HUAWEI-POWER-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
16
Rows
16
Columns
160
.1.3.6.1.4.1.2011.6.2.1.1 · 1 row entry · 14 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwPowerSysInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwPowerSysInfoTable'
Power basic information table. The indexes of this table are hwEnvEmuIndex 
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is 
the index of the monitoring unit. hwPowerIndex is the index of the power 
supply monitored by the monitoring unit.
hwPowerSysInfoEntry row .1.3.6.1.4.1.2011.6.2.1.1.1
Power basic information table. The indexes of this entry are hwEnvEmuIndex
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the po…
Column Syntax OID
Index of the power supply monitored by the monitoring unit
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.1.1.1
Type of the Power emu device.
Options:
1.power4875(1) - Type of the Power emu device is power4875
2.power4810(2) - Type of the Power emu device is power4810 …
Enumerationr/w
Enumerated Values:
1power4875
2power4810
3power48100
4power4850
5power48240
6power48120
7power48300
8power48240SinglePhase
9universalPower
10power4845
11rpower
15power4805
16power4820
17onps
18power4875l
100psma
101permAl175nt
102mcs1800
103mcs1800A
104mcs3000
105sm40sm60
106scu
107eltek
108dk04
109dk04C
110dpc
120power4830
121h831pmua
122power3000
123liFeBattery
125etp4830
126etp4890
127h801pmu
128etp48150
129etp4850
130etp48200
131etp4860
255other
.1.3.6.1.4.1.2011.6.2.1.1.1.2
Power name.
Invalid: null string.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.2011.6.2.1.1.1.3
Power board status:
Refers to the status of communication between the internal monitor board
of the power device and the external upper board.
Options:
1.normal(1) - indicates the normal state
2.fault(2) - in…
Enumeration
Enumerated Values:
-1invalid
1normal
2fault
3protecting
4switched
.1.3.6.1.4.1.2011.6.2.1.1.1.4
RowStatus standard operation. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status.
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.1.1.5
Control mode of the power monitor module.
Options:
1.manualControl(1) - control by manual, the remote mode
2.autoControl(2) - auto control mode, the default is auto control mode
3.invalid(-1) - indicates that th…
Enumerationr/w
Enumerated Values:
-1invalid
1manualControl
2autoControl
.1.3.6.1.4.1.2011.6.2.1.1.1.6
Apply for remote power system.
It is the frame ID that the remote unit exists in
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.1.1.7
Apply for remote power system.
It is used to enable or disable N+1 protection function.
Options:
1.protect(1) - enables the N+1 protection function
2.undoProtect(2) - disables the N+1 protection function
Enumerationr/w
Enumerated Values:
1protect
2undoProtect
.1.3.6.1.4.1.2011.6.2.1.1.1.8
Version of power
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.2011.6.2.1.1.1.9
Power supply modes.
Options:
1.ac(1) - indicates the AC power supply
2.battery(2) - indicates power supply by the batteries
Enumeration
Enumerated Values:
1ac
2battery
.1.3.6.1.4.1.2011.6.2.1.1.1.10
Power wiring check switch of SMU.
Options:
1. disable(1) - indicates that the power wiring check state of SMU is disabled
2. enable(2) - indicates that the power wiring check state is enabled
3. invalid(-1) …
Enumerationr/w
Enumerated Values:
-1invalid
1disable
2enable
.1.3.6.1.4.1.2011.6.2.1.1.1.11
The power latitude value.
Invalid: -.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.2011.6.2.1.1.1.12
The power longitude value.
Invalid: -.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.2011.6.2.1.1.1.13
Power bluetooth state of SMU.
Options:
1. enable(0) - indicates that the power bluetooth state of SMU is enabled.
2. disable(1) - indicates that the power bluetooth state of SMU is disabled.
3. invalid(-1) - indic…
Enumerationr/w
Enumerated Values:
-1invalid
0enable
1disable
.1.3.6.1.4.1.2011.6.2.1.1.1.14
.1.3.6.1.4.1.2011.6.2.1.2 · 1 row entry · 14 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwACInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwACInputTable'
AC input table. Through this table, 
AC input monitoring parameters of 4875 power supply, 4845 power supply, 
4810 power supply, 48100 power supply, and 48240 power supply can 
be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. 
hwEnvEmuIndex is the index of the monitoring unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
hwACInputEntry row .1.3.6.1.4.1.2011.6.2.1.2.1
AC input table. Through this table,
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this ent…
Column Syntax OID
Input loop index. There are two channels of AC current input,
which are the backup for each other.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.2.1.1
Status of power supply.
Options:
1.normal(1) - indicates that the power supply is normal
2.offline(2) - indicates that the power supply is offline
3.exceedVoltage(3) - indicates that the power supply is …
Enumeration
Enumerated Values:
-1invalid
1normal
2offline
3exceedVoltage
4belowVoltage
5backup
.1.3.6.1.4.1.2011.6.2.1.2.1.2
AC Inuput voltage A.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRange .1.3.6.1.4.1.2011.6.2.1.2.1.3
AC input Current A.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mAMeasuresRange .1.3.6.1.4.1.2011.6.2.1.2.1.4
AC input voltage B.
Unit: mv
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRange .1.3.6.1.4.1.2011.6.2.1.2.1.5
AC input current B.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mAMeasuresRange .1.3.6.1.4.1.2011.6.2.1.2.1.6
AC input voltage C.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRange .1.3.6.1.4.1.2011.6.2.1.2.1.7
AC input current C.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mAMeasuresRange .1.3.6.1.4.1.2011.6.2.1.2.1.8
AC input over-voltage alarm threshold.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.2.1.9
AC input under-voltage alarm threshold.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.2.1.10
Only the add operation, delete operation, and status query operation are supported.
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.2.1.11
Phase AB/A of AC input state.
Options:
1. normal(0) - indicates that the Phase AB/A of AC input state is normal
2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage …
Enumeration
Enumerated Values:
-1invalid
0normal
1belowVoltage
2exceedVoltage
3missingPhase
.1.3.6.1.4.1.2011.6.2.1.2.1.12
Phase BC/B of AC input state.
Options:
1. normal(0) - indicates that the Phase BC/B of AC input state is normal
2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage …
Enumeration
Enumerated Values:
-1invalid
0normal
1belowVoltage
2exceedVoltage
3missingPhase
.1.3.6.1.4.1.2011.6.2.1.2.1.13
Phase CA/C of AC input state.
Options:
1. normal(0) - indicates that the Phase CA/C of AC input state is normal
2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage …
Enumeration
Enumerated Values:
-1invalid
0normal
1belowVoltage
2exceedVoltage
3missingPhase
.1.3.6.1.4.1.2011.6.2.1.2.1.14

hwDCOutTable

table
.1.3.6.1.4.1.2011.6.2.1.3 · 1 row entry · 13 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwDCOutTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwDCOutTable'
DC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply, 
4810 power supply, 482400 power supply, and 48100 power supply can 
be set and queried.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex. 
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, 
is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwDCOutEntry row .1.3.6.1.4.1.2011.6.2.1.3.1
DC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this …
Column Syntax OID
DC voltage output.
Unit: mV.
invalid: -1
mVMeasuresRange .1.3.6.1.4.1.2011.6.2.1.3.1.1
DC current output.
Unit: mA
mAMeasuresRange .1.3.6.1.4.1.2011.6.2.1.3.1.2
Output DC exceed-voltage alarm point.
Default: 58000
Unit: mV
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.3.1.3
Output DC below-voltage alarm point . Default value is 45V.
Unit: mV
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.3.1.4
DC output voltage status.
Options:
1. normal(1) - indicates that the DC output voltage state is normal
2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage
3. belowVol…
Enumeration
Enumerated Values:
-1invalid
1normal
2exceedVoltage
3belowVoltage
.1.3.6.1.4.1.2011.6.2.1.3.1.5
Output DC exceed-current alarm point .
Unit: mA
mAMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.3.1.6
Output below-current alarm point .
Unit: mA
mAMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.3.1.7
DC output current status.
Options:
1.normal(1) - indicates that the DC output current state is normal
2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage
3.belowVoltage(3) - in…
Enumeration
Enumerated Values:
-1invalid
1normal
2exceedVoltage
3belowVoltage
.1.3.6.1.4.1.2011.6.2.1.3.1.8
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.3.1.9
Total load current of DC output .
Unit: mA.
invalid: -1
mAMeasuresRange .1.3.6.1.4.1.2011.6.2.1.3.1.10
The off protection point under the load temperature, by default,
it is 65 degrees centigrade.
Unit: 0.01 degree
0.01 degreeMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.3.1.11
DC output running status.
Options:
1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current
2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current
3.batteryVoltageOver(2) - indicates outpu…
Bits
Enumerated Values:
0battery1ChargeCurOver
1battery2ChargeCurOver
2batteryVoltageOver
3batteryVoltageLack
4loadOff
5batteryOff
6communicationFailure
7dcOutManual
.1.3.6.1.4.1.2011.6.2.1.3.1.12
DC communication status.
Options:
1.normal(0) - indicates that the DC communication state is normal
2.fault(1) - indicates that the DC communication state is fault
Enumeration
Enumerated Values:
0normal
1fault
.1.3.6.1.4.1.2011.6.2.1.3.1.13
.1.3.6.1.4.1.2011.6.2.1.4 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwLoadinfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwLoadinfoTable'
Load information table. Through this table, the load parameter can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit. 
hwLoadIndex is the index of the monitored load.
hwLoadinfoEntry row .1.3.6.1.4.1.2011.6.2.1.4.1
Load information table. Through this table, the load parameter can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, …
Column Syntax OID
Loop index: usually each DC output loop corresponds to a load.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.4.1.1
Load operation.
Options:
1. on(1) - indicates that the Load is enabled
2. off(2) - indicates that the Load is disabled
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not s…
Enumerationr/w
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.4.1.2
Status of power supply.
Options:
1. normal(1) - indicates that the state of power supply is normal
2. abnormal(2) - indicates that the state of power supply is abnormal
3. stop(3) - indicates that the state …
Enumeration
Enumerated Values:
-1invalid
1normal
2abnormal
3stop
.1.3.6.1.4.1.2011.6.2.1.4.1.3
Present current .
Unit: mA
mAMeasuresRange .1.3.6.1.4.1.2011.6.2.1.4.1.4
Present voltage .
Unit: mV
mVMeasuresRange .1.3.6.1.4.1.2011.6.2.1.4.1.5
Off voltage (Stop external voltage), in unit of mV,
When DC output voltage exceeds the value, the load will be automatically cut off.
Unit: mV
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.4.1.6
Load name: usually each DC output loop corresponds to a load.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.2011.6.2.1.4.1.7
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.4.1.8
Load fuse state, including the auxiliary load fuse.
Options:
1. on(1) - indicates that the fuse is connected
2. off(2) - indicates that the fuse is disconnected
3. invalid(-1) - indicates that the device can …
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.4.1.9
load hore index
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.4.1.10
.1.3.6.1.4.1.2011.6.2.1.5 · 1 row entry · 9 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRectifierTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRectifierTable'
Rectifier module table. 
Through this table, the status information of the rectifier module 
can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwRectifierIndex is the index of the monitored rectifier module under the power supply.
hwRectifierEntry row .1.3.6.1.4.1.2011.6.2.1.5.1
Rectifier module table.
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which …
Column Syntax OID
Rectifier Module index. There are multiple rectifier
modules to a power source.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.5.1.1
Switch operation of rectifier module.
Options:
1.on(1) - indicates that the Rectifier module is enabled
2.off(2) - indicates that the Rectifier module is disabled
3.invalid(-1) - indicates that the devic…
Enumerationr/w
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.5.1.2
Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device.
Options:
1. normal(1) - indicates that the Rectifier operation state is normal
2.…
Enumeration
Enumerated Values:
-1invalid
1normal
2fault
3protect
4communicationFailure
5on
6noConfig
7offline
8close
.1.3.6.1.4.1.2011.6.2.1.5.1.3
Output voltage .
Unit: mV
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mVMeasuresRange .1.3.6.1.4.1.2011.6.2.1.5.1.4
Output current .
Unit: mA
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mAMeasuresRange .1.3.6.1.4.1.2011.6.2.1.5.1.5
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.5.1.6
current limit switch
SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.2011.6.2.1.5.1.7
Running state of rectifier module.
Options:
1.rectifierOn(0) - indicates that the module is on
2.averageCharge(1) - indicates that the module is being averagely charged.
3.output(2) - indicates that the mod…
Bits
Enumerated Values:
0rectifierOn
1averageCharge
2output
3isLimit
.1.3.6.1.4.1.2011.6.2.1.5.1.8
Charging state of rectifier.
Options:
1. float(0) - indicates that the Charge state of Rectifier is float
2. average(1) - indicates that the Charge state of Rectifier is average
3. test(2) - indicates that t…
Enumeration
Enumerated Values:
0float
1average
2test
.1.3.6.1.4.1.2011.6.2.1.5.1.9
.1.3.6.1.4.1.2011.6.2.1.6.1 · 1 row entry · 15 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBatteryGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryGroupTable'
Basic information table of battery group. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit, 
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryGroupEntry row .1.3.6.1.4.1.2011.6.2.1.6.1.1
Basic information table of battery group.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by …
Column Syntax OID
Total capacity of the present battery group.
Unit: Ah
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.1.1.1
Total remain capacity of the present battery group .
invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
Unit: Ah
Integer32
Constraints:
range: -1-100
.1.3.6.1.4.1.2011.6.2.1.6.1.1.2
Number of battery group
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.6.1.1.3
When the voltage of the battery group is lower than the value set,
the battery group will no longer supply power. Its unit is mV.
Default: 43000
Unit: mV
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.6.1.1.4
Charge limit point quotient, the product of which and the max capacity
of the battery group is the max charge current allowed.
Default: 15
Unit: percent
percentMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.6.1.1.5
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.6.1.1.6
The State of the battery supply which was connected with Power EMU.
To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal.
When the mains supply is ab…
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.1.1.7
When the voltage of the battery group is higher than the value set, the battery group
will no longer supply power. Its unit is mV.
Default: 43000
Unit: mV
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.6.1.1.8
The twice off protection voltage of the battery group. Its unit is mV.
Default: 44000
Unit: mV
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.6.1.1.9
The first off protection voltage of the battery,
whose default is 43V.
Default: 43000
Unit: mV
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.6.1.1.10
The high temperature off protection point of the battery group,
whose default is 50 degrees centigrade.
Unit: 0.01 degree
0.01 degreeMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.6.1.1.11
The installing date of battery group.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.2011.6.2.1.6.1.1.12
The BOM code of battery.
Invalid: null string.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2011.6.2.1.6.1.1.13
The type of lead-acid battery.
1: general.
2: tcbc.
3: tcbb.
Enumerationr/w
Enumerated Values:
1general
2tcbc
3tcbb
.1.3.6.1.4.1.2011.6.2.1.6.1.1.14
The charge limit quotiety of the LiBattery.
SNMP uses it which has been enlarged 1000 by host.
user uses it which has been lessened 1000 by SNMP.
Default: 1050.
The invalid value -1 indicates that the device can not ge…
Integer32r/w
Constraints:
range: 50-1050
range: -1--1
.1.3.6.1.4.1.2011.6.2.1.6.1.1.15
.1.3.6.1.4.1.2011.6.2.1.6.2 · 1 row entry · 7 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwChargeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwChargeTable'
Charge management table. 
Through this table, the charging parameter of the battery can be set and queried. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwChargeEntry row .1.3.6.1.4.1.2011.6.2.1.6.2.1
Charge management table.
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit…
Column Syntax OID
Charge management mode.
Options:
1. average(1) - indicates that the charge management mode is average charge
2. float(2) - indicates that the charge management mode is float charge
3. auto(3) - indicate…
Enumerationr/w
Enumerated Values:
-1invalid
1average
2float
3auto
.1.3.6.1.4.1.2011.6.2.1.6.2.1.1
Charge operation status.
Options:
1. average(1) - indicates that the charge operation state is average charge
2. float(2) - indicates that the charge operation state is float charge
3. full(3) - indicates that t…
Enumeration
Enumerated Values:
-1invalid
1average
2float
3full
4noCharge
5discharge
6sleep
.1.3.6.1.4.1.2011.6.2.1.6.2.1.2
Voltage value of average charge, in unit of mV.
Default: 56500
Unit: mV
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.6.2.1.3
Voltage value of float charge .
Default: 53500
Unit: mV
mVMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.6.2.1.4
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.6.2.1.5
Timing average charge time interval, effective range is 190 days.
Default :value is 60 days
Unit: day
daySNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.2.1.6
Temperature redeeming quotient, used to set the co-relation
between the float charge voltage and the battery temperature.
It means How much will the float charge voltage decrease
with the increasing of every degree ce…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.2.1.7
.1.3.6.1.4.1.2011.6.2.1.6.3 · 1 row entry · 22 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBatteryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryTable'
Battery group state table. 
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. 
hwEnvEmuIndex is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryIndex is the index of the monitored battery group.
hwBatteryEntry row .1.3.6.1.4.1.2011.6.2.1.6.3.1
Battery group state table.
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index …
Column Syntax OID
Battery group loop index
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.6.3.1.1
The permitted max battery capacity of the battery group loop charge.
Unit: Ah
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.2
The battery group present status.
Options:
1. on(1) - indicates that the present state of battery group is on
2. off(2) - indicates that the present state of battery group is off
3. invalid(-1) - indicates…
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.3.1.3
The loop voltage of the battery group.
Unit: mV
invalid: -1
mVMeasuresRange .1.3.6.1.4.1.2011.6.2.1.6.3.1.4
The present state of the battery group loop.
Options:
1. charge(1) - indicates that the present state of the battery group loop is charge
2. discharge(2) - indicates that the present state of the battery group loop i…
Enumeration
Enumerated Values:
-1invalid
1charge
2discharge
.1.3.6.1.4.1.2011.6.2.1.6.3.1.5
Present current .
Unit: mA
invalid: -1
mAMeasuresRange .1.3.6.1.4.1.2011.6.2.1.6.3.1.6
The loop temperature of the battery group.
Unit: degree
Invaild:2147483647(0X7FFFFFFF)
degreeSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.7
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.6.3.1.8
The over-current alarm point of the battery group.
Unit: mA
mAMeasuresRanger/w .1.3.6.1.4.1.2011.6.2.1.6.3.1.9
Battery fuse state.
Options:
1. on(1) - indicates that the fuse is connected
2. off(2) - indicates that the fuse is disconnected
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU …
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.3.1.10
The state of the battery contactor.
Options:
1. on(1) - indicates that the contactor is connected
2. off(2) - indicates that the contactor is disconnected
3. invalid(-1) - indicates that the device can not…
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.3.1.11
Remain capacity of the battery,
invalid(-1)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.12
Protection status of the battery.
Options:
1. normal(1) - indicates that the Protection status of the battery is normal
2. overtemperature(2) - indicates that the Protection status of the battery is overte…
Enumeration
Enumerated Values:
1normal
2overtemperature
3overCurrent
.1.3.6.1.4.1.2011.6.2.1.6.3.1.13
Voltage state of Battery.
Options:
1. normal(1) - indicates that Voltage state of Battery is normal
2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage
3. belowVoltage(3) - indicat…
Enumeration
Enumerated Values:
1normal
2exceedVoltage
3belowVoltage
.1.3.6.1.4.1.2011.6.2.1.6.3.1.14
Hardware State of Battery.
Options:
1. normal(1) - indicates that the hardware state of Battery is normal
2. fault(2) - indicates that the hardware state of Battery is fault
Enumeration
Enumerated Values:
1normal
2fault
.1.3.6.1.4.1.2011.6.2.1.6.3.1.15
The lowest loop temperature of the battery group.
Unit: degree
Invaild:2147483647(0X7FFFFFFF)
degreeSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.16
Anti-theft switch of Battery.
Options:
1. disable(1) - indicates that the anti-theft state of Battery is disabled
2. enable(2) - indicates that the anti-theft state of Battery is enabled
3. invalid(-1) - ind…
Enumerationr/w
Enumerated Values:
-1invalid
1disable
2enable
.1.3.6.1.4.1.2011.6.2.1.6.3.1.17
The anti-theft timeout time of battery.
The invalid value -1 indicates that the device can not get the value, e.g. the EMU does not support this operation.
hourInteger32r/w
Constraints:
range: 8-720
range: -1--1
.1.3.6.1.4.1.2011.6.2.1.6.3.1.18
The sequence of LiBattery.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.19
The address of LiBattery which corresponds to the subnode of LiBattery.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.20
The state of battery heater.
Enumeration
Enumerated Values:
-1invalid
1on
2off
3noconfig
.1.3.6.1.4.1.2011.6.2.1.6.3.1.21
The health state of battery.
Unit:%
invalid:-1
%Integer32
Constraints:
range: -1-100
.1.3.6.1.4.1.2011.6.2.1.6.3.1.22
.1.3.6.1.4.1.2011.6.2.1.6.4 · 1 row entry · 11 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBatteryTestTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryTestTable'
Battery test table. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex. 
hwEnvEmuIndex is the index of the monitored unit, 
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryTestEntry row .1.3.6.1.4.1.2011.6.2.1.6.4.1
Battery test table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Column Syntax OID
Battery test admin status.
Options:
1. start(1) - indicates that the Battery starts testing
2. terminate(2) - indicates that the Battery terminates testing
3. enableAutoTest(3) - indicates that th…
Enumerationr/w
Enumerated Values:
1start
2terminate
3enableAutoTest
4disableAutoTest
5timeautoTest
6offautoTest
7timeoffautoTest
.1.3.6.1.4.1.2011.6.2.1.6.4.1.1
Auto discharge test period.
Effective range is 30 -240 days.
Default: 120
Unit: day
daySNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.2
Test result:
Options:
1. testing(1) - indicates that the Battery test is in operation
2. complete(2) - indicates that the Battery test is completed normally
3. alarmTerminated(3) - indicates…
Enumeration
Enumerated Values:
1testing
2complete
3alarmTerminated
4hostTerminated
5overtimeTerminated
6normal
7supplyRecoverAutotestTerminated
.1.3.6.1.4.1.2011.6.2.1.6.4.1.3
Time of starting test
SNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.2011.6.2.1.6.4.1.4
Battery discharge test duration.
Effective range is 1-100 hours.
Default :value is 10 hours
Unit: hour
hourSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.5
Battery discharge test end voltage.
Effective range (DC lack alarm voltage+0.5V-voltage of floating charge).
Default: 45600
Unit: mV
mVSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.6
Total discharge AH.
Unit: mAH
mAHSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.7
Battery discharge test operate status.
Options:
1. autoTestPermit(1) - indicates that auto discharge test is enabled
2. autoTestForbid(2) - indicates that auto discharge test is disabled
3. timeautoTestPer…
Enumeration
Enumerated Values:
1autoTestPermit
2autoTestForbid
3timeautoTestPermit
4offautoTestPermit
5timeoffautoTestPermit
.1.3.6.1.4.1.2011.6.2.1.6.4.1.8
Battery test phase.
Options:
1. charge(1) - indicates the batter test phase is charge
2. discharge(2) - indicates the batter test phase is discharge
3. record(3) - indicates the powe…
Enumeration
Enumerated Values:
1charge
2discharge
3record
4finish
5waitingfordischarge
.1.3.6.1.4.1.2011.6.2.1.6.4.1.9
Discharge start time.
Effective range is 0 23
Default: 0
Unit: hour
hourSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.10
The battery discharge test alarm threshold in ratio of the range:1~79.
percentSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.11
.1.3.6.1.4.1.2011.6.2.1.6.5 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBatteryLogTestTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryLogTestTable'
Battery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuIndex is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit. 
hwBatteryLogTestIndex is the index of the monitored battery.
hwBatteryLogTestEntry row .1.3.6.1.4.1.2011.6.2.1.6.5.1
Battery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuInd…
Column Syntax OID
Battery discharge test result index
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.6.5.1.1
Battery discharge test start time
SNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.2011.6.2.1.6.5.1.2
Duration of discharge.
Unit: minute
minuteSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.3
End voltage of battery discharge test .
Unit: mV
mVSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.4
Battery status.
Options:
1. expectant(1) - indicates the batter test state is expectant
2. unexpected(2) - indicates the batter test state is unexpected
3. unknown(3) - indicates the batter test state is unknown
Enumeration
Enumerated Values:
1expectant
2unexpected
3unknown
.1.3.6.1.4.1.2011.6.2.1.6.5.1.5
Discharge cumulate AH.
Unit: mAH
mAHSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.6
Battery Test result.
Options:
1. testing(1) - indicates that it is during testing
2. completed(2) - indicates that the test is completed normally
3. alarmTerminated(3) - indicates that the test is …
Enumeration
Enumerated Values:
1testing
2completed
3alarmTerminated
4hostTerminated
5overtimeTerminated
6notTest
7supplyRecoverAutotestTerminated
.1.3.6.1.4.1.2011.6.2.1.6.5.1.7
The information of battery test efficiency.
percentSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.8
Battery discharge test end Temperature.
Unit: 0.01 Degree
Invaild: 0X7FFFFFFF
0.01 DegreeSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.9
Battery discharge test average Current.
Unit: mA
mASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.10
.1.3.6.1.4.1.2011.6.2.1.6.6 · 1 row entry · 3 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBatteryCellTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryCellTable'
The state of battery cell.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit. 
hwBatteryCellIndex is the index of the battery cell.
hwBatteryCellEntry row .1.3.6.1.4.1.2011.6.2.1.6.6.1
The state of battery cell.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by…
Column Syntax OID
The index of battery cell.
Integer32
Constraints:
range: 0-15
.1.3.6.1.4.1.2011.6.2.1.6.6.1.1
The temperature of battery cell.
Unit: C
Non-value: 0x7FFFFFFF
CSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.6.1.2
The voltage of battery cell.
Unit: mV
Non-value: -1
mVSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.6.1.3
.1.3.6.1.4.1.2011.6.2.1.7 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRemoteProvidePowerInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteProvidePowerInfoTable'
Remote provide power basic information table. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit, 
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwRemoteProvidePowerInfoEntry row .1.3.6.1.4.1.2011.6.2.1.7.1
Remote provide power basic information table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored…
Column Syntax OID
State of the central module.
Options:
1. normal(1) - indicates the normal state
2. temOver(2) - indicates the over-temperature
Enumeration
Enumerated Values:
1normal
2temOver
.1.3.6.1.4.1.2011.6.2.1.7.1.1
State of central module DC input:
Options:
1.normal(1) - indicates the normal state
2.lack(2) - indicates the voltage underflow
3.over(3) - indicates the voltage overflow
Enumeration
Enumerated Values:
1normal
2lack
3over
.1.3.6.1.4.1.2011.6.2.1.7.1.2
State of central module DC output.
Options:
1. normal(1) - indicates the normal state
2. volLack(2) - indicates the voltage underflow
3. volOver(3) - indicates the voltage overflow
4. loadOver(4) …
Enumeration
Enumerated Values:
1normal
2volLack
3volOver
4loadOver
5shortCircuit
6noLoad
.1.3.6.1.4.1.2011.6.2.1.7.1.3
Mode of central module DC output.
Options:
1. highVolMode(1) - indicates the high voltage output mode
2. lowVolMode(2) - indicates the low voltage output mode
Enumeration
Enumerated Values:
1highVolMode
2lowVolMode
.1.3.6.1.4.1.2011.6.2.1.7.1.4
Remote power module communications state.
Options:
1. normal(1) - indicates the normal state
2. revfault(2) - indicates the receiving of fault
3. sendfault(3) - indicates the sending of fault
Enumerationr/w
Enumerated Values:
1normal
2revfault
3sendfault
.1.3.6.1.4.1.2011.6.2.1.7.1.5
State of remote module DC input.
Options:
1. normal(1) - indicates the normal state
2. lack(2) - indicates that the voltage is underflow
Enumerationr/w
Enumerated Values:
1normal
2lack
.1.3.6.1.4.1.2011.6.2.1.7.1.6
state of line between central and remote module.
Options:
1.normal(1) - indicates the normal state
2.cablejoining(2) - indicates the cable joining
3.curLeakage(3) - indicates the cur Leakage
4.curOver(4) - …
Enumerationr/w
Enumerated Values:
1normal
2cablejoining
3curLeakage
4curOver
.1.3.6.1.4.1.2011.6.2.1.7.1.7
state of remote UA60 power.
Options:
1. normal(1) - indicates the normal state
2. fault(2) - indicates the faulty state
Enumerationr/w
Enumerated Values:
1normal
2fault
.1.3.6.1.4.1.2011.6.2.1.7.1.8
State of line U1.
Options:
1. u1state(0) - indicates the power remote line state is u1 state
2. u2state(1) - indicates the power remote line state is u2 state
3. u3state(2) - indicates the power remote line state is u3 …
Bitsr/w
Enumerated Values:
0u1state
1u2state
2u3state
3u4state
4a1state
5a2state
6a3state
7a4state
.1.3.6.1.4.1.2011.6.2.1.7.1.9
state of central load.
Options:
1. normal(1) - indicates the normal state
2. overload(2) - indicates overload
3. nonload(3) - indicates non-load
Enumerationr/w
Enumerated Values:
1normal
2overload
3nonload
.1.3.6.1.4.1.2011.6.2.1.7.1.10
.1.3.6.1.4.1.2011.6.2.1.8 · 1 row entry · 6 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwACInfomationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwACInfomationTable'
AC infomation table.  The table is not supported.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwACInfomationEntry row .1.3.6.1.4.1.2011.6.2.1.8.1
AC infomation table. The table is not supported.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
Column Syntax OID
communication state of AC input module.
The node is not supported.
Options:
1. normal(0) - indicates the communication state of AC is normal
2. fault(1) - indicates the communication state of AC is fault
Enumeration
Enumerated Values:
0normal
1fault
.1.3.6.1.4.1.2011.6.2.1.8.1.1
Thunder's state.
The node is not supported.
Options:
1. normal(0) - indicates the state of Thunder is normal
2. fault(1) - indicates the state of Thunder is fault
Enumeration
Enumerated Values:
0normal
1fault
.1.3.6.1.4.1.2011.6.2.1.8.1.2
Current AC input working loop.
The leaf is not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.8.1.3
AC input MCB trigger state.
The leaf is not supported.
Options:
1. normal(0) - indicates the AC input MCB trigger state is normal
2. breakDown(1)- indicates the AC input MCB trigger state is break-down
Enumeration
Enumerated Values:
0normal
1breakDown
.1.3.6.1.4.1.2011.6.2.1.8.1.4
The infomation of AC input frequency.
This leaf is not supported.
Unit: HZ
HZSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.8.1.5
RowStatus standard operation
The leaf is not supported.
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.8.1.6
.1.3.6.1.4.1.2011.6.2.5.1 · 1 row entry · 4 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRemoteUnitSysInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteUnitSysInfoTable'
Remote power system, remote unit basic information table. The indexes of 
this entry is hwEnvEmuIndex.
hwRemoteUnitSysInfoEntry row .1.3.6.1.4.1.2011.6.2.5.1.1
Remote power system, remote unit basic information table. The indexes of
this entry is hwEnvEmuIndex.
Column Syntax OID
Type of the remote unit power system.
Options:
1.rftv(1) - Type of the remote unit power system is RFT-V
2.rftc(2) - Type of the remote unit power system is RFT-C …
Enumeration
Enumerated Values:
1rftv
2rftc
255invalid
.1.3.6.1.4.1.2011.6.2.5.1.1.1
The remote unit DC output voltage.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mVSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.1.1.2
The remote unit DC output current.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.1.1.3
The remote unit slot number.
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.1.1.4
.1.3.6.1.4.1.2011.6.2.5.2 · 1 row entry · 8 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRemoteUnitSlotTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteUnitSlotTable'
Remote power system, remote unit slot information table. The indexes of 
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
hwRemoteUnitSlotEntry row .1.3.6.1.4.1.2011.6.2.5.2.1
Remote power system, remote unit slot information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
Column Syntax OID
The remote unit slot index.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.1
The remote unit slot circuit number.
Invalid:-1.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.2
The remote unit slot hard version.
Invalid: null string.
OctetString
Constraints:
range: 1-128
.1.3.6.1.4.1.2011.6.2.5.2.1.3
The remote unit slot soft version.
Invalid: null string.
OctetString
Constraints:
range: 1-128
.1.3.6.1.4.1.2011.6.2.5.2.1.4
The state of the remote unit slot.
Options:
1.normal(1) - The state of the remote unit slot is normal
2.fault(2) - The state of the remote unit slot is fault
3.null(3) - The sta…
Enumeration
Enumerated Values:
1normal
2fault
3null
255invalid
.1.3.6.1.4.1.2011.6.2.5.2.1.5
Delete the remote unit slot.
Options:
1.delete(1) - Delete the remote unit slot
2.invalid(255) - Unknown
Enumerationr/w
Enumerated Values:
1delete
255invalid
.1.3.6.1.4.1.2011.6.2.5.2.1.6
The remote unit slot DC output voltage.
Invalid:-1.
mVSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.7
The remote unit slot DC output current.
Invalid:-1.
mASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.8
.1.3.6.1.4.1.2011.6.2.5.3 · 1 row entry · 4 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRemoteUnitCircuitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteUnitCircuitTable'
Remote power system, remote unit circuit information table. The indexes of 
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
hwRemoteUnitCircuitEntry row .1.3.6.1.4.1.2011.6.2.5.3.1
Remote power system, remote unit circuit information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
Column Syntax OID
The remote unit circuit index.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.3.1.1
The remote unit circuit input voltage.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mVSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.3.1.2
The remote unit circuit input current.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.3.1.3
The state of the remote unit circuit.
Options:
1.normal(1) - The state of the remote unit circuit is normal
2.fault(2) - The state of the remote unit circuit is fault
3.null(3) -…
Enumeration
Enumerated Values:
1normal
2fault
3null
255invalid
.1.3.6.1.4.1.2011.6.2.5.3.1.4