the PDU.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.2 |
|
cpiPduOutletAlertWarnLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.3 |
|
cpiPduOutletAlertWarnHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.4 |
|
cpiPduOutletAlertLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.5 |
|
cpiPduOutletAlertHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.6 |
|
cpiPduOutletAlertCriticalCurrent
Set or get the critical current draw in 1/100 amp of the
outlet on the PDU. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.7 |
cpiPduProbeTable
table.1.3.6.1.4.1.30932.1.10.1.5.5
·
1 row entry
·
3 columns
This table contains a list of PDU probes that are being monitored
by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of probes attached to the PDUs in
the daisy chain. Each row in the table represents a probe in the daisy chain.
The table is index based on the corresponding Probe ID and the source
PDU MAC.
This entry defines the columns to be populated in the
'cpiPduProbeTable'. Each column represents an attribute of a PDU probe.
This table is indexed by the PDU identifier that is unique
within the PDU and the probe ID.
'cpiPduProbeTable'. Each column represents an attribute of a PDU probe.
This table is indexed by the PDU identifier that is unique
within the PDU and the probe ID.
Indexes
cpiPduProbeId cpiPduProbeMac
| Column | Syntax | OID |
|---|---|---|
|
cpiPduProbeMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.5.5.1.1 |
|
cpiPduProbeId
Get the probe ID on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.5.1.2 |
|
cpiPduProbeName
Set or get the user defined name of the probe.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.5.5.1.3 |
cpiPduSensorTable
table.1.3.6.1.4.1.30932.1.10.1.5.10
·
1 row entry
·
5 columns
This table contains a list of PDU sensor entries that are being monitored
by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
The table is index based on the corresponding Sensor ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiPduSensorTable'.
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor …
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor …
Indexes
cpiPduSensorId cpiPduSensorMac
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
cpiPduSensorMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.5.10.1.1 |
||||
|
cpiPduSensorId
Get the sensor ID on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.10.1.2 |
||||
|
cpiPduSensorName
Set or get the user defined name of the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.5.10.1.3 |
||||
|
cpiPduSensorType
Get the type of sensor for the entry.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.5.10.1.4 |
||||
|
cpiPduSensorValue
Get the value of the sensor. For temperature the value is in degrees
Fahrenheit and for humidity the value is percent humidity. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.10.1.5 |
cpiPduSensorAlertTable
table.1.3.6.1.4.1.30932.1.10.1.5.110
·
1 row entry
·
6 columns
This table contains a list of PDU sensor alert entries that are
being monitored by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
The table is index based on the corresponding Sonsor ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiPduSensorAlertTable'.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU.
Indexes
cpiPduSensorAlertSensorId cpiPduSensorAlertMac
| Column | Syntax | OID |
|---|---|---|
|
cpiPduSensorAlertMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.1 |
|
cpiPduSensorAlertSensorId
Get the id of the sensor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.2 |
|
cpiPduSensorAlertWarnMin
Set or get the minimum warning value of the sensor.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.3 |
|
cpiPduSensorAlertWarnMax
Set or get the maximum warning value of the sensor.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.4 |
|
cpiPduSensorAlertMin
Set or get the minimum alarm value of the sensor.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.5 |
|
cpiPduSensorAlertMax
Set or get the maximum alarm value of the sensor.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.6 |
cpiGroupTable
table.1.3.6.1.4.1.30932.1.10.1.6.10
·
1 row entry
·
2 columns
This table contains a list of PDU group entries that are being monitored
by the PDU.
The table contains one, or many rows, depending upon the number
of groups that have been configured. Each row in the table represents a
group.
This entry defines the columns to be populated in the
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU.
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU.
Indexes
cpiGroupEntryIndex
| Column | Syntax | OID |
|---|---|---|
|
cpiGroupEntryIndex
This is the index that indicates the row of the 'cpiPduTable'.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.10.1.6.10.1.1 |
|
cpiGroupName
Name for GROUP 1 of receptacles.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.6.10.1.2 |
cpiGroupOutletTable
table.1.3.6.1.4.1.30932.1.10.1.6.20
·
1 row entry
·
4 columns
This table contains a list of PDU group entries. The table contains zero, one, or many rows, depending upon the number of groups that have been configured. Each row in the table represents a group.
This entry defines the columns to be populated in the
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU.
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU.
Indexes
cpiGroupOutletEntryIndex
| Column | Syntax | OID |
|---|---|---|
|
cpiGroupOutletEntryIndex
This is the index that indicates the row of the 'cpiGroupOutletTable'.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.10.1.6.20.1.1 |
|
cpiGroupOutletGroupID
Name for GROUP 1 of receptacles.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.10.1.6.20.1.2 |
|
cpiGroupOutletPDUMac
MAC of PDU the outlet is on.
|
SNMPv2-TCMacAddressr/w Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.6.20.1.3 |
|
cpiGroupOutletOutletId
The ID of the outlet on the PDU.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.6.20.1.4 |
cpiEasConfigTable
table.1.3.6.1.4.1.30932.1.10.1.7.90
·
1 row entry
·
6 columns
This table contains a list of electronic locks that are connected to the PDU
and allows for the configuration of the various settings associated with the
EAS (electronic access system).
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
The table is index based on the corresponding lock ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
cpiEasConfigLockMac
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
cpiEasConfigLockMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.7.90.1.1 |
||||
|
cpiEasConfigEnabled
Indicates whether the Electronic Access System (EAS) is available on the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.90.1.2 |
||||
|
cpiEasFrontLockEnabled
Enables the front lock on the EAS.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.90.1.3 |
||||
|
cpiEasRearLockEnabled
Enables the rear lock on the EAS.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.90.1.4 |
||||
|
cpiEasLockHoldOpenTime
The length of time in seconds to hold open the lock after a successful card scan.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.7.90.1.5 |
||||
|
cpiEasDoorOpenAlarmTime
The length of time in minutes before alerting that the door is open.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.7.90.1.6 |
cpiEasTable
table.1.3.6.1.4.1.30932.1.10.1.7.100
·
1 row entry
·
11 columns
This table contains a list of electronic locks that are connected to the PDU
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
The table is index based on the corresponding lock ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
cpiPduLockId cpiPduLockMac
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
cpiPduLockMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.10.1.7.100.1.1 |
||||||
|
cpiPduLockId
Get the lock ID on the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.2 |
||||||
|
cpiPduEasStatus
Indicates if the Electronic Access Control system is ready, inactive, or in an error state.
If the status is Inactive, then the lock is not enabled on the PDU. If the status is Error, then the cpiEasError… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.3 |
||||||
|
cpiPduDoorStatus
Indicates if the door sensor is closed or open.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.4 |
||||||
|
cpiPduLockStatus
Indicates if the lock is closed or open.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.5 |
||||||
|
cpiPduForceStatus
Indicates if the cabinet was forced open by a command from the webUI or SNMP interfaces.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.6 |
||||||
|
cpiPduTamperStatus
Indicates if the cabinet is currently unlocked/opened without an authorization scan.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.7 |
||||||
|
cpiEasError
Gets the error code associated for the electronic lock system. The possible error codes are:
196608 (0x00030000 ) - No error, the lock is working and ready. 167968771 (0x0a030003 ) - The lock is not enabl… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.10.1.7.100.1.8 |
||||||
|
cpiEasLockVer
Gets the version of the electronic lock control.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.7.100.1.9 |
||||||
|
cpiEasLockSerialNumber
Get the serial number of the electronic lock control.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.10.1.7.100.1.10 |
||||||
|
cpiPduLockCtrl
Tells the system to open the locks on the cabinet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.11 |
saIpv4Table
table.1.3.6.1.4.1.30932.1.20.5.5.11
·
1 row entry
·
11 columns
This table contains a list of PDU IPv4 entries that are attached through
the SecureArray connection.
The Row ID field is used as an index on the table. The Row ID is not
guaranteed to be the same PDU from one instance in time to another. It
is recommended to utilize the MAC address as a universally unique ID.
This entry defines the columns to be populated in the
'saIpv4Table'. Each column represents an attribute of a PDU.
'saIpv4Table'. Each column represents an attribute of a PDU.
Indexes
saIpv4RowId
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
saIpv4RowId
The Row ID of the PDU.
|
Integer32 Constraints: range: 1-48 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.1 |
||||
|
saIpv4PduMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.2 |
||||
|
saIpV4Enable
Controls whether the IPv4 network interface is enabled.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.5.5.11.1.3 |
||||
|
saIpv4PduIP
Set or get the IPv4 address of the PDU.
|
SNMPv2-SMIIpAddressr/w Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.4 |
||||
|
saAutoIP
Controls whether the IPv4 address is retrieved from a
DHCP server or is set statically. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.5.5.11.1.5 |
||||
|
saAutoDNS
Controls whether the DNS addresses are retrieved from
a DHCP server or are set statically. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.5.5.11.1.6 |
||||
|
saSubnetMask
The subnet mask associated with the IPv4 address of this
entry. The value of the mask is an IPv4 address with all the network bits set to 1 and all the hosts bits set to 0. |
SNMPv2-SMIIpAddressr/w Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.7 |
||||
|
saGateway
Set or get the IPv4 address of the gateway router for the PDU.
|
SNMPv2-SMIIpAddressr/w Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.8 |
||||
|
saDns1
Set or get the IPv4 address of the first DNS entry for the PDU.
|
SNMPv2-SMIIpAddressr/w Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.9 |
||||
|
saDns2
Set or get the IPv4 address of the second DNS entry for the PDU.
|
SNMPv2-SMIIpAddressr/w Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.10 |
||||
|
saDns3
Set or get the IPv4 address of the third DNS entry for the PDU.
|
SNMPv2-SMIIpAddressr/w Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.11 |
saPduTable
table.1.3.6.1.4.1.30932.1.20.10.11
·
1 row entry
·
19 columns
This table contains a list of PDU entries that are attached through
the SecureArray connection.
The table contains one, or many rows, depending upon the
number of PDUs being monitored. Each row in the table represents a PDU
in the SecureArray.
This table always contains at least one entry and a maximum of 48 entries.
The Row ID field is used as an index on the table. The Row ID is not
guaranteed to be the same PDU from one instance in time to another. It
is recommended to utilize the MAC address as a universally unique ID.
This entry defines the columns to be populated in the
'saPduTable'. Each column represents an attribute of a PDU.
'saPduTable'. Each column represents an attribute of a PDU.
Indexes
saPduRowId
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
saPduRowId
The Row ID of the PDU.
|
Integer32 Constraints: range: 1-48 |
.1.3.6.1.4.1.30932.1.20.10.11.1.1 |
||||||
|
saPduMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.10.11.1.2 |
||||||
|
saPduModel
Get the model number of the PDU.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.10.11.1.3 |
||||||
|
saPduName
Set or get the user assigned name of the PDU.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.10.11.1.4 |
||||||
|
saPduDescription
Set or get the user assigned description of the PDU.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.10.11.1.5 |
||||||
|
saPduHasBranchMonitor
An indicator if the PDU supports monitoring voltage, and current on branches in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.6 |
||||||
|
saPduHasOutletMonitor
An indicator if the PDU supports monitoring current on the individual outlets in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.7 |
||||||
|
saPduHasOutletControl
An indicator if the PDU supports control (turn on/off) individual outlets in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.8 |
||||||
|
saPduNumberBranches
Get the number of branches (breakers) in the PDU.
|
Integer32 Constraints: range: 0-12 |
.1.3.6.1.4.1.30932.1.20.10.11.1.9 |
||||||
|
saPduNumberOutlets
Get the number of outlets in the PDU.
|
Integer32 Constraints: range: 0-48 |
.1.3.6.1.4.1.30932.1.20.10.11.1.10 |
||||||
|
saPduOutOfService
Set or get whether the PDU is in-service.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.11 |
||||||
|
saPduVersion
Get the firmware version number of the PDU.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.10.11.1.12 |
||||||
|
saPduUpgrade
An indicator if the PDU firmware is being upgraded.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.13 |
||||||
|
saPduChainRole
Get the role of the PDU in a SecureArray.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.14 |
||||||
|
saPduIp
Get IP address of the PDU.
|
SNMPv2-SMIIpAddress Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.10.11.1.15 |
||||||
|
saPduIpv6
Get the IPv6 address of the PDU.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.10.11.1.16 |
||||||
|
saPduTotalPower
Get the power in volt-amps for the entire PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.10.11.1.17 |
||||||
|
saPduCabinetId
Get/set the name of the cabinet the PDU is in.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.10.11.1.18 |
||||||
|
saPduSerialNum
Get the serial number of the PDU.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.10.11.1.19 |
saPduLineTable
table.1.3.6.1.4.1.30932.1.20.15.11
·
1 row entry
·
5 columns
This table contains a list of PDU line entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of input lines. Each row
in the table represents a PDU line in the SecureArray.
The table is indexed based on the corresponding Line Row ID.
This entry defines the columns to be populated in the
'saPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'saPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
saPduLineRowId
| Column | Syntax | OID |
|---|---|---|
|
saPduLineRowId
Get the ID of the input line on the PDU.
|
Integer32 Constraints: range: 0-512 |
.1.3.6.1.4.1.30932.1.20.15.11.1.1 |
|
saPduLineId
Get the ID of the input line on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.15.11.1.2 |
|
saPduLineMac
Get the MAC address of the PDU that owns the input line.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.15.11.1.3 |
|
saPduLinePduName
Get the MAC address of the PDU that owns the input line.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.15.11.1.4 |
|
saPduLineCurrent
Get current draw in 1/100 amp of the line on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.15.11.1.5 |
saPduBranchTable
table.1.3.6.1.4.1.30932.1.20.20.11
·
1 row entry
·
11 columns
This table contains a list of PDU branch entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row
in the table represents a PDU branch in the daisy chain.
The table is indexed based on the corresponding Branch ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'saPduBranchEntry'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'saPduBranchEntry'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
saPduBranchRowId
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
saPduBranchRowId
Get the Row ID of the branch on the owning PDU.
|
Integer32 Constraints: range: 0-768 |
.1.3.6.1.4.1.30932.1.20.20.11.1.1 |
||||||
|
saPduBranchId
Get the ID of the branch on the owning PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.2 |
||||||
|
saPduBranchMac
Get the MAC address of the PDU that owns the branch.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.20.11.1.3 |
||||||
|
saPduBranchPduName
Get the MAC address of the PDU that owns the input line.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.20.11.1.4 |
||||||
|
saPduBranchCurrent
Get the current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.5 |
||||||
|
saPduBranchMaxCurrent
Get the maximum current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.6 |
||||||
|
saPduBranchVoltage
Get the voltage in 1/10 volts of the branch on the PDU. Convert the value by dividing by 10.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.7 |
||||||
|
saPduBranchPower
Get the power in volt-amps for the branch.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.8 |
||||||
|
saPduBranchPowerFactor
Get the power factor for the branch.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.9 |
||||||
|
saPduBranchStatus
Get the alarm status of the branch.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.20.11.1.10 |
||||||
|
saPduBranchEnergy
Get the branch energy accumulated in decaVA-secs, divide by 360 to obtain VA-hr.
|
SNMPv2-SMICounter64 Textual Convention: SNMPv2-SMICounter64 Unsigned64Type Constraints: range: 0..18446744073709551615 |
.1.3.6.1.4.1.30932.1.20.20.11.1.11 |
saPduBranchAlertTable
table.1.3.6.1.4.1.30932.1.20.20.12
·
1 row entry
·
13 columns
This table contains a list of PDU branch alert entries that are
being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row
in the table represents a PDU branch in the daisy chain.
The table is indexed based on the corresponding Branch ID and the
source PDU MAC.
This entry defines the columns to be populated in the
'saPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'saPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
saPduBranchAlertRowId
| Column | Syntax | OID |
|---|---|---|
|
saPduBranchAlertRowId
Get the Row ID of the branch on the owning PDU.
|
Integer32 Constraints: range: 0-768 |
.1.3.6.1.4.1.30932.1.20.20.12.1.1 |
|
saPduBranchAlertMac
Get the MAC address of the PDU that owns the branch.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.20.12.1.2 |
|
saPduBranchAlertPduName
Get the MAC address of the PDU that owns the input line.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.20.12.1.3 |
|
saPduBranchAlertBranchId
Get the branch of the owning PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.4 |
|
saPduBranchAlertWarnLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.5 |
|
saPduBranchAlertWarnHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.6 |
|
saPduBranchAlertLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.7 |
|
saPduBranchAlertHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.8 |
|
saPduBranchAlertCriticalCurrent
Set or get the critical current draw in 1/100 amp of the
branch on the PDU. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.9 |
|
saPduBranchAlertWarnLoVolt
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.10 |
|
saPduBranchAlertWarnHiVolt
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.11 |
|
saPduBranchAlertLoVolt
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.12 |
|
saPduBranchAlertHiVolt
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.13 |
saPduOutletTable
table.1.3.6.1.4.1.30932.1.20.25.11
·
1 row entry
·
13 columns
This table contains a list of PDU outlet entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets on each PDU.
Each row in the table represents a PDU outlet in the SecureArray.
This entry defines the columns to be populated in the
'saPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU.
'saPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU.
Indexes
saPduOutletRowId
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
saPduOutletRowId
Get the ID of the outlet on the PDU.
|
Integer32 Constraints: range: 1-4096 |
.1.3.6.1.4.1.30932.1.20.25.11.1.1 |
||||||
|
saPduOutletMac
Get the MAC address of the source PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.25.11.1.2 |
||||||
|
saPduOutletId
Get the ID of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.11.1.3 |
||||||
|
saPduOutletBranchId
Get the ID of the branch the outlet is associated with on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.11.1.4 |
||||||
|
saPduOutletName
Set or get the user supplied name of the outlet on the PDU.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.25.11.1.5 |
||||||
|
saPduOutletDescription
Set or get the user supplied description of the outlet on the PDU.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.25.11.1.6 |
||||||
|
saPduOutletCurrent
Get the current draw in 1/100 amp of the outlet on the PDU. Convert
the value by dividing by 100. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.11.1.7 |
||||||
|
saPduOutletVoltage
Get the voltage in 1/10 volts of the outlet on the PDU. Convert the
value by dividing by 10. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.11.1.8 |
||||||
|
saPduOutletPower
The power in Volt-Amps of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.11.1.9 |
||||||
|
saPduOutletStatus
Get the alarm status of the outlet.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.25.11.1.10 |
||||||
|
saPduOutletEnergy
Get the outlet energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.
|
SNMPv2-SMICounter64 Textual Convention: SNMPv2-SMICounter64 Unsigned64Type Constraints: range: 0..18446744073709551615 |
.1.3.6.1.4.1.30932.1.20.25.11.1.11 |
||||||
|
saPduOutletControl
Set or get power control to the outlet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.25.11.1.12 |
||||||
|
saPduOutletReset
Set or get reset power to the outlet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.25.11.1.13 |
saPduOutletConfigTable
table.1.3.6.1.4.1.30932.1.20.25.20
·
1 row entry
·
5 columns
This table contains a list of PDU outlet configuration entries
that are being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets per PDU. Each row
in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
uni…
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
uni…
Indexes
saPduOutletConfigOutletRowId
| Column | Syntax | OID |
|---|---|---|
|
saPduOutletConfigOutletRowId
Get the ID of the outlet on the PDU.
|
Integer32 Constraints: range: 1-4096 |
.1.3.6.1.4.1.30932.1.20.25.20.1.1 |
|
saPduOutletConfigMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.25.20.1.2 |
|
saPduOutletConfigOutletId
Get the ID of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.20.1.3 |
|
saPduOutletConfigOnDelay
Set or get the outlet power-on delay in seconds.
|
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.30932.1.20.25.20.1.4 |
|
saPduOutletConfigResetDelay
Set or get the outlet reset delay in seconds.
|
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.30932.1.20.25.20.1.5 |
saPduOutletAlertTable
table.1.3.6.1.4.1.30932.1.20.25.30
·
1 row entry
·
8 columns
This table contains a list of PDU outlet alert entries that are
being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets per PDU. Each row
in the table represents a PDU outlet in the daisy chain.
This entry defines the columns to be populated in the
'saPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'saPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
saPduOutletAlertOutletRowId
| Column | Syntax | OID |
|---|---|---|
|
saPduOutletAlertOutletRowId
Get the outlet ID on the PDU.
|
Integer32 Constraints: range: 1-4096 |
.1.3.6.1.4.1.30932.1.20.25.30.1.1 |
|
saPduOutletAlertMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.25.30.1.2 |
|
saPduOutletAlertOutletId
Get the outlet ID on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.3 |
|
saPduOutletAlertWarnLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.4 |
|
saPduOutletAlertWarnHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.5 |
|
saPduOutletAlertLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.6 |
|
saPduOutletAlertHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.7 |
|
saPduOutletAlertCriticalCurrent
Set or get the critical current draw in 1/100 amp of the
outlet on the PDU. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.8 |
saPduSensorTable
table.1.3.6.1.4.1.30932.1.20.30.10
·
1 row entry
·
6 columns
This table contains a list of PDU sensor entries that are being monitored
by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
This entry defines the columns to be populated in the 'saPduSensorTable'.
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor I…
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor I…
Indexes
saPduSensorRowId
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
saPduSensorRowId
Get the sensor ID on the PDU.
|
Integer32 Constraints: range: 1-8192 |
.1.3.6.1.4.1.30932.1.20.30.10.1.1 |
||||
|
saPduSensorMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.30.10.1.2 |
||||
|
saPduSensorId
Get the sensor ID on the PDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.10.1.3 |
||||
|
saPduSensorName
Set or get the user defined name of the sensor.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.30.10.1.4 |
||||
|
saPduSensorType
Get the type of sensor for the entry.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.30.10.1.5 |
||||
|
saPduSensorValue
Get the value of the sensor. For temperature the value is in degrees
Fahrenheit and for humidity the value is percent humidity. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.10.1.6 |
saPduSensorAlertTable
table.1.3.6.1.4.1.30932.1.20.30.20
·
1 row entry
·
7 columns
This table contains a list of PDU sensor alert entries that are
being monitored by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
This entry defines the columns to be populated in the 'cpiPduSensorAlertTable'.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU.
Indexes
saPduSensorAlertSensorRowId
| Column | Syntax | OID |
|---|---|---|
|
saPduSensorAlertSensorRowId
Get the id of the sensor.
|
Integer32 Constraints: range: 1-4096 |
.1.3.6.1.4.1.30932.1.20.30.20.1.1 |
|
saPduSensorAlertMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.30.20.1.2 |
|
saPduSensorAlertSensorId
Get the id of the sensor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.20.1.3 |
|
saPduSensorAlertWarnMin
Set or get the minimum warning value of the sensor.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.20.1.4 |
|
saPduSensorAlertWarnMax
Set or get the maximum warning value of the sensor.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.20.1.5 |
|
saPduSensorAlertMin
Set or get the minimum alarm value of the sensor.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.20.1.6 |
|
saPduSensorAlertMax
Set or get the maximum alarm value of the sensor.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.20.1.7 |
saEasConfigTable
table.1.3.6.1.4.1.30932.1.20.40.20
·
1 row entry
·
7 columns
This table contains a list of electronic locks that are connected to the PDU
and allows for the configuration of the various settings associated with the
EAS (electronic access system).
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
The table is index based on the corresponding lock ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
saEasConfigLockRowId
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
saEasConfigLockRowId
Get the MAC address of the PDU.
|
Integer32 Constraints: range: 1-128 |
.1.3.6.1.4.1.30932.1.20.40.20.1.1 |
||||
|
saEasConfigLockMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.40.20.1.2 |
||||
|
saEasConfigEnabled
Indicates whether the Electronic Access System (EAS) is available on the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.20.1.3 |
||||
|
saEasFrontLockEnabled
Enables the front lock on the EAS.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.20.1.4 |
||||
|
saEasRearLockEnabled
Enables the rear lock on the EAS.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.20.1.5 |
||||
|
saEasLockHoldOpenTime
The length of time in seconds to hold open the lock after a successful card scan.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.40.20.1.6 |
||||
|
saEasDoorOpenAlarmTime
The length of time in minutes before alerting that the door is open.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.40.20.1.7 |
saEasTable
table.1.3.6.1.4.1.30932.1.20.40.30
·
1 row entry
·
12 columns
This table contains a list of electronic locks that are connected to the PDU
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
The table is index based on the corresponding lock ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
saPduLockRowId
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
saPduLockRowId
Get the lock ID on the PDU.
|
Integer32 Constraints: range: 0-128 |
.1.3.6.1.4.1.30932.1.20.40.30.1.1 |
||||||
|
saPduLockMac
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Textual Convention: SNMPv2-TCMacAddress OctetStringType Constraints: range: 6 |
.1.3.6.1.4.1.30932.1.20.40.30.1.2 |
||||||
|
saPduLockId
Get the lock ID on the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.3 |
||||||
|
saPduEasStatus
Indicates if the Electronic Access Control system is ready, inactive, or in an error state.
If the status is Inactive, then the lock is not enabled on the PDU. If the status is Error, then the cpiEasError… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.4 |
||||||
|
saPduDoorStatus
Indicates if the door sensor is closed or open.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.5 |
||||||
|
saPduLockStatus
Indicates if the lock is closed or open.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.6 |
||||||
|
saPduForceStatus
Indicates if the cabinet was forced open by a command from the webUI or SNMP interfaces.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.7 |
||||||
|
saPduTamperStatus
Indicates if the cabinet is currently unlocked/opened without an authorization scan.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.8 |
||||||
|
saEasError
Gets the error code associated for the electronic lock system. The possible error codes are:
196608 (0x00030000 ) - No error, the lock is working and ready. 167968771 (0x0a030003 ) - The lock is not enabl… |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.20.40.30.1.9 |
||||||
|
saEasLockVer
Gets the version of the electronic lock control.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.40.30.1.10 |
||||||
|
saEasLockSerialNumber
Get the serial number of the electronic lock control.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.30932.1.20.40.30.1.11 |
||||||
|
saPduLockCtrl
Tells the system to open the locks on the cabinet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.12 |