cpiPduBranchAlertEntry
CPI-UNIFIED-MIB ·
.1.3.6.1.4.1.30932.1.10.1.3.210.1
Object
row
This entry defines the columns to be populated in the 'cpiPduBranchAlertTable'. Each column represents an alert attribute of a PDU. This table is indexed by the PDU Line identifier that is unique within the PDU.
Context
- MIB
- CPI-UNIFIED-MIB
- OID
.1.3.6.1.4.1.30932.1.10.1.3.210.1- Type
- row
- Status
- current
- Parent
- cpiPduBranchAlertTable
- Table
- cpiPduBranchAlertTable
- Children
- 12
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| cpiPduBranchAlertMac Get the MAC address of the PDU. | column | SNMPv2-TCMacAddress | .1.3.6.1.4.1.30932.1.10.1.3.210.1.1 |
| cpiPduBranchAlertLoVolt Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.10 |
| cpiPduBranchAlertHiVolt Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.11 |
| cpiPduBranchAlertIndex Index for branch alert. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.12 |
| cpiPduBranchAlertBranchId Get the branch ID on the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.2 |
| cpiPduBranchAlertWarnLoCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.3 |
| cpiPduBranchAlertWarnHiCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.4 |
| cpiPduBranchAlertLoCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.5 |
| cpiPduBranchAlertHiCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.6 |
| cpiPduBranchAlertCriticalCurrent Set or get the critical current draw in 1/100 amp of the
branch on the PDU. Convert the value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.7 |
| cpiPduBranchAlertWarnLoVolt Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.8 |
| cpiPduBranchAlertWarnHiVolt Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| cpiPduBranchAlertIndex Index for branch alert. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.30932.1.10.1.3.210.1.12 |