powerConnFaultAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.1 | This trap message is reported when the communication between
the power module and the monitoring board is fault. |
dcOutputVoltageHighAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.10 | This trap message is reported when the output voltage
resumes to the normal range from a high value. |
dcOutputCurrentHighAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.11 | This trap message is reported when the output current is too high. |
dcOutputCurrentHighAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.12 | This trap message is reported when the output current
resumes to the normal range from a high value. |
dcOutputVoltageLowAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.13 | This trap message is reported when the output voltage is too low. |
dcOutputVoltageLowAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.14 | This trap message is reported when the output voltage
resumes to the normal range from a low value. |
dcOutputCurrentLowAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.15 | This trap message is reported when the output current is too low. |
dcOutputCurrentLowAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.16 | This trap message is reported when the output current
resumes to the normal range from a low value. |
overLoadPowerAbnormalAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.17 | This trap message is reported when the state of load power is abnormal. |
overLoadPowerAbnormalAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.18 | This trap message is reported when the state of load power recovers to normal. |
overBattPowerOffAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.19 | This trap message is reported when the battery is powered off. |
powerConnFaultAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.2 | This trap message is reported when the communication between
the power module and the monitoring board resumes. |
overBattPowerOffAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.20 | This trap message is reported when the battery is powered on. |
overLoadPowerOffAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.21 | This trap message is reported when the loadpower is powered off. |
overLoadPowerOffAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.22 | This trap message is reported when the loadpower is powered on. |
acMainsSupplyAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.23 | This trap message is reported when the AC mains supply is abnormal. |
acMainsSupplyAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.24 | This trap message is reported when the AC mains supply recovers to normal. |
batteryLoopAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.25 | This trap message is reported when the loop of battery group disconnects. |
batteryLoopAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.26 | This trap message is reported when the loop of battery group connects. |
batteryFuseAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.27 | This trap message is reported when the fuse of battery group disconnects. |
batteryFuseAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.28 | This trap message is reported when the fuse of battery group connects. |
batteryContachAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.29 | This trap message is reported when the contactor of battery group disconnects. |
acInputVoltageAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.3 | This trap message is reported when there is a exception of AC input voltage. |
batteryContachAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.30 | This trap message is reported when the contactor of battery group connects. |
userModuleOffAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.31 | This trap message is reported when the user module is powered off. |
userModuleOffAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.32 | This trap message is reported when the user module is powered on. |
transferModuleOffAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.33 | This trap message is reported when the transfer module is powered off. |
transferModuleOffAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.34 | This trap message is reported when the transfer module is powered on. |
userModuleSwitchAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.35 | This trap message is reported when the user module is switched off. |
transferModuleSwitchAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.37 | This trap message is reported when the transfer module is switched off. |
loadFuseAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.39 | This trap message is reported when the load fuse is abnormal. |
acInputVoltageAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.4 | This trap message is reported when the state of AC input voltage resumes. |
loadFuseAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.40 | This trap message is reported when the load fuse resumes. |
chargeCtrlStateAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.41 | This trap message is reported when the control state of average or floating charge converts. |
chargeModeAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.42 | This trap message is reported when the charge state converts. |
acCommFailAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.43 | This trap message is reported when the AC panel communication fails. |
acCommFailAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.44 | This trap message is reported when the AC panel communication resumes. |
batteryChargeOverAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.45 | This trap message is reported when the Over-current of battery group happens. |
batteryChargeOverAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.46 | OThis trap message is reported when the Over-current of battery group resumes. |
batteryVoltageLackAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.47 | This trap message is reported when the voltage of battery group lacks. |
batteryVoltageLackAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.48 | This trap message is reported when the voltage of battery group recovers from lack. |
loadTwiceOffAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.49 | This trap message is reported when the load is powered off twice. |
acInputVoltageHighAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.5 | This trap message is reported when the input voltage is too high. |
loadTwiceOffAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.50 | This trap message is reported when the load recovers from powering off twice. |
loadOnceOffAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.51 | This trap message is reported when the load is powered off once. |
loadOnceOffAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.52 | This trap message is reported when the load recovers from powering off once. |
acInputPowerOffAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.53 | This trap message is reported when the AC input is powered off. |
acInputPowerOffAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.54 | This trap message is reported when the AC input power is powered off. |
acInputLoopSwtichAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.55 | This trap message is reported when the AC input loop switches to another one. |
batteryDischargeTestStartAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.56 | This trap message is reported when the battery discharge test starts. |
batteryDischargeTestStopAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.57 | This trap message is reported when the battery discharge test stops. |
powerProtectAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.58 | This trap message is reported when the power protection function is enbaled. |
powerUndoProtectAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.59 | This trap message is reported when the power protection function is disabled. |
acInputVoltageHighAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.6 | This trap message is reported when the input voltage
resumes to the normal range from a high value. |
powerCentralOutputModeSwtichAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.60 | This trap message is reported when the central output mode swtiches to another one. |
powerCentralTempretaureAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.61 | This trap message is reported when the central tempretaure is abnormal. |
powerCentralInputAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.62 | This trap message is reported when the central input voltage is abnormal. |
powerCentralOutputAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.63 | This trap message is reported when the central output voltage is abnormal. |
powerRemoteCommFaultAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.64 | This trap message is reported when the communiction between the remote and central fails. |
powerRemoteVoltageAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.65 | This trap message is reported when the remote voltage is abnormal. |
powerLineAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.66 | This trap message is reported when the power line is abnormal. |
powerRemotePowerAlarm1
| .1.3.6.1.4.1.2011.6.2.2.2.0.67 | This trap message is reported when the remote power is abnormal. |
powerRemotePowerAlarm2
| .1.3.6.1.4.1.2011.6.2.2.2.0.68 | This trap message is reported when the Line UA is abnormal. |
powerRemotePowerAlarm3
| .1.3.6.1.4.1.2011.6.2.2.2.0.69 | This trap message is reported when the Central load is abnormal. |
acInputVoltageLowAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.7 | This trap message is reported when the input voltage is too low. |
acInputVoltageLowAlarmResume
| .1.3.6.1.4.1.2011.6.2.2.2.0.8 | This trap message is reported when the input voltage
resumes to the normal range from a low value. |
dcOutputVoltageHighAlarm
| .1.3.6.1.4.1.2011.6.2.2.2.0.9 | This trap message is reported when the output voltage is too high. |
hwEmmPowerBattaryTestStartTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.1 | The agent generates this trap when the power
device battary discharge test starts. |
hwEmmPowerLoadfuseRecoverTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.10 | The agent generates this trap when the fuse of the power
device recovers. |
hwEmmPowerRectifierFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.11 | The agent generates this trap when the rectifier
module of the power device is abnormal and the spully power may decrease. |
hwEmmPowerRectifierRecoverTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.12 | The agent generates this trap when the rectifier module of the
power device recovers. |
hwEmmDigMainsupplyFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.13 | The agent generates this trap when the
main supply digital is faulty. |
hwEmmDigMainsupplyRecoverTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.14 | The agent generates this trap when the
main supply digital recovers. |
hwEmmPowerBatteryOffTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.15 | The agent generates this trap when the power
of battary is off. |
hwEmmBatt1TempFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.16 | The agent generates this trap when the
battery group 1 temperature sensor fault
occurs. |
hwEmmBatt1TempRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.17 | The agent generates this trap when the
battery group 1 temperature sensor fault
recovers. |
hwEmmEnviHumFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.18 | The agent generates this trap when the
environment humidity sensor fault occurs. |
hwEmmEnviHumRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.19 | The agent generates this trap when the
environment humidity sensor fault recovers. |
hwEmmPowerBattaryTestStopTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.2 | The agent generates this trap when the power
device battary discharge test ends. |
hwEmmEnvi1TempFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.20 | The agent generates this trap when the
environment 1 temperature sensor fault
occurs. |
hwEmmEnvi1TempRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.21 | The agent generates this trap when the
environment 1 temperature sensor fault
recovers. |
hwEmmBattTemFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.22 | The agent generates this trap when the battery
temperature out of normal range. |
hwEmmBattTemRecoverTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.23 | The agent generates this trap when the battery
temperature recovers to normal range. |
hwEmmPowerBatteryOffRecoverTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.24 | The agent generates this trap when the power
of battary recovers to on state. |
hwEmmPowerBatteryUnDetectTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.25 | The agent generates this trap when the
one or more batteries are not detected. |
hwEmmPowerBatteryDetectRecoverTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.26 | The agent generates this trap when the
batteries recover. |
hwPowerModuleMismatchTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.27 | The agent generates this trap when the
the power supply system detects mismatched power module . |
hwPowerModuleRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.28 | The agent generates this trap when the power module recovers. |
hwPowerBatteryTempLowTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.29 | The agent generates this trap when the
battery temperature is low. |
hwEmmPowerAcvolFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.3 | The agent generates this trap when the power
device AC input voltage is abnormal. |
hwPowerBatteryTempLowRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.30 | The agent generates this trap when the
battery recovers from low temperature. |
hwPowerBatteryTempHighTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.31 | The agent generates this trap when the
battery temperature is High. |
hwPowerBatteryTempHighRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.32 | The agent generates this trap when the
battery recovers from High temperature. |
hwPowerBatteryChargeOverVolTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.33 | The agent generates this trap when the
battery is charged over voltage. |
hwPowerBatteryChargeOverVolRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.34 | The agent generates this trap when the
battery recovers from charged over voltage. |
hwPowerBatteryDischargeLackVolTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.35 | The agent generates this trap when the
discharging battery is lack voltage. |
hwPowerBatteryDischargeLackVolRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.36 | The agent generates this trap when the
battery recovers from discharging lack voltage. |
hwPowerBatteryChargeOverCurTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.37 | The agent generates this trap when the
battery is charged over current. |
hwPowerBatteryChargeOverCurRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.38 | The agent generates this trap when the
battery recovers from charged over current. |
hwPowerBatteryDischargeOverCurTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.39 | The agent generates this trap when the
discharging battery is over current. |
hwEmmPowerAcvolRecoverTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.4 | The agent generates this trap when the power
device AC input voltage recovers. |
hwPowerBatteryDischargeOverCurRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.40 | The agent generates this trap when the
battery recovers from discharging over current. |
hwRemoteUnitCircuitFailTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.41 | The agent generates this trap when the
circuit of the power module is fault. |
hwRemoteUnitCircuitRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.42 | The agent generates this trap when the
circuit of the power module is recovers from fault. |
hwRemoteUnitFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.43 | The agent generates this trap when the
power module is fault. |
hwRemoteUnitRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.44 | The agent generates this trap when the
power module is recovers from fault. |
hwPowerBatteryEleCoreFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.45 | The agent generates this trap when the
LiBattery cell is fault. |
hwPowerBatteryEleCoreRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.46 | The agent generates this trap when the
LiBattery cell is recovers from fault. |
hwPowerBatteryHeaterFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.47 | The agent generates this trap when the
battery heater fault occurs. |
hwPowerBatteryHeaterFaultRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.48 | The agent generates this trap when the
battery heater fault recovers. |
hwPowerBatteryPortReverseConnectTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.49 | The agent generates this trap when the
battery port is connected reversely. |
hwEmmPowerDcvolFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.5 | The agent generates this trap when the power
device DC output voltage is abnormal. |
hwPowerBatteryPortReverseConnectRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.50 | The agent generates this trap when the
battery port is connected correctly . |
hwPowerBatteryContactorFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.51 | The agent generates this trap when the
battery contactor is fault. |
hwPowerBatteryContactorRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.52 | The agent generates this trap when the
battery contactor fault recovers. |
hwPowerLowTemperatureProtectionFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.53 | The agent generates this trap when the battery cell temperature is lower
than the protection point. |
hwPowerLowTemperatureProtectionRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.54 | The agent generates this trap when the
battery cell low temperature protection fault recovers. |
hwPowerCellChargeHighTemperatureProtectionFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.55 | The agent generates this trap when the battery cell temperature is higher
than the protection point when the battery is charging or discharging. |
hwPowerCellChargeHighTemperatureProtectionRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.56 | The agent generates this trap when the
battery cell high temperature protection fault recovers. |
hwPowerOvervoltageProtectionFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.57 | The agent generates this trap when the battery charging voltage is higher
than the protection point. |
hwPowerOvervoltageProtectionRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.58 | The agent generates this trap when the
battery over voltage protection fault recovers. |
hwPowerOvercurrentProtectionFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.59 | The agent generates this trap when the battery charging electric current is bigger
than the protection point. |
hwEmmPowerDcvolRecoverTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.6 | The agent generates this trap when the power
device DC output voltage recovers. |
hwPowerOvercurrentProtectionRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.60 | The agent generates this trap when the
battery over electric current protection fault recovers. |
hwPowerBattCellPackFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.61 | The agent generates this trap when the battery cell pack fault. |
hwPowerBattCellPackRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.62 | The agent generates this trap when the battery cell pack fault recovers. |
hwPowerBattManualDisconnectionFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.63 | The agent generates this trap when the battery is disconnected manually. |
hwPowerBattManualDisconnectionRestoreTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.64 | The agent generates this trap when the battery manual disconnection fault recovers. |
hwEmmPowerBatteryBoardFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.65 | The agent generates this trap when the
one or more batteries are not detected. |
hwEmmPowerBatteryBoardRecoverTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.66 | The agent generates this trap when the
batteries recover. |
hwEmmPowerBattloopFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.7 | The agent generates this trap when the power
device the battery loop is broken.
In this case, the function of he backup power is lost. |
hwEmmPowerBattloopRecoverTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.8 | The agent generates this trap when the power
device battery loop recovers. |
hwEmmPowerLoadfuseFaultTrap
| .1.3.6.1.4.1.2011.6.2.4.2.0.9 | The agent generates this trap when the fuse of the power device
is broken. In this case, the device is powered off. |