saPduBranchAlertEntry
CPI-UNIFIED-MIB ·
.1.3.6.1.4.1.30932.1.20.20.12.1
Object
row
This entry defines the columns to be populated in the 'saPduBranchAlertTable'. Each column represents an alert attribute of a PDU. This table is indexed by the PDU Line identifier that is unique within the PDU.
Context
- MIB
- CPI-UNIFIED-MIB
- OID
.1.3.6.1.4.1.30932.1.20.20.12.1- Type
- row
- Status
- current
- Parent
- saPduBranchAlertTable
- Table
- saPduBranchAlertTable
- Children
- 13
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| saPduBranchAlertRowId Get the Row ID of the branch on the owning PDU. | column | Integer32 | .1.3.6.1.4.1.30932.1.20.20.12.1.1 |
| saPduBranchAlertWarnLoVolt Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.10 |
| saPduBranchAlertWarnHiVolt Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.11 |
| saPduBranchAlertLoVolt Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.12 |
| saPduBranchAlertHiVolt Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.13 |
| saPduBranchAlertMac Get the MAC address of the PDU that owns the branch. | column | SNMPv2-TCMacAddress | .1.3.6.1.4.1.30932.1.20.20.12.1.2 |
| saPduBranchAlertPduName Get the MAC address of the PDU that owns the input line. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.30932.1.20.20.12.1.3 |
| saPduBranchAlertBranchId Get the branch of the owning PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.4 |
| saPduBranchAlertWarnLoCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.5 |
| saPduBranchAlertWarnHiCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.6 |
| saPduBranchAlertLoCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.7 |
| saPduBranchAlertHiCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.8 |
| saPduBranchAlertCriticalCurrent Set or get the critical current draw in 1/100 amp of the
branch on the PDU. Convert the value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| saPduBranchAlertRowId Get the Row ID of the branch on the owning PDU. | column | Integer32 | .1.3.6.1.4.1.30932.1.20.20.12.1.1 |