CPI-UNIFIED-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
26
Rows
26
Columns
219
.1.3.6.1.4.1.30932.1.10.1.2.10 · 1 row entry · 18 columns
This table contains a list of PDU entries that are being monitored
by the PDU. 
          
The table contains one, or many rows, depending upon the 
number of PDUs being monitored. Each row in the table represents a PDU 
in the daisy chain.
          
This table always contains at least one entry and a maximum of 32 entries.
The MAC address is used as an index on the table to allow data collectors
to ensure that information can be retrieved for a specific PDU.
cpiPduEntry entry .1.3.6.1.4.1.30932.1.10.1.2.10.1
This entry defines the columns to be populated in the
'cpiPduTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU MAC that is globally unique.
Indexes
cpiPduMac
Column Syntax OID
cpiPduMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.2.10.1.1
cpiPduModel
Get the model number of the PDU.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.2.10.1.2
cpiPduName
Set or get the user assigned name of the PDU.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.2.10.1.3
cpiPduDescription
Set or get the user assigned description of the PDU.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.2.10.1.4
cpiPduHasBranchMonitor
An indicator if the PDU supports monitoring voltage, and current on branches in the PDU.
Enumeration
Enumerated Values:
0notsupported
1supported
.1.3.6.1.4.1.30932.1.10.1.2.10.1.5
cpiPduHasOutletMonitor
An indicator if the PDU supports monitoring current on the individual outlets in the PDU.
Enumeration
Enumerated Values:
0notsupported
1supported
.1.3.6.1.4.1.30932.1.10.1.2.10.1.6
cpiPduHasOutletControl
An indicator if the PDU supports control (turn on/off) individual outlets in the PDU.
Enumeration
Enumerated Values:
0notsupported
1supported
.1.3.6.1.4.1.30932.1.10.1.2.10.1.7
cpiPduNumberBranches
Get the number of branches (breakers) in the PDU.
Integer32
Constraints:
range: 0-12
.1.3.6.1.4.1.30932.1.10.1.2.10.1.8
cpiPduNumberOutlets
Get the number of outlets in the PDU.
Integer32
Constraints:
range: 0-72
.1.3.6.1.4.1.30932.1.10.1.2.10.1.9
cpiPduOutOfService
Set or get whether the PDU is in-service.
Enumerationr/w
Enumerated Values:
0inservice
1outofservice
.1.3.6.1.4.1.30932.1.10.1.2.10.1.10
cpiPduVersion
Get the firmware version number of the PDU.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.2.10.1.11
cpiPduUpgrade
An indicator if the PDU firmware is being upgraded.
Enumeration
Enumerated Values:
0no
1yes
.1.3.6.1.4.1.30932.1.10.1.2.10.1.12
cpiPduChainRole
Get the role of the PDU in a daisy chain.
Enumerationr/w
Enumerated Values:
0secondary
1primary
2alternate
.1.3.6.1.4.1.30932.1.10.1.2.10.1.13
cpiPduIp
Get IP address of the PDU.
SNMPv2-SMIIpAddress
Textual Convention: SNMPv2-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.30932.1.10.1.2.10.1.14
cpiPduIpv6
Get the IPv6 address of the PDU.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.2.10.1.15
cpiPduTotalPower
Get the power in volt-amps for the entire PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.2.10.1.16
cpiPduCabinetId
Get/set the name of the cabinet the PDU is in.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.2.10.1.17
cpiPduSerialNum
Get the serial number of the PDU.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.2.10.1.18
.1.3.6.1.4.1.30932.1.10.1.3.10 · 1 row entry · 3 columns
This table contains a list of PDU line entries that are being
monitored by the PDU.
          
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of input lines. Each row 
in the table represents a PDU line in the daisy chain.
          
The table is indexed based on the corresponding Line Input ID and
the source PDU MAC.
cpiPduLineEntry entry .1.3.6.1.4.1.30932.1.10.1.3.10.1
This entry defines the columns to be populated in the
'cpiPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
cpiPduLineId cpiPduLineMac
Column Syntax OID
cpiPduLineMac
Get the MAC address of the PDU that owns the input line.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.3.10.1.1
cpiPduLineId
Get the ID of the input line on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.10.1.2
cpiPduLineCurrent
Get current draw in 1/100 amp of the line on the PDU. Convert the value by dividing by 100.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.10.1.3
.1.3.6.1.4.1.30932.1.10.1.3.110 · 1 row entry · 9 columns
This table contains a list of PDU branch entries that are being
monitored by the PDU.
          
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row 
in the table represents a PDU branch in the daisy chain.
          
The table is indexed based on the corresponding Branch ID and
the source PDU MAC.
cpiPduBranchEntry entry .1.3.6.1.4.1.30932.1.10.1.3.110.1
This entry defines the columns to be populated in the
'cpiPduBranchTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
cpiPduBranchId cpiPduBranchMac
Column Syntax OID
cpiPduBranchMac
Get the MAC address of the PDU that owns the branch.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.3.110.1.1
cpiPduBranchId
Get the ID of the branch on the owning PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.110.1.2
cpiPduBranchCurrent
Get the current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.110.1.3
cpiPduBranchMaxCurrent
Get the maximum current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.110.1.4
cpiPduBranchVoltage
Get the voltage in 1/10 volts of the branch on the PDU. Convert the value by dividing by 10.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.110.1.5
cpiPduBranchPower
Get the power in volt-amps for the branch.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.110.1.6
cpiPduBranchPowerFactor
Get the power factor for the branch.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.110.1.7
cpiPduBranchStatus
Get the alarm status of the branch.
Enumeration
Enumerated Values:
0noalarm
1warning
2alarm
.1.3.6.1.4.1.30932.1.10.1.3.110.1.8
cpiPduBranchEnergy
Get the branch energy accumulated in decaVA-secs, divide by 360 to obtain VA-hr.
SNMPv2-SMICounter64
Textual Convention: SNMPv2-SMICounter64 Unsigned64
Type Constraints:
range: 0..18446744073709551615
.1.3.6.1.4.1.30932.1.10.1.3.110.1.9
.1.3.6.1.4.1.30932.1.10.1.3.210 · 1 row entry · 12 columns
This table contains a list of PDU branch alert entries that are
being monitored by the PDU.
          
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row 
in the table represents a PDU branch in the daisy chain.
          
The table is indexed based on the corresponding Branch ID and the
source PDU MAC.
cpiPduBranchAlertEntry entry .1.3.6.1.4.1.30932.1.10.1.3.210.1
This entry defines the columns to be populated in the
'cpiPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
cpiPduBranchAlertIndex
Column Syntax OID
cpiPduBranchAlertMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.3.210.1.1
cpiPduBranchAlertBranchId
Get the branch ID on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.210.1.2
cpiPduBranchAlertWarnLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.210.1.3
cpiPduBranchAlertWarnHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.210.1.4
cpiPduBranchAlertLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.210.1.5
cpiPduBranchAlertHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.210.1.6
cpiPduBranchAlertCriticalCurrent
Set or get the critical current draw in 1/100 amp of the
branch on the PDU. Convert the value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.210.1.7
cpiPduBranchAlertWarnLoVolt
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.210.1.8
cpiPduBranchAlertWarnHiVolt
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.210.1.9
cpiPduBranchAlertLoVolt
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.210.1.10
cpiPduBranchAlertHiVolt
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.3.210.1.11
cpiPduBranchAlertIndex
Index for branch alert.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.30932.1.10.1.3.210.1.12
.1.3.6.1.4.1.30932.1.10.1.4.10 · 1 row entry · 12 columns
This table contains a list of PDU outlet entries that are being
monitored by the PDU.
          
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets on each PDU. 
Each row in the table represents a PDU outlet in the daisy chain.
          
The table is indexed based on the corresponding Outlet ID and
the source PDU MAC.
cpiPduOutletEntry entry .1.3.6.1.4.1.30932.1.10.1.4.10.1
This entry defines the columns to be populated in the
'cpiPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU.
Indexes
cpiPduOutletId cpiPduOutletMac
Column Syntax OID
cpiPduOutletMac
Get the MAC address of the source PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.4.10.1.1
cpiPduOutletId
Get the ID of the outlet on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.10.1.2
cpiPduOutletBranchId
Get the ID of the branch the outlet is associated with on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.10.1.3
cpiPduOutletName
Set or get the user supplied name of the outlet on the PDU.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.4.10.1.4
cpiPduOutletDescription
Set or get the user supplied description of the outlet on the PDU.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.4.10.1.5
cpiPduOutletCurrent
Get the current draw in 1/100 amp of the outlet on the PDU. Convert
the value by dividing by 100.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.10.1.6
cpiPduOutletVoltage
Get the voltage in 1/10 volts of the outlet on the PDU. Convert the
value by dividing by 10.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.10.1.7
cpiPduOutletPower
The power in Volt-Amps of the outlet on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.10.1.8
cpiPduOutletStatus
Get the alarm status of the outlet.
Enumeration
Enumerated Values:
0noalarm
1warning
2alarm
.1.3.6.1.4.1.30932.1.10.1.4.10.1.9
cpiPduOutletEnergy
Get the outlet energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.
SNMPv2-SMICounter64
Textual Convention: SNMPv2-SMICounter64 Unsigned64
Type Constraints:
range: 0..18446744073709551615
.1.3.6.1.4.1.30932.1.10.1.4.10.1.10
cpiPduOutletControl
Set or get power control to the outlet.
Enumerationr/w
Enumerated Values:
0off
1on
.1.3.6.1.4.1.30932.1.10.1.4.10.1.11
cpiPduOutletReset
Set or get reset power to the outlet.
Enumerationr/w
Enumerated Values:
0nominal
1reset
.1.3.6.1.4.1.30932.1.10.1.4.10.1.12
.1.3.6.1.4.1.30932.1.10.1.4.210 · 1 row entry · 4 columns
This table contains a list of PDU outlet configuration entries
that are being monitored by the PDU.
          
 The table contains one, or many rows, depending upon the number
 of PDUs being monitored and the number of outlets per PDU. Each row 
 in the table represents a PDU outlet in the daisy chain.
           
 The table is indexed based on the corresponding Outlet ID and
 the source PDU MAC.
cpiPduOutletConfigEntry entry .1.3.6.1.4.1.30932.1.10.1.4.210.1
This entry defines the columns to be populated in the
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
uni…
Indexes
cpiPduOutletConfigOutletId cpiPduOutletConfigMac
Column Syntax OID
cpiPduOutletConfigMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.4.210.1.1
cpiPduOutletConfigOutletId
Get the ID of the outlet on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.210.1.2
cpiPduOutletConfigOnDelay
Set or get the outlet power-on delay in seconds.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.30932.1.10.1.4.210.1.3
cpiPduOutletConfigResetDelay
Set or get the outlet reset delay in seconds.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.30932.1.10.1.4.210.1.4
.1.3.6.1.4.1.30932.1.10.1.4.310 · 1 row entry · 7 columns
This table contains a list of PDU outlet alert entries that are
being monitored by the PDU.
          
 The table contains one, or many rows, depending upon the number
 of PDUs being monitored and the number of outlets per PDU. Each row 
 in the table represents a PDU outlet in the daisy chain.
           
 The table is indexed based on the corresponding Outlet ID and the
 source PDU MAC.
cpiPduOutletAlertEntry entry .1.3.6.1.4.1.30932.1.10.1.4.310.1
This entry defines the columns to be populated in the
'cpiPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
cpiPduOutletAlertOutletId cpiPduOutletAlertMac
Column Syntax OID
cpiPduOutletAlertMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.4.310.1.1
cpiPduOutletAlertOutletId
Get the outlet ID on the PDU.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.4.310.1.2
cpiPduOutletAlertWarnLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.310.1.3
cpiPduOutletAlertWarnHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.310.1.4
cpiPduOutletAlertLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.310.1.5
cpiPduOutletAlertHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.310.1.6
cpiPduOutletAlertCriticalCurrent
Set or get the critical current draw in 1/100 amp of the
outlet on the PDU. Convert the value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.4.310.1.7
.1.3.6.1.4.1.30932.1.10.1.5.5 · 1 row entry · 3 columns
This table contains a list of PDU probes that are being monitored
by the PDU.
          
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of probes attached to the PDUs in
the daisy chain. Each row in the table represents a probe in the daisy chain.
          
The table is index based on the corresponding Probe ID and the source
PDU MAC.
cpiPduProbeEntry entry .1.3.6.1.4.1.30932.1.10.1.5.5.1
This entry defines the columns to be populated in the
'cpiPduProbeTable'. Each column represents an attribute of a PDU probe.
This table is indexed by the PDU identifier that is unique
within the PDU and the probe ID.
Indexes
cpiPduProbeId cpiPduProbeMac
Column Syntax OID
cpiPduProbeMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.5.5.1.1
cpiPduProbeId
Get the probe ID on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.5.5.1.2
cpiPduProbeName
Set or get the user defined name of the probe.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.5.5.1.3
.1.3.6.1.4.1.30932.1.10.1.5.10 · 1 row entry · 5 columns
This table contains a list of PDU sensor entries that are being monitored
by the PDU.
          
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
          
The table is index based on the corresponding Sensor ID and the source
PDU MAC.
cpiPduSensorEntry entry .1.3.6.1.4.1.30932.1.10.1.5.10.1
This entry defines the columns to be populated in the 'cpiPduSensorTable'.
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor …
Indexes
cpiPduSensorId cpiPduSensorMac
Column Syntax OID
cpiPduSensorMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.5.10.1.1
cpiPduSensorId
Get the sensor ID on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.5.10.1.2
cpiPduSensorName
Set or get the user defined name of the sensor.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.5.10.1.3
cpiPduSensorType
Get the type of sensor for the entry.
Enumeration
Enumerated Values:
1temperature
2humidity
.1.3.6.1.4.1.30932.1.10.1.5.10.1.4
cpiPduSensorValue
Get the value of the sensor. For temperature the value is in degrees
Fahrenheit and for humidity the value is percent humidity.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.5.10.1.5
.1.3.6.1.4.1.30932.1.10.1.5.110 · 1 row entry · 6 columns
This table contains a list of PDU sensor alert entries that are
being monitored by the PDU.
          
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
          
The table is index based on the corresponding Sonsor ID and the source
PDU MAC.
cpiPduSensorAlertEntry entry .1.3.6.1.4.1.30932.1.10.1.5.110.1
This entry defines the columns to be populated in the 'cpiPduSensorAlertTable'.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU.
Indexes
cpiPduSensorAlertSensorId cpiPduSensorAlertMac
Column Syntax OID
cpiPduSensorAlertMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.5.110.1.1
cpiPduSensorAlertSensorId
Get the id of the sensor.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.5.110.1.2
cpiPduSensorAlertWarnMin
Set or get the minimum warning value of the sensor.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.5.110.1.3
cpiPduSensorAlertWarnMax
Set or get the maximum warning value of the sensor.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.5.110.1.4
cpiPduSensorAlertMin
Set or get the minimum alarm value of the sensor.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.5.110.1.5
cpiPduSensorAlertMax
Set or get the maximum alarm value of the sensor.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.5.110.1.6
.1.3.6.1.4.1.30932.1.10.1.6.10 · 1 row entry · 2 columns
This table contains a list of PDU group entries that are being monitored
by the PDU.
           
 The table contains one, or many rows, depending upon the number
 of groups that have been configured. Each row in the table represents a
 group.
cpiGroupEntry entry .1.3.6.1.4.1.30932.1.10.1.6.10.1
This entry defines the columns to be populated in the
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU.
Indexes
cpiGroupEntryIndex
Column Syntax OID
cpiGroupEntryIndex
This is the index that indicates the row of the 'cpiPduTable'.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.30932.1.10.1.6.10.1.1
cpiGroupName
Name for GROUP 1 of receptacles.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.6.10.1.2
.1.3.6.1.4.1.30932.1.10.1.6.20 · 1 row entry · 4 columns
This table contains a list of PDU group entries.
The table contains zero, one, or many rows, depending upon the number
of groups that have been configured. Each row in the table represents a
group.
cpiGroupOutletEntry entry .1.3.6.1.4.1.30932.1.10.1.6.20.1
This entry defines the columns to be populated in the
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU.
Indexes
cpiGroupOutletEntryIndex
Column Syntax OID
cpiGroupOutletEntryIndex
This is the index that indicates the row of the 'cpiGroupOutletTable'.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.30932.1.10.1.6.20.1.1
cpiGroupOutletGroupID
Name for GROUP 1 of receptacles.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.30932.1.10.1.6.20.1.2
cpiGroupOutletPDUMac
MAC of PDU the outlet is on.
SNMPv2-TCMacAddressr/w
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.6.20.1.3
cpiGroupOutletOutletId
The ID of the outlet on the PDU.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.6.20.1.4
.1.3.6.1.4.1.30932.1.10.1.7.90 · 1 row entry · 6 columns
This table contains a list of electronic locks that are connected to the PDU
and allows for the configuration of the various settings associated with the
EAS (electronic access system).
          
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
          
The table is index based on the corresponding lock ID and the source
PDU MAC.
cpiEasConfigEntry entry .1.3.6.1.4.1.30932.1.10.1.7.90.1
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
cpiEasConfigLockMac
Column Syntax OID
cpiEasConfigLockMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.7.90.1.1
cpiEasConfigEnabled
Indicates whether the Electronic Access System (EAS) is available on the PDU.
Enumeration
Enumerated Values:
0not-available
1available
.1.3.6.1.4.1.30932.1.10.1.7.90.1.2
cpiEasFrontLockEnabled
Enables the front lock on the EAS.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.30932.1.10.1.7.90.1.3
cpiEasRearLockEnabled
Enables the rear lock on the EAS.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.30932.1.10.1.7.90.1.4
cpiEasLockHoldOpenTime
The length of time in seconds to hold open the lock after a successful card scan.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.7.90.1.5
cpiEasDoorOpenAlarmTime
The length of time in minutes before alerting that the door is open.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.10.1.7.90.1.6
.1.3.6.1.4.1.30932.1.10.1.7.100 · 1 row entry · 11 columns
This table contains a list of electronic locks that are connected to the PDU
          
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
          
The table is index based on the corresponding lock ID and the source
PDU MAC.
cpiEasEntry entry .1.3.6.1.4.1.30932.1.10.1.7.100.1
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
cpiPduLockId cpiPduLockMac
Column Syntax OID
cpiPduLockMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.10.1.7.100.1.1
cpiPduLockId
Get the lock ID on the PDU.
Enumeration
Enumerated Values:
1front
2rear
.1.3.6.1.4.1.30932.1.10.1.7.100.1.2
cpiPduEasStatus
Indicates if the Electronic Access Control system is ready, inactive, or in an error state.

If the status is Inactive, then the lock is not enabled on the PDU.
If the status is Error, then the cpiEasError…
Enumeration
Enumerated Values:
0inactive
1ready
2error
.1.3.6.1.4.1.30932.1.10.1.7.100.1.3
cpiPduDoorStatus
Indicates if the door sensor is closed or open.
Enumeration
Enumerated Values:
0closed
1open
.1.3.6.1.4.1.30932.1.10.1.7.100.1.4
cpiPduLockStatus
Indicates if the lock is closed or open.
Enumeration
Enumerated Values:
0closed
1open
.1.3.6.1.4.1.30932.1.10.1.7.100.1.5
cpiPduForceStatus
Indicates if the cabinet was forced open by a command from the webUI or SNMP interfaces.
Enumeration
Enumerated Values:
0normal
1force
.1.3.6.1.4.1.30932.1.10.1.7.100.1.6
cpiPduTamperStatus
Indicates if the cabinet is currently unlocked/opened without an authorization scan.
Enumeration
Enumerated Values:
0normal
1tamper
.1.3.6.1.4.1.30932.1.10.1.7.100.1.7
cpiEasError
Gets the error code associated for the electronic lock system. The possible error codes are:

196608 (0x00030000
) - No error, the lock is working and ready.
167968771 (0x0a030003
) - The lock is not enabl…
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.30932.1.10.1.7.100.1.8
cpiEasLockVer
Gets the version of the electronic lock control.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.7.100.1.9
cpiEasLockSerialNumber
Get the serial number of the electronic lock control.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.10.1.7.100.1.10
cpiPduLockCtrl
Tells the system to open the locks on the cabinet.
Enumerationr/w
Enumerated Values:
0close
1open
.1.3.6.1.4.1.30932.1.10.1.7.100.1.11
.1.3.6.1.4.1.30932.1.20.5.5.11 · 1 row entry · 11 columns
This table contains a list of PDU IPv4 entries that are attached through
the SecureArray connection. 
          
The Row ID field is used as an index on the table.  The Row ID is not
guaranteed to be the same PDU from one instance in time to another.  It 
is recommended to utilize the MAC address as a universally unique ID.
saIpv4Entry entry .1.3.6.1.4.1.30932.1.20.5.5.11.1
This entry defines the columns to be populated in the
'saIpv4Table'. Each column represents an attribute of a PDU.
Indexes
saIpv4RowId
Column Syntax OID
saIpv4RowId
The Row ID of the PDU.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.30932.1.20.5.5.11.1.1
saIpv4PduMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.5.5.11.1.2
saIpV4Enable
Controls whether the IPv4 network interface is enabled.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.30932.1.20.5.5.11.1.3
saIpv4PduIP
Set or get the IPv4 address of the PDU.
SNMPv2-SMIIpAddressr/w
Textual Convention: SNMPv2-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.30932.1.20.5.5.11.1.4
saAutoIP
Controls whether the IPv4 address is retrieved from a
DHCP server or is set statically.
Enumerationr/w
Enumerated Values:
0static
1dynamic
.1.3.6.1.4.1.30932.1.20.5.5.11.1.5
saAutoDNS
Controls whether the DNS addresses are retrieved from
a DHCP server or are set statically.
Enumerationr/w
Enumerated Values:
0static
1dynamic
.1.3.6.1.4.1.30932.1.20.5.5.11.1.6
saSubnetMask
The subnet mask associated with the IPv4 address of this
entry. The value of the mask is an IPv4 address with all the
network bits set to 1 and all the hosts bits set to 0.
SNMPv2-SMIIpAddressr/w
Textual Convention: SNMPv2-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.30932.1.20.5.5.11.1.7
saGateway
Set or get the IPv4 address of the gateway router for the PDU.
SNMPv2-SMIIpAddressr/w
Textual Convention: SNMPv2-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.30932.1.20.5.5.11.1.8
saDns1
Set or get the IPv4 address of the first DNS entry for the PDU.
SNMPv2-SMIIpAddressr/w
Textual Convention: SNMPv2-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.30932.1.20.5.5.11.1.9
saDns2
Set or get the IPv4 address of the second DNS entry for the PDU.
SNMPv2-SMIIpAddressr/w
Textual Convention: SNMPv2-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.30932.1.20.5.5.11.1.10
saDns3
Set or get the IPv4 address of the third DNS entry for the PDU.
SNMPv2-SMIIpAddressr/w
Textual Convention: SNMPv2-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.30932.1.20.5.5.11.1.11
.1.3.6.1.4.1.30932.1.20.10.11 · 1 row entry · 19 columns
This table contains a list of PDU entries that are attached through
the SecureArray connection. 
          
The table contains one, or many rows, depending upon the 
number of PDUs being monitored. Each row in the table represents a PDU 
in the SecureArray.
          
This table always contains at least one entry and a maximum of 48 entries.
          
The Row ID field is used as an index on the table.  The Row ID is not
guaranteed to be the same PDU from one instance in time to another.  It 
is recommended to utilize the MAC address as a universally unique ID.
saPduEntry entry .1.3.6.1.4.1.30932.1.20.10.11.1
This entry defines the columns to be populated in the
'saPduTable'. Each column represents an attribute of a PDU.
Indexes
saPduRowId
Column Syntax OID
saPduRowId
The Row ID of the PDU.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.30932.1.20.10.11.1.1
saPduMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.10.11.1.2
saPduModel
Get the model number of the PDU.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.10.11.1.3
saPduName
Set or get the user assigned name of the PDU.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.10.11.1.4
saPduDescription
Set or get the user assigned description of the PDU.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.10.11.1.5
saPduHasBranchMonitor
An indicator if the PDU supports monitoring voltage, and current on branches in the PDU.
Enumeration
Enumerated Values:
0notsupported
1supported
.1.3.6.1.4.1.30932.1.20.10.11.1.6
saPduHasOutletMonitor
An indicator if the PDU supports monitoring current on the individual outlets in the PDU.
Enumeration
Enumerated Values:
0notsupported
1supported
.1.3.6.1.4.1.30932.1.20.10.11.1.7
saPduHasOutletControl
An indicator if the PDU supports control (turn on/off) individual outlets in the PDU.
Enumeration
Enumerated Values:
0notsupported
1supported
.1.3.6.1.4.1.30932.1.20.10.11.1.8
saPduNumberBranches
Get the number of branches (breakers) in the PDU.
Integer32
Constraints:
range: 0-12
.1.3.6.1.4.1.30932.1.20.10.11.1.9
saPduNumberOutlets
Get the number of outlets in the PDU.
Integer32
Constraints:
range: 0-48
.1.3.6.1.4.1.30932.1.20.10.11.1.10
saPduOutOfService
Set or get whether the PDU is in-service.
Enumerationr/w
Enumerated Values:
0inservice
1outofservice
.1.3.6.1.4.1.30932.1.20.10.11.1.11
saPduVersion
Get the firmware version number of the PDU.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.10.11.1.12
saPduUpgrade
An indicator if the PDU firmware is being upgraded.
Enumeration
Enumerated Values:
0no
1yes
.1.3.6.1.4.1.30932.1.20.10.11.1.13
saPduChainRole
Get the role of the PDU in a SecureArray.
Enumerationr/w
Enumerated Values:
0secondary
1primary
2alternate
.1.3.6.1.4.1.30932.1.20.10.11.1.14
saPduIp
Get IP address of the PDU.
SNMPv2-SMIIpAddress
Textual Convention: SNMPv2-SMIIpAddress OctetString
Type Constraints:
range: 4
.1.3.6.1.4.1.30932.1.20.10.11.1.15
saPduIpv6
Get the IPv6 address of the PDU.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.10.11.1.16
saPduTotalPower
Get the power in volt-amps for the entire PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.10.11.1.17
saPduCabinetId
Get/set the name of the cabinet the PDU is in.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.10.11.1.18
saPduSerialNum
Get the serial number of the PDU.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.10.11.1.19
.1.3.6.1.4.1.30932.1.20.15.11 · 1 row entry · 5 columns
This table contains a list of PDU line entries that are being
monitored by the PDU.
          
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of input lines. Each row 
in the table represents a PDU line in the SecureArray.
          
The table is indexed based on the corresponding Line Row ID.
saPduLineEntry entry .1.3.6.1.4.1.30932.1.20.15.11.1
This entry defines the columns to be populated in the
'saPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
saPduLineRowId
Column Syntax OID
saPduLineRowId
Get the ID of the input line on the PDU.
Integer32
Constraints:
range: 0-512
.1.3.6.1.4.1.30932.1.20.15.11.1.1
saPduLineId
Get the ID of the input line on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.15.11.1.2
saPduLineMac
Get the MAC address of the PDU that owns the input line.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.15.11.1.3
saPduLinePduName
Get the MAC address of the PDU that owns the input line.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.15.11.1.4
saPduLineCurrent
Get current draw in 1/100 amp of the line on the PDU. Convert the value by dividing by 100.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.15.11.1.5
.1.3.6.1.4.1.30932.1.20.20.11 · 1 row entry · 11 columns
This table contains a list of PDU branch entries that are being
monitored by the PDU.
          
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row 
in the table represents a PDU branch in the daisy chain.
          
The table is indexed based on the corresponding Branch ID and
the source PDU MAC.
saPduBranchEntry entry .1.3.6.1.4.1.30932.1.20.20.11.1
This entry defines the columns to be populated in the
'saPduBranchEntry'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
saPduBranchRowId
Column Syntax OID
saPduBranchRowId
Get the Row ID of the branch on the owning PDU.
Integer32
Constraints:
range: 0-768
.1.3.6.1.4.1.30932.1.20.20.11.1.1
saPduBranchId
Get the ID of the branch on the owning PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.11.1.2
saPduBranchMac
Get the MAC address of the PDU that owns the branch.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.20.11.1.3
saPduBranchPduName
Get the MAC address of the PDU that owns the input line.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.20.11.1.4
saPduBranchCurrent
Get the current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.11.1.5
saPduBranchMaxCurrent
Get the maximum current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.11.1.6
saPduBranchVoltage
Get the voltage in 1/10 volts of the branch on the PDU. Convert the value by dividing by 10.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.11.1.7
saPduBranchPower
Get the power in volt-amps for the branch.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.11.1.8
saPduBranchPowerFactor
Get the power factor for the branch.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.11.1.9
saPduBranchStatus
Get the alarm status of the branch.
Enumeration
Enumerated Values:
0noalarm
1warning
2alarm
.1.3.6.1.4.1.30932.1.20.20.11.1.10
saPduBranchEnergy
Get the branch energy accumulated in decaVA-secs, divide by 360 to obtain VA-hr.
SNMPv2-SMICounter64
Textual Convention: SNMPv2-SMICounter64 Unsigned64
Type Constraints:
range: 0..18446744073709551615
.1.3.6.1.4.1.30932.1.20.20.11.1.11
.1.3.6.1.4.1.30932.1.20.20.12 · 1 row entry · 13 columns
This table contains a list of PDU branch alert entries that are
being monitored by the PDU.
          
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row 
in the table represents a PDU branch in the daisy chain.
          
The table is indexed based on the corresponding Branch ID and the
source PDU MAC.
saPduBranchAlertEntry entry .1.3.6.1.4.1.30932.1.20.20.12.1
This entry defines the columns to be populated in the
'saPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
saPduBranchAlertRowId
Column Syntax OID
saPduBranchAlertRowId
Get the Row ID of the branch on the owning PDU.
Integer32
Constraints:
range: 0-768
.1.3.6.1.4.1.30932.1.20.20.12.1.1
saPduBranchAlertMac
Get the MAC address of the PDU that owns the branch.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.20.12.1.2
saPduBranchAlertPduName
Get the MAC address of the PDU that owns the input line.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.20.12.1.3
saPduBranchAlertBranchId
Get the branch of the owning PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.12.1.4
saPduBranchAlertWarnLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.12.1.5
saPduBranchAlertWarnHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.12.1.6
saPduBranchAlertLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.12.1.7
saPduBranchAlertHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.12.1.8
saPduBranchAlertCriticalCurrent
Set or get the critical current draw in 1/100 amp of the
branch on the PDU. Convert the value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.12.1.9
saPduBranchAlertWarnLoVolt
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.12.1.10
saPduBranchAlertWarnHiVolt
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.12.1.11
saPduBranchAlertLoVolt
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.12.1.12
saPduBranchAlertHiVolt
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.20.12.1.13
.1.3.6.1.4.1.30932.1.20.25.11 · 1 row entry · 13 columns
This table contains a list of PDU outlet entries that are being
monitored by the PDU.
          
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets on each PDU. 
Each row in the table represents a PDU outlet in the SecureArray.
saPduOutletEntry entry .1.3.6.1.4.1.30932.1.20.25.11.1
This entry defines the columns to be populated in the
'saPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU.
Indexes
saPduOutletRowId
Column Syntax OID
saPduOutletRowId
Get the ID of the outlet on the PDU.
Integer32
Constraints:
range: 1-4096
.1.3.6.1.4.1.30932.1.20.25.11.1.1
saPduOutletMac
Get the MAC address of the source PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.25.11.1.2
saPduOutletId
Get the ID of the outlet on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.11.1.3
saPduOutletBranchId
Get the ID of the branch the outlet is associated with on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.11.1.4
saPduOutletName
Set or get the user supplied name of the outlet on the PDU.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.25.11.1.5
saPduOutletDescription
Set or get the user supplied description of the outlet on the PDU.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.25.11.1.6
saPduOutletCurrent
Get the current draw in 1/100 amp of the outlet on the PDU. Convert
the value by dividing by 100.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.11.1.7
saPduOutletVoltage
Get the voltage in 1/10 volts of the outlet on the PDU. Convert the
value by dividing by 10.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.11.1.8
saPduOutletPower
The power in Volt-Amps of the outlet on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.11.1.9
saPduOutletStatus
Get the alarm status of the outlet.
Enumeration
Enumerated Values:
0noalarm
1warning
2alarm
.1.3.6.1.4.1.30932.1.20.25.11.1.10
saPduOutletEnergy
Get the outlet energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.
SNMPv2-SMICounter64
Textual Convention: SNMPv2-SMICounter64 Unsigned64
Type Constraints:
range: 0..18446744073709551615
.1.3.6.1.4.1.30932.1.20.25.11.1.11
saPduOutletControl
Set or get power control to the outlet.
Enumerationr/w
Enumerated Values:
0off
1on
.1.3.6.1.4.1.30932.1.20.25.11.1.12
saPduOutletReset
Set or get reset power to the outlet.
Enumerationr/w
Enumerated Values:
0nominal
1reset
.1.3.6.1.4.1.30932.1.20.25.11.1.13
.1.3.6.1.4.1.30932.1.20.25.20 · 1 row entry · 5 columns
This table contains a list of PDU outlet configuration entries
that are being monitored by the PDU.
          
 The table contains one, or many rows, depending upon the number
 of PDUs being monitored and the number of outlets per PDU. Each row 
 in the table represents a PDU outlet in the daisy chain.
           
 The table is indexed based on the corresponding Outlet ID and
 the source PDU MAC.
saPduOutletConfigEntry entry .1.3.6.1.4.1.30932.1.20.25.20.1
This entry defines the columns to be populated in the
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
uni…
Indexes
saPduOutletConfigOutletRowId
Column Syntax OID
saPduOutletConfigOutletRowId
Get the ID of the outlet on the PDU.
Integer32
Constraints:
range: 1-4096
.1.3.6.1.4.1.30932.1.20.25.20.1.1
saPduOutletConfigMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.25.20.1.2
saPduOutletConfigOutletId
Get the ID of the outlet on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.20.1.3
saPduOutletConfigOnDelay
Set or get the outlet power-on delay in seconds.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.30932.1.20.25.20.1.4
saPduOutletConfigResetDelay
Set or get the outlet reset delay in seconds.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.30932.1.20.25.20.1.5
.1.3.6.1.4.1.30932.1.20.25.30 · 1 row entry · 8 columns
This table contains a list of PDU outlet alert entries that are
being monitored by the PDU.
          
 The table contains one, or many rows, depending upon the number
 of PDUs being monitored and the number of outlets per PDU. Each row 
 in the table represents a PDU outlet in the daisy chain.
saPduOutletAlertEntry entry .1.3.6.1.4.1.30932.1.20.25.30.1
This entry defines the columns to be populated in the
'saPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
saPduOutletAlertOutletRowId
Column Syntax OID
saPduOutletAlertOutletRowId
Get the outlet ID on the PDU.
Integer32
Constraints:
range: 1-4096
.1.3.6.1.4.1.30932.1.20.25.30.1.1
saPduOutletAlertMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.25.30.1.2
saPduOutletAlertOutletId
Get the outlet ID on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.30.1.3
saPduOutletAlertWarnLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.30.1.4
saPduOutletAlertWarnHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.30.1.5
saPduOutletAlertLoCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.30.1.6
saPduOutletAlertHiCurrent
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the
value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.30.1.7
saPduOutletAlertCriticalCurrent
Set or get the critical current draw in 1/100 amp of the
outlet on the PDU. Convert the value by dividing by 100.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.25.30.1.8
.1.3.6.1.4.1.30932.1.20.30.10 · 1 row entry · 6 columns
This table contains a list of PDU sensor entries that are being monitored
by the PDU.
          
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
saPduSensorEntry entry .1.3.6.1.4.1.30932.1.20.30.10.1
This entry defines the columns to be populated in the 'saPduSensorTable'.
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor I…
Indexes
saPduSensorRowId
Column Syntax OID
saPduSensorRowId
Get the sensor ID on the PDU.
Integer32
Constraints:
range: 1-8192
.1.3.6.1.4.1.30932.1.20.30.10.1.1
saPduSensorMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.30.10.1.2
saPduSensorId
Get the sensor ID on the PDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.30.10.1.3
saPduSensorName
Set or get the user defined name of the sensor.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.30.10.1.4
saPduSensorType
Get the type of sensor for the entry.
Enumeration
Enumerated Values:
1temperature
2humidity
.1.3.6.1.4.1.30932.1.20.30.10.1.5
saPduSensorValue
Get the value of the sensor. For temperature the value is in degrees
Fahrenheit and for humidity the value is percent humidity.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.30.10.1.6
.1.3.6.1.4.1.30932.1.20.30.20 · 1 row entry · 7 columns
This table contains a list of PDU sensor alert entries that are
being monitored by the PDU.
          
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
saPduSensorAlertEntry entry .1.3.6.1.4.1.30932.1.20.30.20.1
This entry defines the columns to be populated in the 'cpiPduSensorAlertTable'.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU.
Indexes
saPduSensorAlertSensorRowId
Column Syntax OID
saPduSensorAlertSensorRowId
Get the id of the sensor.
Integer32
Constraints:
range: 1-4096
.1.3.6.1.4.1.30932.1.20.30.20.1.1
saPduSensorAlertMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.30.20.1.2
saPduSensorAlertSensorId
Get the id of the sensor.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.30.20.1.3
saPduSensorAlertWarnMin
Set or get the minimum warning value of the sensor.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.30.20.1.4
saPduSensorAlertWarnMax
Set or get the maximum warning value of the sensor.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.30.20.1.5
saPduSensorAlertMin
Set or get the minimum alarm value of the sensor.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.30.20.1.6
saPduSensorAlertMax
Set or get the maximum alarm value of the sensor.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.30.20.1.7
.1.3.6.1.4.1.30932.1.20.40.20 · 1 row entry · 7 columns
This table contains a list of electronic locks that are connected to the PDU
and allows for the configuration of the various settings associated with the
EAS (electronic access system).
          
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
          
The table is index based on the corresponding lock ID and the source
PDU MAC.
saEasConfigEntry entry .1.3.6.1.4.1.30932.1.20.40.20.1
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
saEasConfigLockRowId
Column Syntax OID
saEasConfigLockRowId
Get the MAC address of the PDU.
Integer32
Constraints:
range: 1-128
.1.3.6.1.4.1.30932.1.20.40.20.1.1
saEasConfigLockMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.40.20.1.2
saEasConfigEnabled
Indicates whether the Electronic Access System (EAS) is available on the PDU.
Enumeration
Enumerated Values:
0not-available
1available
.1.3.6.1.4.1.30932.1.20.40.20.1.3
saEasFrontLockEnabled
Enables the front lock on the EAS.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.30932.1.20.40.20.1.4
saEasRearLockEnabled
Enables the rear lock on the EAS.
Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.30932.1.20.40.20.1.5
saEasLockHoldOpenTime
The length of time in seconds to hold open the lock after a successful card scan.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.40.20.1.6
saEasDoorOpenAlarmTime
The length of time in minutes before alerting that the door is open.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.30932.1.20.40.20.1.7
.1.3.6.1.4.1.30932.1.20.40.30 · 1 row entry · 12 columns
This table contains a list of electronic locks that are connected to the PDU
          
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
          
The table is index based on the corresponding lock ID and the source
PDU MAC.
saEasEntry entry .1.3.6.1.4.1.30932.1.20.40.30.1
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
saPduLockRowId
Column Syntax OID
saPduLockRowId
Get the lock ID on the PDU.
Integer32
Constraints:
range: 0-128
.1.3.6.1.4.1.30932.1.20.40.30.1.1
saPduLockMac
Get the MAC address of the PDU.
SNMPv2-TCMacAddress
Textual Convention: SNMPv2-TCMacAddress OctetString
Type Constraints:
range: 6
.1.3.6.1.4.1.30932.1.20.40.30.1.2
saPduLockId
Get the lock ID on the PDU.
Enumeration
Enumerated Values:
1front
2rear
.1.3.6.1.4.1.30932.1.20.40.30.1.3
saPduEasStatus
Indicates if the Electronic Access Control system is ready, inactive, or in an error state.

If the status is Inactive, then the lock is not enabled on the PDU.
If the status is Error, then the cpiEasError…
Enumeration
Enumerated Values:
0inactive
1ready
2error
.1.3.6.1.4.1.30932.1.20.40.30.1.4
saPduDoorStatus
Indicates if the door sensor is closed or open.
Enumeration
Enumerated Values:
0closed
1open
.1.3.6.1.4.1.30932.1.20.40.30.1.5
saPduLockStatus
Indicates if the lock is closed or open.
Enumeration
Enumerated Values:
0closed
1open
.1.3.6.1.4.1.30932.1.20.40.30.1.6
saPduForceStatus
Indicates if the cabinet was forced open by a command from the webUI or SNMP interfaces.
Enumeration
Enumerated Values:
0normal
1force
.1.3.6.1.4.1.30932.1.20.40.30.1.7
saPduTamperStatus
Indicates if the cabinet is currently unlocked/opened without an authorization scan.
Enumeration
Enumerated Values:
0normal
1tamper
.1.3.6.1.4.1.30932.1.20.40.30.1.8
saEasError
Gets the error code associated for the electronic lock system. The possible error codes are:

196608 (0x00030000
) - No error, the lock is working and ready.
167968771 (0x0a030003
) - The lock is not enabl…
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.30932.1.20.40.30.1.9
saEasLockVer
Gets the version of the electronic lock control.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.40.30.1.10
saEasLockSerialNumber
Get the serial number of the electronic lock control.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.30932.1.20.40.30.1.11
saPduLockCtrl
Tells the system to open the locks on the cabinet.
Enumerationr/w
Enumerated Values:
0close
1open
.1.3.6.1.4.1.30932.1.20.40.30.1.12