HUAWEI-POWER-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
16
Rows
16
Columns
160
hwPowerSysInfoTable
table.1.3.6.1.4.1.2011.6.2.1.1
·
1 row entry
·
14 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwPowerSysInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwPowerSysInfoTable'
Power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Power basic information table. The indexes of this entry are hwEnvEmuIndex
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the po…
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the po…
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwPowerIndexIndex of the power supply monitored by the monitoring unit | Integer32 Constraints: range: 0-255 | .1.3.6.1.4.1.2011.6.2.1.1.1.1 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerTypeType of the Power emu device. Options: 1.power4875(1) - Type of the Power emu device is power4875 2.power4810(2) - Type of the Power emu device is power4810 … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.1.1.2 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerNamePower name. Invalid: null string. | SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… | .1.3.6.1.4.1.2011.6.2.1.1.1.3 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerStatePower board status: Refers to the status of communication between the internal monitor board of the power device and the external upper board. Options: 1.normal(1) - indicates the normal state 2.fault(2) - in… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.1.1.4 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerRowStatusRowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status. | SNMPv2-TCRowStatusr/w Type Values:
Description: The RowStatus textual convention is used to manage the creation and deletion of conceptual rows, and is used as the value of the SYNTAX clause for the status column of a conceptual row (as described in Section 7.7.1 of … | .1.3.6.1.4.1.2011.6.2.1.1.1.5 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerControlModeControl mode of the power monitor module. Options: 1.manualControl(1) - control by manual, the remote mode 2.autoControl(2) - auto control mode, the default is auto control mode 3.invalid(-1) - indicates that th… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.1.1.6 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerRemoteFrameIDApply for remote power system. It is the frame ID that the remote unit exists in | Integer32r/w Constraints: range: 0-255 | .1.3.6.1.4.1.2011.6.2.1.1.1.7 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerProtectApply for remote power system. It is used to enable or disable N+1 protection function. Options: 1.protect(1) - enables the N+1 protection function 2.undoProtect(2) - disables the N+1 protection function | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.1.1.8 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerVersionVersion of power | SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… | .1.3.6.1.4.1.2011.6.2.1.1.1.9 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerSupplyStatePower supply modes. Options: 1.ac(1) - indicates the AC power supply 2.battery(2) - indicates power supply by the batteries | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.1.1.10 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerWiringCheckSwitchPower wiring check switch of SMU. Options: 1. disable(1) - indicates that the power wiring check state of SMU is disabled 2. enable(2) - indicates that the power wiring check state is enabled 3. invalid(-1) … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.1.1.11 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerLatitudeThe power latitude value. Invalid: -. | OctetString Constraints: range: 0-32 | .1.3.6.1.4.1.2011.6.2.1.1.1.12 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerLongitudeThe power longitude value. Invalid: -. | OctetString Constraints: range: 0-32 | .1.3.6.1.4.1.2011.6.2.1.1.1.13 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| hwPowerBluetoothSwitchPower bluetooth state of SMU. Options: 1. enable(0) - indicates that the power bluetooth state of SMU is enabled. 2. disable(1) - indicates that the power bluetooth state of SMU is disabled. 3. invalid(-1) - indic… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.1.1.14 |
hwACInputTable
table.1.3.6.1.4.1.2011.6.2.1.2
·
1 row entry
·
14 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwACInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwACInputTable'
AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. hwEnvEmuIndex is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
AC input table. Through this table,
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this ent…
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this ent…
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwACLoopIndexInput loop index. There are two channels of AC current input, which are the backup for each other. | Integer32 Constraints: range: 0-255 | .1.3.6.1.4.1.2011.6.2.1.2.1.1 | ||||||||||||
| hwACPowerStateStatus of power supply. Options: 1.normal(1) - indicates that the power supply is normal 2.offline(2) - indicates that the power supply is offline 3.exceedVoltage(3) - indicates that the power supply is … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.2.1.2 | ||||||||||||
| hwACVoltAAC Inuput voltage A. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | mVMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.3 | ||||||||||||
| hwACCurrentAAC input Current A. Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | mAMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.4 | ||||||||||||
| hwACVoltBAC input voltage B. Unit: mv invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | mVMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.5 | ||||||||||||
| hwACCurrentBAC input current B. Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | mAMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.6 | ||||||||||||
| hwACVoltCAC input voltage C. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | mVMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.7 | ||||||||||||
| hwACCurrentCAC input current C. Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | mAMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.8 | ||||||||||||
| hwACVoltageHighAC input over-voltage alarm threshold. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.2.1.9 | ||||||||||||
| hwACVoltageLowAC input under-voltage alarm threshold. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.2.1.10 | ||||||||||||
| hwACRowStatusOnly the add operation, delete operation, and status query operation are supported. | SNMPv2-TCRowStatusr/w Type Values:
Description: The RowStatus textual convention is used to manage the creation and deletion of conceptual rows, and is used as the value of the SYNTAX clause for the status column of a conceptual row (as described in Section 7.7.1 of … | .1.3.6.1.4.1.2011.6.2.1.2.1.11 | ||||||||||||
| hwACVoltageAStatePhase AB/A of AC input state. Options: 1. normal(0) - indicates that the Phase AB/A of AC input state is normal 2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.2.1.12 | ||||||||||||
| hwACVoltageBStatePhase BC/B of AC input state. Options: 1. normal(0) - indicates that the Phase BC/B of AC input state is normal 2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.2.1.13 | ||||||||||||
| hwACVoltageCStatePhase CA/C of AC input state. Options: 1. normal(0) - indicates that the Phase CA/C of AC input state is normal 2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.2.1.14 |
hwDCOutTable
table.1.3.6.1.4.1.2011.6.2.1.3
·
1 row entry
·
13 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwDCOutTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwDCOutTable'
DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
DC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this …
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this …
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwDCVoltageOutDC voltage output. Unit: mV. invalid: -1 | mVMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.1 | ||||||||||||||||
| hwDCCurrentOutDC current output. Unit: mA | mAMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.2 | ||||||||||||||||
| hwDCVoltageOutHighOutput DC exceed-voltage alarm point. Default: 58000 Unit: mV | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.3.1.3 | ||||||||||||||||
| hwDCVoltageOutLowOutput DC below-voltage alarm point . Default value is 45V. Unit: mV | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.3.1.4 | ||||||||||||||||
hwDCVoltageOutStatedeprecated DC output voltage status.Options: 1. normal(1) - indicates that the DC output voltage state is normal 2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage 3. belowVol… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.3.1.5 | ||||||||||||||||
| hwDCCurrentOutHighOutput DC exceed-current alarm point . Unit: mA | mAMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.3.1.6 | ||||||||||||||||
| hwDCCurrentOutLowOutput below-current alarm point . Unit: mA | mAMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.3.1.7 | ||||||||||||||||
hwDCCurrentOutStatedeprecated DC output current status.Options: 1.normal(1) - indicates that the DC output current state is normal 2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage 3.belowVoltage(3) - in… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.3.1.8 | ||||||||||||||||
| hwDCOutRowStatusRowStatus standard operation | SNMPv2-TCRowStatusr/w Type Values:
Description: The RowStatus textual convention is used to manage the creation and deletion of conceptual rows, and is used as the value of the SYNTAX clause for the status column of a conceptual row (as described in Section 7.7.1 of … | .1.3.6.1.4.1.2011.6.2.1.3.1.9 | ||||||||||||||||
| hwDCOutLoadCurrentTotal load current of DC output . Unit: mA. invalid: -1 | mAMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.10 | ||||||||||||||||
| hwDCOutLoadTmpHighThe off protection point under the load temperature, by default, it is 65 degrees centigrade. Unit: 0.01 degree | 0.01 degreeMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.3.1.11 | ||||||||||||||||
| hwDCOutRunStateDC output running status. Options: 1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current 2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current 3.batteryVoltageOver(2) - indicates outpu… | Bits Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.3.1.12 | ||||||||||||||||
| hwDCCommunicationStateDC communication status. Options: 1.normal(0) - indicates that the DC communication state is normal 2.fault(1) - indicates that the DC communication state is fault | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.3.1.13 |
hwLoadinfoTable
table.1.3.6.1.4.1.2011.6.2.1.4
·
1 row entry
·
10 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwLoadinfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwLoadinfoTable'
Load information table. Through this table, the load parameter can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwLoadIndex is the index of the monitored load.
Load information table. Through this table, the load parameter can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, …
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, …
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwLoadIndexLoop index: usually each DC output loop corresponds to a load. | Integer32 Constraints: range: 0-255 | .1.3.6.1.4.1.2011.6.2.1.4.1.1 | ||||||||||||
| hwLoadInfoAdminStateLoad operation. Options: 1. on(1) - indicates that the Load is enabled 2. off(2) - indicates that the Load is disabled 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not s… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.4.1.2 | ||||||||||||
| hwLoadInfoOperStatusStatus of power supply. Options: 1. normal(1) - indicates that the state of power supply is normal 2. abnormal(2) - indicates that the state of power supply is abnormal 3. stop(3) - indicates that the state … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.4.1.3 | ||||||||||||
| hwLoadCurrentPresent current . Unit: mA | mAMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.4.1.4 | ||||||||||||
| hwLoadVoltagePresent voltage . Unit: mV | mVMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.4.1.5 | ||||||||||||
| hwLoadVoltageHighOff voltage (Stop external voltage), in unit of mV, When DC output voltage exceeds the value, the load will be automatically cut off. Unit: mV | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.4.1.6 | ||||||||||||
| hwLoadLoadNameLoad name: usually each DC output loop corresponds to a load. | SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… | .1.3.6.1.4.1.2011.6.2.1.4.1.7 | ||||||||||||
| hwLoadInfoRowStatusRowStatus standard operation | SNMPv2-TCRowStatusr/w Type Values:
Description: The RowStatus textual convention is used to manage the creation and deletion of conceptual rows, and is used as the value of the SYNTAX clause for the status column of a conceptual row (as described in Section 7.7.1 of … | .1.3.6.1.4.1.2011.6.2.1.4.1.8 | ||||||||||||
| hwLoadFuseStateLoad fuse state, including the auxiliary load fuse. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.4.1.9 | ||||||||||||
| hwLoadHoreIndexload hore index | Integer32r/w Constraints: range: 0-255 | .1.3.6.1.4.1.2011.6.2.1.4.1.10 |
hwRectifierTable
table.1.3.6.1.4.1.2011.6.2.1.5
·
1 row entry
·
9 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwRectifierTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRectifierTable'
Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwRectifierIndex is the index of the monitored rectifier module under the power supply.
Rectifier module table.
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which …
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which …
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwRectifierIndexRectifier Module index. There are multiple rectifier modules to a power source. | Integer32 Constraints: range: 0-255 | .1.3.6.1.4.1.2011.6.2.1.5.1.1 | ||||||||||||||||||
| hwRectifierAdminStateSwitch operation of rectifier module. Options: 1.on(1) - indicates that the Rectifier module is enabled 2.off(2) - indicates that the Rectifier module is disabled 3.invalid(-1) - indicates that the devic… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.5.1.2 | ||||||||||||||||||
| hwRectifierOperStatePresent state, 5 and 6 respectively indicates the on/off state of the 48100 power device. Options: 1. normal(1) - indicates that the Rectifier operation state is normal 2.… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.5.1.3 | ||||||||||||||||||
| hwRectifierVoltageOutput voltage . Unit: mV Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. | mVMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.5.1.4 | ||||||||||||||||||
| hwRectifierCurrentOutput current . Unit: mA Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. | mAMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.5.1.5 | ||||||||||||||||||
| hwRectifierRowStatusRowStatus standard operation | SNMPv2-TCRowStatusr/w Type Values:
Description: The RowStatus textual convention is used to manage the creation and deletion of conceptual rows, and is used as the value of the SYNTAX clause for the status column of a conceptual row (as described in Section 7.7.1 of … | .1.3.6.1.4.1.2011.6.2.1.5.1.6 | ||||||||||||||||||
| hwRectifierCurrentLimitcurrent limit switch | SNMPv2-TCTruthValuer/w Type Values:
Description: Represents a boolean value. | .1.3.6.1.4.1.2011.6.2.1.5.1.7 | ||||||||||||||||||
| hwRectifierRunStateRunning state of rectifier module. Options: 1.rectifierOn(0) - indicates that the module is on 2.averageCharge(1) - indicates that the module is being averagely charged. 3.output(2) - indicates that the mod… | Bits Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.5.1.8 | ||||||||||||||||||
| hwRectifierChargeStateCharging state of rectifier. Options: 1. float(0) - indicates that the Charge state of Rectifier is float 2. average(1) - indicates that the Charge state of Rectifier is average 3. test(2) - indicates that t… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.5.1.9 |
hwBatteryGroupTable
table.1.3.6.1.4.1.2011.6.2.1.6.1
·
1 row entry
·
15 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwBatteryGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryGroupTable'
Basic information table of battery group. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Basic information table of battery group.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by …
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by …
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwBatteryGroupCapacityTotal capacity of the present battery group. Unit: Ah | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.1.1.1 | ||||||||||||
| hwBatteryGroupCapcaityRemainTotal remain capacity of the present battery group . invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. Unit: Ah | Integer32 Constraints: range: -1-100 | .1.3.6.1.4.1.2011.6.2.1.6.1.1.2 | ||||||||||||
| hwBatteryGroupsNumber of battery group | Integer32r/w Constraints: range: 0-255 | .1.3.6.1.4.1.2011.6.2.1.6.1.1.3 | ||||||||||||
| hwBatteryGroupVoltageLowWhen the voltage of the battery group is lower than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.6.1.1.4 | ||||||||||||
| hwBatteryGroupChargeLimitCharge limit point quotient, the product of which and the max capacity of the battery group is the max charge current allowed. Default: 15 Unit: percent | percentMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.6.1.1.5 | ||||||||||||
| hwBatteryGroupRowStatusRowStatus standard operation | SNMPv2-TCRowStatusr/w Type Values:
Description: The RowStatus textual convention is used to manage the creation and deletion of conceptual rows, and is used as the value of the SYNTAX clause for the status column of a conceptual row (as described in Section 7.7.1 of … | .1.3.6.1.4.1.2011.6.2.1.6.1.1.6 | ||||||||||||
| hwBatteryGroupOperStatusThe State of the battery supply which was connected with Power EMU. To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal. When the mains supply is ab… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.1.1.7 | ||||||||||||
| hwBatteryGroupVoltageHighWhen the voltage of the battery group is higher than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.6.1.1.8 | ||||||||||||
| hwBatteryGroupTwiceOffVoltageThe twice off protection voltage of the battery group. Its unit is mV. Default: 44000 Unit: mV | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.6.1.1.9 | ||||||||||||
| hwBatteryGroupProtectVoltageThe first off protection voltage of the battery, whose default is 43V. Default: 43000 Unit: mV | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.6.1.1.10 | ||||||||||||
| hwBatteryGroupTmpOffHighThe high temperature off protection point of the battery group, whose default is 50 degrees centigrade. Unit: 0.01 degree | 0.01 degreeMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.6.1.1.11 | ||||||||||||
| hwBatteryInstallTimeThe installing date of battery group. | SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… | .1.3.6.1.4.1.2011.6.2.1.6.1.1.12 | ||||||||||||
| hwBatteryGroupBomCodeThe BOM code of battery. Invalid: null string. | OctetStringr/w Constraints: range: 0-32 | .1.3.6.1.4.1.2011.6.2.1.6.1.1.13 | ||||||||||||
| hwBatteryGroupTypeThe type of lead-acid battery. 1: general. 2: tcbc. 3: tcbb. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.1.1.14 | ||||||||||||
| hwLiBatteryGroupChargeLimitThe charge limit quotiety of the LiBattery. SNMP uses it which has been enlarged 1000 by host. user uses it which has been lessened 1000 by SNMP. Default: 1050. The invalid value -1 indicates that the device can not ge… | Integer32r/w Constraints: range: 50-1050range: -1--1 | .1.3.6.1.4.1.2011.6.2.1.6.1.1.15 |
hwChargeTable
table.1.3.6.1.4.1.2011.6.2.1.6.2
·
1 row entry
·
7 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwChargeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwChargeTable'
Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Charge management table.
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit…
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit…
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwChargeAdminStatusCharge management mode. Options: 1. average(1) - indicates that the charge management mode is average charge 2. float(2) - indicates that the charge management mode is float charge 3. auto(3) - indicate… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.2.1.1 | ||||||||||||||
| hwChargeOperStatusCharge operation status. Options: 1. average(1) - indicates that the charge operation state is average charge 2. float(2) - indicates that the charge operation state is float charge 3. full(3) - indicates that t… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.2.1.2 | ||||||||||||||
| hwAverageChargeVoltageVoltage value of average charge, in unit of mV. Default: 56500 Unit: mV | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.6.2.1.3 | ||||||||||||||
| hwFloatChargeVoltageVoltage value of float charge . Default: 53500 Unit: mV | mVMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.6.2.1.4 | ||||||||||||||
| hwChargeControlRowStatusRowStatus standard operation | SNMPv2-TCRowStatusr/w Type Values:
Description: The RowStatus textual convention is used to manage the creation and deletion of conceptual rows, and is used as the value of the SYNTAX clause for the status column of a conceptual row (as described in Section 7.7.1 of … | .1.3.6.1.4.1.2011.6.2.1.6.2.1.5 | ||||||||||||||
| hwAverageChargeTimeTiming average charge time interval, effective range is 190 days. Default :value is 60 days Unit: day | daySNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.2.1.6 | ||||||||||||||
| hwBatteryTmpRedeemingQuotietyTemperature redeeming quotient, used to set the co-relation between the float charge voltage and the battery temperature. It means How much will the float charge voltage decrease with the increasing of every degree ce… | SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.2.1.7 |
hwBatteryTable
table.1.3.6.1.4.1.2011.6.2.1.6.3
·
1 row entry
·
22 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwBatteryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryTable'
Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryIndex is the index of the monitored battery group.
Battery group state table.
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index …
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index …
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwBatteryIndexBattery group loop index | Integer32 Constraints: range: 0-255 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.1 | ||||||||||||
| hwBatteryCapacityThe permitted max battery capacity of the battery group loop charge. Unit: Ah Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. | SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.2 | ||||||||||||
| hwBatteryLoopStateThe battery group present status. Options: 1. on(1) - indicates that the present state of battery group is on 2. off(2) - indicates that the present state of battery group is off 3. invalid(-1) - indicates… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.3.1.3 | ||||||||||||
| hwBatteryVoltageThe loop voltage of the battery group. Unit: mV invalid: -1 | mVMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.3.1.4 | ||||||||||||
| hwBatteryOperStatusThe present state of the battery group loop. Options: 1. charge(1) - indicates that the present state of the battery group loop is charge 2. discharge(2) - indicates that the present state of the battery group loop i… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.3.1.5 | ||||||||||||
| hwBatteryCurrentPresent current . Unit: mA invalid: -1 | mAMeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.3.1.6 | ||||||||||||
| hwBatteryTemperatureThe loop temperature of the battery group. Unit: degree Invaild:2147483647(0X7FFFFFFF) | degreeSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.7 | ||||||||||||
| hwBatteryRowStatusRowStatus standard operation | SNMPv2-TCRowStatusr/w Type Values:
Description: The RowStatus textual convention is used to manage the creation and deletion of conceptual rows, and is used as the value of the SYNTAX clause for the status column of a conceptual row (as described in Section 7.7.1 of … | .1.3.6.1.4.1.2011.6.2.1.6.3.1.8 | ||||||||||||
| hwBatteryCurrentHighThe over-current alarm point of the battery group. Unit: mA | mAMeasuresRanger/w | .1.3.6.1.4.1.2011.6.2.1.6.3.1.9 | ||||||||||||
| hwBatteryFuseStateBattery fuse state. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.3.1.10 | ||||||||||||
| hwBatteryContactStateThe state of the battery contactor. Options: 1. on(1) - indicates that the contactor is connected 2. off(2) - indicates that the contactor is disconnected 3. invalid(-1) - indicates that the device can not… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.3.1.11 | ||||||||||||
| hwBatteryRemainCapacityRemain capacity of the battery, invalid(-1) | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.12 | ||||||||||||
| hwBatteryProtectStateProtection status of the battery. Options: 1. normal(1) - indicates that the Protection status of the battery is normal 2. overtemperature(2) - indicates that the Protection status of the battery is overte… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.3.1.13 | ||||||||||||
| hwBatteryVoltageStateVoltage state of Battery. Options: 1. normal(1) - indicates that Voltage state of Battery is normal 2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage 3. belowVoltage(3) - indicat… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.3.1.14 | ||||||||||||
| hwBatteryHardwareStateHardware State of Battery. Options: 1. normal(1) - indicates that the hardware state of Battery is normal 2. fault(2) - indicates that the hardware state of Battery is fault | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.3.1.15 | ||||||||||||
| hwBatteryLowTemperatureThe lowest loop temperature of the battery group. Unit: degree Invaild:2147483647(0X7FFFFFFF) | degreeSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.16 | ||||||||||||
| hwBatteryAntiTheftSwitchAnti-theft switch of Battery. Options: 1. disable(1) - indicates that the anti-theft state of Battery is disabled 2. enable(2) - indicates that the anti-theft state of Battery is enabled 3. invalid(-1) - ind… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.3.1.17 | ||||||||||||
| hwBatteryAntiTheftTimeoutThe anti-theft timeout time of battery. The invalid value -1 indicates that the device can not get the value, e.g. the EMU does not support this operation. | hourInteger32r/w Constraints: range: 8-720range: -1--1 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.18 | ||||||||||||
| hwBatterySequenceThe sequence of LiBattery. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.19 | ||||||||||||
| hwBatteryAddressThe address of LiBattery which corresponds to the subnode of LiBattery. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.20 | ||||||||||||
| hwBatteryHeaterStateThe state of battery heater. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.3.1.21 | ||||||||||||
| hwBatteryHealthStateThe health state of battery. Unit:% invalid:-1 | %Integer32 Constraints: range: -1-100 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.22 |
hwBatteryTestTable
table.1.3.6.1.4.1.2011.6.2.1.6.4
·
1 row entry
·
11 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwBatteryTestTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryTestTable'
Battery test table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Battery test table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwBatteryTestAdminStatusBattery test admin status. Options: 1. start(1) - indicates that the Battery starts testing 2. terminate(2) - indicates that the Battery terminates testing 3. enableAutoTest(3) - indicates that th… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.4.1.1 | ||||||||||||||
| hwBatteryTestAutoDischargePeriodAuto discharge test period. Effective range is 30 -240 days. Default: 120 Unit: day | daySNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.2 | ||||||||||||||
hwBatteryTestResultobsolete Test result:Options: 1. testing(1) - indicates that the Battery test is in operation 2. complete(2) - indicates that the Battery test is completed normally 3. alarmTerminated(3) - indicates… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.4.1.3 | ||||||||||||||
hwBatteryTestStartTimeobsolete Time of starting test | SNMPv2-TCDateAndTime Type Constraints: range: 8range: 11Description: A date-time specification. field octets contents range ----- ------ -------- ----- 1 1-2 year* 0..65536 2 3 month … | .1.3.6.1.4.1.2011.6.2.1.6.4.1.4 | ||||||||||||||
| hwBatteryTestDurationBattery discharge test duration. Effective range is 1-100 hours. Default :value is 10 hours Unit: hour | hourSNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.5 | ||||||||||||||
| hwBatteryTestTerminateVoltageBattery discharge test end voltage. Effective range (DC lack alarm voltage+0.5V-voltage of floating charge). Default: 45600 Unit: mV | mVSNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.6 | ||||||||||||||
hwBatteryTestTotalDischargeAHobsolete Total discharge AH.Unit: mAH | mAHSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.7 | ||||||||||||||
| hwBatteryTestOperStatusBattery discharge test operate status. Options: 1. autoTestPermit(1) - indicates that auto discharge test is enabled 2. autoTestForbid(2) - indicates that auto discharge test is disabled 3. timeautoTestPer… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.4.1.8 | ||||||||||||||
| hwBatteryTestPhaseBattery test phase. Options: 1. charge(1) - indicates the batter test phase is charge 2. discharge(2) - indicates the batter test phase is discharge 3. record(3) - indicates the powe… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.4.1.9 | ||||||||||||||
| hwBatteryTestStartHourDischarge start time. Effective range is 0 23 Default: 0 Unit: hour | hourSNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.10 | ||||||||||||||
| hwBatteryTestAlarmThresholdThe battery discharge test alarm threshold in ratio of the range:1~79. | percentSNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.11 |
hwBatteryLogTestTable
table.1.3.6.1.4.1.2011.6.2.1.6.5
·
1 row entry
·
10 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwBatteryLogTestTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryLogTestTable'
Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryLogTestIndex is the index of the monitored battery.
Battery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuInd…
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuInd…
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwBatteryLogTestIndexBattery discharge test result index | Integer32 Constraints: range: 0-255 | .1.3.6.1.4.1.2011.6.2.1.6.5.1.1 | ||||||||||||||
| hwBatteryLogTestStartTimeBattery discharge test start time | SNMPv2-TCDateAndTime Type Constraints: range: 8range: 11Description: A date-time specification. field octets contents range ----- ------ -------- ----- 1 1-2 year* 0..65536 2 3 month … | .1.3.6.1.4.1.2011.6.2.1.6.5.1.2 | ||||||||||||||
| hwBatteryLogTestDischargeDurationDuration of discharge. Unit: minute | minuteSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.5.1.3 | ||||||||||||||
| hwBatteryLogTestTerminateVoltageEnd voltage of battery discharge test . Unit: mV | mVSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.5.1.4 | ||||||||||||||
| hwBatteryLogTestBatteryStatusBattery status. Options: 1. expectant(1) - indicates the batter test state is expectant 2. unexpected(2) - indicates the batter test state is unexpected 3. unknown(3) - indicates the batter test state is unknown | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.5.1.5 | ||||||||||||||
| hwBatteryLogTestTotalDischargeAHDischarge cumulate AH. Unit: mAH | mAHSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.5.1.6 | ||||||||||||||
| hwBatteryLogTestFinishBattery Test result. Options: 1. testing(1) - indicates that it is during testing 2. completed(2) - indicates that the test is completed normally 3. alarmTerminated(3) - indicates that the test is … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.6.5.1.7 | ||||||||||||||
| hwBatteryLogTestEfficiencyThe information of battery test efficiency. | percentSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.5.1.8 | ||||||||||||||
| hwBatteryLogTestBatteryTemperatureBattery discharge test end Temperature. Unit: 0.01 Degree Invaild: 0X7FFFFFFF | 0.01 DegreeSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.5.1.9 | ||||||||||||||
| hwBatteryLogTestBatteryCurrentBattery discharge test average Current. Unit: mA | mASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.5.1.10 |
hwBatteryCellTable
table.1.3.6.1.4.1.2011.6.2.1.6.6
·
1 row entry
·
3 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwBatteryCellTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryCellTable'
The state of battery cell. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryCellIndex is the index of the battery cell.
The state of battery cell.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by…
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by…
| Column | Syntax | OID |
|---|---|---|
| hwBatteryCellIndexThe index of battery cell. | Integer32 Constraints: range: 0-15 | .1.3.6.1.4.1.2011.6.2.1.6.6.1.1 |
| hwBatteryCellTemperatureThe temperature of battery cell. Unit: C Non-value: 0x7FFFFFFF | CSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.6.1.2 |
| hwBatteryCellVoltageThe voltage of battery cell. Unit: mV Non-value: -1 | mVSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.6.6.1.3 |
.1.3.6.1.4.1.2011.6.2.1.7
·
1 row entry
·
10 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwRemoteProvidePowerInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteProvidePowerInfoTable'
Remote provide power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Remote provide power basic information table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored…
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored…
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwPowerCentralStateState of the central module. Options: 1. normal(1) - indicates the normal state 2. temOver(2) - indicates the over-temperature | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.7.1.1 | ||||||||||||||||
| hwPowerCentralDCInPutStateState of central module DC input: Options: 1.normal(1) - indicates the normal state 2.lack(2) - indicates the voltage underflow 3.over(3) - indicates the voltage overflow | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.7.1.2 | ||||||||||||||||
| hwPowerCentralDCOutputStateState of central module DC output. Options: 1. normal(1) - indicates the normal state 2. volLack(2) - indicates the voltage underflow 3. volOver(3) - indicates the voltage overflow 4. loadOver(4) … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.7.1.3 | ||||||||||||||||
| hwPowerCentralDCOutputModeMode of central module DC output. Options: 1. highVolMode(1) - indicates the high voltage output mode 2. lowVolMode(2) - indicates the low voltage output mode | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.7.1.4 | ||||||||||||||||
| hwPowerRemoteCommStateRemote power module communications state. Options: 1. normal(1) - indicates the normal state 2. revfault(2) - indicates the receiving of fault 3. sendfault(3) - indicates the sending of fault | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.7.1.5 | ||||||||||||||||
| hwPowerRemoteDCInputStateState of remote module DC input. Options: 1. normal(1) - indicates the normal state 2. lack(2) - indicates that the voltage is underflow | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.7.1.6 | ||||||||||||||||
| hwPowerRemoteLineCurStatestate of line between central and remote module. Options: 1.normal(1) - indicates the normal state 2.cablejoining(2) - indicates the cable joining 3.curLeakage(3) - indicates the cur Leakage 4.curOver(4) - … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.7.1.7 | ||||||||||||||||
| hwPowerRemotePowerStatestate of remote UA60 power. Options: 1. normal(1) - indicates the normal state 2. fault(2) - indicates the faulty state | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.7.1.8 | ||||||||||||||||
| hwPowerRemoteLineStateState of line U1. Options: 1. u1state(0) - indicates the power remote line state is u1 state 2. u2state(1) - indicates the power remote line state is u2 state 3. u3state(2) - indicates the power remote line state is u3 … | Bitsr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.7.1.9 | ||||||||||||||||
| hwPowerCentralLoadStatestate of central load. Options: 1. normal(1) - indicates the normal state 2. overload(2) - indicates overload 3. nonload(3) - indicates non-load | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.7.1.10 |
hwACInfomationTable
table.1.3.6.1.4.1.2011.6.2.1.8
·
1 row entry
·
6 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwACInfomationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwACInfomationTable'
AC infomation table. The table is not supported. The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
AC infomation table. The table is not supported.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| hwACInfoCommStatecommunication state of AC input module. The node is not supported. Options: 1. normal(0) - indicates the communication state of AC is normal 2. fault(1) - indicates the communication state of AC is fault | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.8.1.1 | ||||||||||||
| hwACInfoThunderStateThunder's state. The node is not supported. Options: 1. normal(0) - indicates the state of Thunder is normal 2. fault(1) - indicates the state of Thunder is fault | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.8.1.2 | ||||||||||||
| hwACInfoCurrentLoopCurrent AC input working loop. The leaf is not supported. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.8.1.3 | ||||||||||||
| hwACInfoMCBTriggerAC input MCB trigger state. The leaf is not supported. Options: 1. normal(0) - indicates the AC input MCB trigger state is normal 2. breakDown(1)- indicates the AC input MCB trigger state is break-down | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.1.8.1.4 | ||||||||||||
| hwACInfoFrequencyThe infomation of AC input frequency. This leaf is not supported. Unit: HZ | HZSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.1.8.1.5 | ||||||||||||
| hwACInfoRowStatusRowStatus standard operation The leaf is not supported. | SNMPv2-TCRowStatusr/w Type Values:
Description: The RowStatus textual convention is used to manage the creation and deletion of conceptual rows, and is used as the value of the SYNTAX clause for the status column of a conceptual row (as described in Section 7.7.1 of … | .1.3.6.1.4.1.2011.6.2.1.8.1.6 |
hwRemoteUnitSysInfoTable
table.1.3.6.1.4.1.2011.6.2.5.1
·
1 row entry
·
4 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwRemoteUnitSysInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteUnitSysInfoTable'
Remote power system, remote unit basic information table. The indexes of this entry is hwEnvEmuIndex.
Remote power system, remote unit basic information table. The indexes of
this entry is hwEnvEmuIndex.
this entry is hwEnvEmuIndex.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
| hwRemoteUnitPowerSystypeType of the remote unit power system. Options: 1.rftv(1) - Type of the remote unit power system is RFT-V 2.rftc(2) - Type of the remote unit power system is RFT-C … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.5.1.1.1 | ||||||
| hwRemoteUnitDCOutputVolThe remote unit DC output voltage. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. | mVSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.5.1.1.2 | ||||||
| hwRemoteUnitDCOutputCurThe remote unit DC output current. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. | mASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.5.1.1.3 | ||||||
| hwRemoteUnitSlotNumThe remote unit slot number. Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.5.1.1.4 |
hwRemoteUnitSlotTable
table.1.3.6.1.4.1.2011.6.2.5.2
·
1 row entry
·
8 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwRemoteUnitSlotTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteUnitSlotTable'
Remote power system, remote unit slot information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
Remote power system, remote unit slot information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| hwRemoteUnitSlotIndexThe remote unit slot index. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.5.2.1.1 | ||||||||
| hwRemoteUnitSlotCircuitNumThe remote unit slot circuit number. Invalid:-1. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.5.2.1.2 | ||||||||
| hwRemoteUnitSlotHardVersionThe remote unit slot hard version. Invalid: null string. | OctetString Constraints: range: 1-128 | .1.3.6.1.4.1.2011.6.2.5.2.1.3 | ||||||||
| hwRemoteUnitSlotSoftVersionThe remote unit slot soft version. Invalid: null string. | OctetString Constraints: range: 1-128 | .1.3.6.1.4.1.2011.6.2.5.2.1.4 | ||||||||
| hwRemoteUnitSlotStatusThe state of the remote unit slot. Options: 1.normal(1) - The state of the remote unit slot is normal 2.fault(2) - The state of the remote unit slot is fault 3.null(3) - The sta… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.5.2.1.5 | ||||||||
| hwRemoteUnitSlotAdminStatusDelete the remote unit slot. Options: 1.delete(1) - Delete the remote unit slot 2.invalid(255) - Unknown | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.5.2.1.6 | ||||||||
| hwRemoteUnitSlotDCOutputVolThe remote unit slot DC output voltage. Invalid:-1. | mVSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.5.2.1.7 | ||||||||
| hwRemoteUnitSlotDCOutputCurThe remote unit slot DC output current. Invalid:-1. | mASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.5.2.1.8 |
hwRemoteUnitCircuitTable
table.1.3.6.1.4.1.2011.6.2.5.3
·
1 row entry
·
4 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwRemoteUnitCircuitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteUnitCircuitTable'
Remote power system, remote unit circuit information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
Remote power system, remote unit circuit information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| hwRemoteUnitCircuitIndexThe remote unit circuit index. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.5.3.1.1 | ||||||||
| hwRemoteUnitCircuitInputVolThe remote unit circuit input voltage. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. | mVSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.5.3.1.2 | ||||||||
| hwRemoteUnitCircuitInputCurThe remote unit circuit input current. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. | mASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.2011.6.2.5.3.1.3 | ||||||||
| hwRemoteUnitCircuitStateThe state of the remote unit circuit. Options: 1.normal(1) - The state of the remote unit circuit is normal 2.fault(2) - The state of the remote unit circuit is fault 3.null(3) -… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.2011.6.2.5.3.1.4 |