saPduBranchRowId
CPI-UNIFIED-MIB ·
.1.3.6.1.4.1.30932.1.20.20.11.1.1
Object
column
Integer32
Get the Row ID of the branch on the owning PDU.
Context
- MIB
- CPI-UNIFIED-MIB
- OID
.1.3.6.1.4.1.30932.1.20.20.11.1.1- Type
- column
- Access
- readonly
- Status
- current
- Parent
- saPduBranchEntry
- Table
- saPduBranchTable
- Siblings
- 10
Syntax
Integer32
Values & Constraints
Object Constraints
range: 0-768
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| saPduBranchStatus Get the alarm status of the branch. | column | Enumeration | .1.3.6.1.4.1.30932.1.20.20.11.1.10 |
| saPduBranchEnergy Get the branch energy accumulated in decaVA-secs, divide by 360 to obtain VA-hr. | column | SNMPv2-SMICounter64 | .1.3.6.1.4.1.30932.1.20.20.11.1.11 |
| saPduBranchId Get the ID of the branch on the owning PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.11.1.2 |
| saPduBranchMac Get the MAC address of the PDU that owns the branch. | column | SNMPv2-TCMacAddress | .1.3.6.1.4.1.30932.1.20.20.11.1.3 |
| saPduBranchPduName Get the MAC address of the PDU that owns the input line. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.30932.1.20.20.11.1.4 |
| saPduBranchCurrent Get the current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.11.1.5 |
| saPduBranchMaxCurrent Get the maximum current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.11.1.6 |
| saPduBranchVoltage Get the voltage in 1/10 volts of the branch on the PDU. Convert the value by dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.11.1.7 |
| saPduBranchPower Get the power in volt-amps for the branch. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.11.1.8 |
| saPduBranchPowerFactor Get the power factor for the branch. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.11.1.9 |