saPduBranchAlertWarnHiCurrent
CPI-UNIFIED-MIB ·
.1.3.6.1.4.1.30932.1.20.20.12.1.6
Object
Set or get the current draw in 1/100 amp of the branch on the PDU that triggers a warning condition. Convert the value by dividing by 100.
Context
- MIB
- CPI-UNIFIED-MIB
- OID
.1.3.6.1.4.1.30932.1.20.20.12.1.6- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- saPduBranchAlertEntry
- Table
- saPduBranchAlertTable
- Siblings
- 12
Syntax
SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| saPduBranchAlertRowId Get the Row ID of the branch on the owning PDU. | column | Integer32 | .1.3.6.1.4.1.30932.1.20.20.12.1.1 |
| saPduBranchAlertWarnLoVolt Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.10 |
| saPduBranchAlertWarnHiVolt Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.11 |
| saPduBranchAlertLoVolt Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.12 |
| saPduBranchAlertHiVolt Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.13 |
| saPduBranchAlertMac Get the MAC address of the PDU that owns the branch. | column | SNMPv2-TCMacAddress | .1.3.6.1.4.1.30932.1.20.20.12.1.2 |
| saPduBranchAlertPduName Get the MAC address of the PDU that owns the input line. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.30932.1.20.20.12.1.3 |
| saPduBranchAlertBranchId Get the branch of the owning PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.4 |
| saPduBranchAlertWarnLoCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.5 |
| saPduBranchAlertLoCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.7 |
| saPduBranchAlertHiCurrent Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the
value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.8 |
| saPduBranchAlertCriticalCurrent Set or get the critical current draw in 1/100 amp of the
branch on the PDU. Convert the value by dividing by 100. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.30932.1.20.20.12.1.9 |