HUAWEI-POWER-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
16
Rows
16
Columns
160
.1.3.6.1.4.1.2011.6.2.1.1 · 1 row entry · 14 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwPowerSysInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwPowerSysInfoTable'
Power basic information table. The indexes of this table are hwEnvEmuIndex 
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is 
the index of the monitoring unit. hwPowerIndex is the index of the power 
supply monitored by the monitoring unit.
hwPowerSysInfoEntry row .1.3.6.1.4.1.2011.6.2.1.1.1
Power basic information table. The indexes of this entry are hwEnvEmuIndex
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the po…
Column Syntax OID
hwPowerIndexIndex of the power supply monitored by the monitoring unitInteger32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.1.1.1
hwPowerTypeType of the Power emu device.
Options:
1.power4875(1) - Type of the Power emu device is power4875
2.power4810(2) - Type of the Power emu device is power4810 …
Enumerationr/w
Enumerated Values:
1power4875
2power4810
3power48100
4power4850
5power48240
6power48120
7power48300
8power48240SinglePhase
9universalPower
10power4845
11rpower
15power4805
16power4820
17onps
18power4875l
100psma
101permAl175nt
102mcs1800
103mcs1800A
104mcs3000
105sm40sm60
106scu
107eltek
108dk04
109dk04C
110dpc
120power4830
121h831pmua
122power3000
123liFeBattery
125etp4830
126etp4890
127h801pmu
128etp48150
129etp4850
130etp48200
131etp4860
255other
.1.3.6.1.4.1.2011.6.2.1.1.1.2
hwPowerNamePower name.
Invalid: null string.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.2011.6.2.1.1.1.3
hwPowerStatePower board status:
Refers to the status of communication between the internal monitor board
of the power device and the external upper board.
Options:
1.normal(1) - indicates the normal state
2.fault(2) - in…
Enumeration
Enumerated Values:
-1invalid
1normal
2fault
3protecting
4switched
.1.3.6.1.4.1.2011.6.2.1.1.1.4
hwPowerRowStatusRowStatus standard operation. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status.
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.1.1.5
hwPowerControlModeControl mode of the power monitor module.
Options:
1.manualControl(1) - control by manual, the remote mode
2.autoControl(2) - auto control mode, the default is auto control mode
3.invalid(-1) - indicates that th…
Enumerationr/w
Enumerated Values:
-1invalid
1manualControl
2autoControl
.1.3.6.1.4.1.2011.6.2.1.1.1.6
hwPowerRemoteFrameIDApply for remote power system.
It is the frame ID that the remote unit exists in
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.1.1.7
hwPowerProtectApply for remote power system.
It is used to enable or disable N+1 protection function.
Options:
1.protect(1) - enables the N+1 protection function
2.undoProtect(2) - disables the N+1 protection function
Enumerationr/w
Enumerated Values:
1protect
2undoProtect
.1.3.6.1.4.1.2011.6.2.1.1.1.8
hwPowerVersionVersion of powerSNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.2011.6.2.1.1.1.9
hwPowerSupplyStatePower supply modes.
Options:
1.ac(1) - indicates the AC power supply
2.battery(2) - indicates power supply by the batteries
Enumeration
Enumerated Values:
1ac
2battery
.1.3.6.1.4.1.2011.6.2.1.1.1.10
hwPowerWiringCheckSwitchPower wiring check switch of SMU.
Options:
1. disable(1) - indicates that the power wiring check state of SMU is disabled
2. enable(2) - indicates that the power wiring check state is enabled
3. invalid(-1) …
Enumerationr/w
Enumerated Values:
-1invalid
1disable
2enable
.1.3.6.1.4.1.2011.6.2.1.1.1.11
hwPowerLatitudeThe power latitude value.
Invalid: -.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.2011.6.2.1.1.1.12
hwPowerLongitudeThe power longitude value.
Invalid: -.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.2011.6.2.1.1.1.13
hwPowerBluetoothSwitchPower bluetooth state of SMU.
Options:
1. enable(0) - indicates that the power bluetooth state of SMU is enabled.
2. disable(1) - indicates that the power bluetooth state of SMU is disabled.
3. invalid(-1) - indic…
Enumerationr/w
Enumerated Values:
-1invalid
0enable
1disable
.1.3.6.1.4.1.2011.6.2.1.1.1.14
.1.3.6.1.4.1.2011.6.2.1.2 · 1 row entry · 14 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwACInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwACInputTable'
AC input table. Through this table, 
AC input monitoring parameters of 4875 power supply, 4845 power supply, 
4810 power supply, 48100 power supply, and 48240 power supply can 
be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. 
hwEnvEmuIndex is the index of the monitoring unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
hwACInputEntry row .1.3.6.1.4.1.2011.6.2.1.2.1
AC input table. Through this table,
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this ent…
Column Syntax OID
hwACLoopIndexInput loop index. There are two channels of AC current input,
which are the backup for each other.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.2.1.1
hwACPowerStateStatus of power supply.
Options:
1.normal(1) - indicates that the power supply is normal
2.offline(2) - indicates that the power supply is offline
3.exceedVoltage(3) - indicates that the power supply is …
Enumeration
Enumerated Values:
-1invalid
1normal
2offline
3exceedVoltage
4belowVoltage
5backup
.1.3.6.1.4.1.2011.6.2.1.2.1.2
hwACVoltAAC Inuput voltage A.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRange.1.3.6.1.4.1.2011.6.2.1.2.1.3
hwACCurrentAAC input Current A.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mAMeasuresRange.1.3.6.1.4.1.2011.6.2.1.2.1.4
hwACVoltBAC input voltage B.
Unit: mv
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRange.1.3.6.1.4.1.2011.6.2.1.2.1.5
hwACCurrentBAC input current B.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mAMeasuresRange.1.3.6.1.4.1.2011.6.2.1.2.1.6
hwACVoltCAC input voltage C.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRange.1.3.6.1.4.1.2011.6.2.1.2.1.7
hwACCurrentCAC input current C.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mAMeasuresRange.1.3.6.1.4.1.2011.6.2.1.2.1.8
hwACVoltageHighAC input over-voltage alarm threshold.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.2.1.9
hwACVoltageLowAC input under-voltage alarm threshold.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.2.1.10
hwACRowStatusOnly the add operation, delete operation, and status query operation are supported.SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.2.1.11
hwACVoltageAStatePhase AB/A of AC input state.
Options:
1. normal(0) - indicates that the Phase AB/A of AC input state is normal
2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage …
Enumeration
Enumerated Values:
-1invalid
0normal
1belowVoltage
2exceedVoltage
3missingPhase
.1.3.6.1.4.1.2011.6.2.1.2.1.12
hwACVoltageBStatePhase BC/B of AC input state.
Options:
1. normal(0) - indicates that the Phase BC/B of AC input state is normal
2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage …
Enumeration
Enumerated Values:
-1invalid
0normal
1belowVoltage
2exceedVoltage
3missingPhase
.1.3.6.1.4.1.2011.6.2.1.2.1.13
hwACVoltageCStatePhase CA/C of AC input state.
Options:
1. normal(0) - indicates that the Phase CA/C of AC input state is normal
2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage …
Enumeration
Enumerated Values:
-1invalid
0normal
1belowVoltage
2exceedVoltage
3missingPhase
.1.3.6.1.4.1.2011.6.2.1.2.1.14

hwDCOutTable

table
.1.3.6.1.4.1.2011.6.2.1.3 · 1 row entry · 13 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwDCOutTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwDCOutTable'
DC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply, 
4810 power supply, 482400 power supply, and 48100 power supply can 
be set and queried.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex. 
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, 
is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwDCOutEntry row .1.3.6.1.4.1.2011.6.2.1.3.1
DC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this …
Column Syntax OID
hwDCVoltageOutDC voltage output.
Unit: mV.
invalid: -1
mVMeasuresRange.1.3.6.1.4.1.2011.6.2.1.3.1.1
hwDCCurrentOutDC current output.
Unit: mA
mAMeasuresRange.1.3.6.1.4.1.2011.6.2.1.3.1.2
hwDCVoltageOutHighOutput DC exceed-voltage alarm point.
Default: 58000
Unit: mV
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.3.1.3
hwDCVoltageOutLowOutput DC below-voltage alarm point . Default value is 45V.
Unit: mV
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.3.1.4
DC output voltage status.
Options:
1. normal(1) - indicates that the DC output voltage state is normal
2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage
3. belowVol…
Enumeration
Enumerated Values:
-1invalid
1normal
2exceedVoltage
3belowVoltage
.1.3.6.1.4.1.2011.6.2.1.3.1.5
hwDCCurrentOutHighOutput DC exceed-current alarm point .
Unit: mA
mAMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.3.1.6
hwDCCurrentOutLowOutput below-current alarm point .
Unit: mA
mAMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.3.1.7
DC output current status.
Options:
1.normal(1) - indicates that the DC output current state is normal
2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage
3.belowVoltage(3) - in…
Enumeration
Enumerated Values:
-1invalid
1normal
2exceedVoltage
3belowVoltage
.1.3.6.1.4.1.2011.6.2.1.3.1.8
hwDCOutRowStatusRowStatus standard operationSNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.3.1.9
hwDCOutLoadCurrentTotal load current of DC output .
Unit: mA.
invalid: -1
mAMeasuresRange.1.3.6.1.4.1.2011.6.2.1.3.1.10
hwDCOutLoadTmpHighThe off protection point under the load temperature, by default,
it is 65 degrees centigrade.
Unit: 0.01 degree
0.01 degreeMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.3.1.11
hwDCOutRunStateDC output running status.
Options:
1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current
2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current
3.batteryVoltageOver(2) - indicates outpu…
Bits
Enumerated Values:
0battery1ChargeCurOver
1battery2ChargeCurOver
2batteryVoltageOver
3batteryVoltageLack
4loadOff
5batteryOff
6communicationFailure
7dcOutManual
.1.3.6.1.4.1.2011.6.2.1.3.1.12
hwDCCommunicationStateDC communication status.
Options:
1.normal(0) - indicates that the DC communication state is normal
2.fault(1) - indicates that the DC communication state is fault
Enumeration
Enumerated Values:
0normal
1fault
.1.3.6.1.4.1.2011.6.2.1.3.1.13
.1.3.6.1.4.1.2011.6.2.1.4 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwLoadinfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwLoadinfoTable'
Load information table. Through this table, the load parameter can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit. 
hwLoadIndex is the index of the monitored load.
hwLoadinfoEntry row .1.3.6.1.4.1.2011.6.2.1.4.1
Load information table. Through this table, the load parameter can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, …
Column Syntax OID
hwLoadIndexLoop index: usually each DC output loop corresponds to a load.Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.4.1.1
hwLoadInfoAdminStateLoad operation.
Options:
1. on(1) - indicates that the Load is enabled
2. off(2) - indicates that the Load is disabled
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not s…
Enumerationr/w
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.4.1.2
hwLoadInfoOperStatusStatus of power supply.
Options:
1. normal(1) - indicates that the state of power supply is normal
2. abnormal(2) - indicates that the state of power supply is abnormal
3. stop(3) - indicates that the state …
Enumeration
Enumerated Values:
-1invalid
1normal
2abnormal
3stop
.1.3.6.1.4.1.2011.6.2.1.4.1.3
hwLoadCurrentPresent current .
Unit: mA
mAMeasuresRange.1.3.6.1.4.1.2011.6.2.1.4.1.4
hwLoadVoltagePresent voltage .
Unit: mV
mVMeasuresRange.1.3.6.1.4.1.2011.6.2.1.4.1.5
hwLoadVoltageHighOff voltage (Stop external voltage), in unit of mV,
When DC output voltage exceeds the value, the load will be automatically cut off.
Unit: mV
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.4.1.6
hwLoadLoadNameLoad name: usually each DC output loop corresponds to a load.SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.2011.6.2.1.4.1.7
hwLoadInfoRowStatusRowStatus standard operationSNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.4.1.8
hwLoadFuseStateLoad fuse state, including the auxiliary load fuse.
Options:
1. on(1) - indicates that the fuse is connected
2. off(2) - indicates that the fuse is disconnected
3. invalid(-1) - indicates that the device can …
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.4.1.9
hwLoadHoreIndexload hore indexInteger32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.4.1.10
.1.3.6.1.4.1.2011.6.2.1.5 · 1 row entry · 9 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRectifierTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRectifierTable'
Rectifier module table. 
Through this table, the status information of the rectifier module 
can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwRectifierIndex is the index of the monitored rectifier module under the power supply.
hwRectifierEntry row .1.3.6.1.4.1.2011.6.2.1.5.1
Rectifier module table.
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which …
Column Syntax OID
hwRectifierIndexRectifier Module index. There are multiple rectifier
modules to a power source.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.5.1.1
hwRectifierAdminStateSwitch operation of rectifier module.
Options:
1.on(1) - indicates that the Rectifier module is enabled
2.off(2) - indicates that the Rectifier module is disabled
3.invalid(-1) - indicates that the devic…
Enumerationr/w
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.5.1.2
hwRectifierOperStatePresent state, 5 and 6 respectively indicates the on/off state of the 48100 power device.
Options:
1. normal(1) - indicates that the Rectifier operation state is normal
2.…
Enumeration
Enumerated Values:
-1invalid
1normal
2fault
3protect
4communicationFailure
5on
6noConfig
7offline
8close
.1.3.6.1.4.1.2011.6.2.1.5.1.3
hwRectifierVoltageOutput voltage .
Unit: mV
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mVMeasuresRange.1.3.6.1.4.1.2011.6.2.1.5.1.4
hwRectifierCurrentOutput current .
Unit: mA
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mAMeasuresRange.1.3.6.1.4.1.2011.6.2.1.5.1.5
hwRectifierRowStatusRowStatus standard operationSNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.5.1.6
hwRectifierCurrentLimitcurrent limit switchSNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.2011.6.2.1.5.1.7
hwRectifierRunStateRunning state of rectifier module.
Options:
1.rectifierOn(0) - indicates that the module is on
2.averageCharge(1) - indicates that the module is being averagely charged.
3.output(2) - indicates that the mod…
Bits
Enumerated Values:
0rectifierOn
1averageCharge
2output
3isLimit
.1.3.6.1.4.1.2011.6.2.1.5.1.8
hwRectifierChargeStateCharging state of rectifier.
Options:
1. float(0) - indicates that the Charge state of Rectifier is float
2. average(1) - indicates that the Charge state of Rectifier is average
3. test(2) - indicates that t…
Enumeration
Enumerated Values:
0float
1average
2test
.1.3.6.1.4.1.2011.6.2.1.5.1.9
.1.3.6.1.4.1.2011.6.2.1.6.1 · 1 row entry · 15 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBatteryGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryGroupTable'
Basic information table of battery group. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit, 
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryGroupEntry row .1.3.6.1.4.1.2011.6.2.1.6.1.1
Basic information table of battery group.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by …
Column Syntax OID
hwBatteryGroupCapacityTotal capacity of the present battery group.
Unit: Ah
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.1.1.1
hwBatteryGroupCapcaityRemainTotal remain capacity of the present battery group .
invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
Unit: Ah
Integer32
Constraints:
range: -1-100
.1.3.6.1.4.1.2011.6.2.1.6.1.1.2
hwBatteryGroupsNumber of battery groupInteger32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.6.1.1.3
hwBatteryGroupVoltageLowWhen the voltage of the battery group is lower than the value set,
the battery group will no longer supply power. Its unit is mV.
Default: 43000
Unit: mV
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.6.1.1.4
hwBatteryGroupChargeLimitCharge limit point quotient, the product of which and the max capacity
of the battery group is the max charge current allowed.
Default: 15
Unit: percent
percentMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.6.1.1.5
hwBatteryGroupRowStatusRowStatus standard operationSNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.6.1.1.6
hwBatteryGroupOperStatusThe State of the battery supply which was connected with Power EMU.
To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal.
When the mains supply is ab…
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.1.1.7
hwBatteryGroupVoltageHighWhen the voltage of the battery group is higher than the value set, the battery group
will no longer supply power. Its unit is mV.
Default: 43000
Unit: mV
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.6.1.1.8
hwBatteryGroupTwiceOffVoltageThe twice off protection voltage of the battery group. Its unit is mV.
Default: 44000
Unit: mV
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.6.1.1.9
hwBatteryGroupProtectVoltageThe first off protection voltage of the battery,
whose default is 43V.
Default: 43000
Unit: mV
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.6.1.1.10
hwBatteryGroupTmpOffHighThe high temperature off protection point of the battery group,
whose default is 50 degrees centigrade.
Unit: 0.01 degree
0.01 degreeMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.6.1.1.11
hwBatteryInstallTimeThe installing date of battery group.SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.2011.6.2.1.6.1.1.12
hwBatteryGroupBomCodeThe BOM code of battery.
Invalid: null string.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2011.6.2.1.6.1.1.13
hwBatteryGroupTypeThe type of lead-acid battery.
1: general.
2: tcbc.
3: tcbb.
Enumerationr/w
Enumerated Values:
1general
2tcbc
3tcbb
.1.3.6.1.4.1.2011.6.2.1.6.1.1.14
hwLiBatteryGroupChargeLimitThe charge limit quotiety of the LiBattery.
SNMP uses it which has been enlarged 1000 by host.
user uses it which has been lessened 1000 by SNMP.
Default: 1050.
The invalid value -1 indicates that the device can not ge…
Integer32r/w
Constraints:
range: 50-1050
range: -1--1
.1.3.6.1.4.1.2011.6.2.1.6.1.1.15
.1.3.6.1.4.1.2011.6.2.1.6.2 · 1 row entry · 7 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwChargeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwChargeTable'
Charge management table. 
Through this table, the charging parameter of the battery can be set and queried. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwChargeEntry row .1.3.6.1.4.1.2011.6.2.1.6.2.1
Charge management table.
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit…
Column Syntax OID
hwChargeAdminStatusCharge management mode.
Options:
1. average(1) - indicates that the charge management mode is average charge
2. float(2) - indicates that the charge management mode is float charge
3. auto(3) - indicate…
Enumerationr/w
Enumerated Values:
-1invalid
1average
2float
3auto
.1.3.6.1.4.1.2011.6.2.1.6.2.1.1
hwChargeOperStatusCharge operation status.
Options:
1. average(1) - indicates that the charge operation state is average charge
2. float(2) - indicates that the charge operation state is float charge
3. full(3) - indicates that t…
Enumeration
Enumerated Values:
-1invalid
1average
2float
3full
4noCharge
5discharge
6sleep
.1.3.6.1.4.1.2011.6.2.1.6.2.1.2
hwAverageChargeVoltageVoltage value of average charge, in unit of mV.
Default: 56500
Unit: mV
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.6.2.1.3
hwFloatChargeVoltageVoltage value of float charge .
Default: 53500
Unit: mV
mVMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.6.2.1.4
hwChargeControlRowStatusRowStatus standard operationSNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.6.2.1.5
hwAverageChargeTimeTiming average charge time interval, effective range is 190 days.
Default :value is 60 days
Unit: day
daySNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.2.1.6
hwBatteryTmpRedeemingQuotietyTemperature redeeming quotient, used to set the co-relation
between the float charge voltage and the battery temperature.
It means How much will the float charge voltage decrease
with the increasing of every degree ce…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.2.1.7
.1.3.6.1.4.1.2011.6.2.1.6.3 · 1 row entry · 22 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBatteryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryTable'
Battery group state table. 
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. 
hwEnvEmuIndex is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryIndex is the index of the monitored battery group.
hwBatteryEntry row .1.3.6.1.4.1.2011.6.2.1.6.3.1
Battery group state table.
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index …
Column Syntax OID
hwBatteryIndexBattery group loop indexInteger32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.6.3.1.1
hwBatteryCapacityThe permitted max battery capacity of the battery group loop charge.
Unit: Ah
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.2
hwBatteryLoopStateThe battery group present status.
Options:
1. on(1) - indicates that the present state of battery group is on
2. off(2) - indicates that the present state of battery group is off
3. invalid(-1) - indicates…
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.3.1.3
hwBatteryVoltageThe loop voltage of the battery group.
Unit: mV
invalid: -1
mVMeasuresRange.1.3.6.1.4.1.2011.6.2.1.6.3.1.4
hwBatteryOperStatusThe present state of the battery group loop.
Options:
1. charge(1) - indicates that the present state of the battery group loop is charge
2. discharge(2) - indicates that the present state of the battery group loop i…
Enumeration
Enumerated Values:
-1invalid
1charge
2discharge
.1.3.6.1.4.1.2011.6.2.1.6.3.1.5
hwBatteryCurrentPresent current .
Unit: mA
invalid: -1
mAMeasuresRange.1.3.6.1.4.1.2011.6.2.1.6.3.1.6
hwBatteryTemperatureThe loop temperature of the battery group.
Unit: degree
Invaild:2147483647(0X7FFFFFFF)
degreeSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.7
hwBatteryRowStatusRowStatus standard operationSNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.6.3.1.8
hwBatteryCurrentHighThe over-current alarm point of the battery group.
Unit: mA
mAMeasuresRanger/w.1.3.6.1.4.1.2011.6.2.1.6.3.1.9
hwBatteryFuseStateBattery fuse state.
Options:
1. on(1) - indicates that the fuse is connected
2. off(2) - indicates that the fuse is disconnected
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU …
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.3.1.10
hwBatteryContactStateThe state of the battery contactor.
Options:
1. on(1) - indicates that the contactor is connected
2. off(2) - indicates that the contactor is disconnected
3. invalid(-1) - indicates that the device can not…
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.3.1.11
hwBatteryRemainCapacityRemain capacity of the battery,
invalid(-1)
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.12
hwBatteryProtectStateProtection status of the battery.
Options:
1. normal(1) - indicates that the Protection status of the battery is normal
2. overtemperature(2) - indicates that the Protection status of the battery is overte…
Enumeration
Enumerated Values:
1normal
2overtemperature
3overCurrent
.1.3.6.1.4.1.2011.6.2.1.6.3.1.13
hwBatteryVoltageStateVoltage state of Battery.
Options:
1. normal(1) - indicates that Voltage state of Battery is normal
2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage
3. belowVoltage(3) - indicat…
Enumeration
Enumerated Values:
1normal
2exceedVoltage
3belowVoltage
.1.3.6.1.4.1.2011.6.2.1.6.3.1.14
hwBatteryHardwareStateHardware State of Battery.
Options:
1. normal(1) - indicates that the hardware state of Battery is normal
2. fault(2) - indicates that the hardware state of Battery is fault
Enumeration
Enumerated Values:
1normal
2fault
.1.3.6.1.4.1.2011.6.2.1.6.3.1.15
hwBatteryLowTemperatureThe lowest loop temperature of the battery group.
Unit: degree
Invaild:2147483647(0X7FFFFFFF)
degreeSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.16
hwBatteryAntiTheftSwitchAnti-theft switch of Battery.
Options:
1. disable(1) - indicates that the anti-theft state of Battery is disabled
2. enable(2) - indicates that the anti-theft state of Battery is enabled
3. invalid(-1) - ind…
Enumerationr/w
Enumerated Values:
-1invalid
1disable
2enable
.1.3.6.1.4.1.2011.6.2.1.6.3.1.17
hwBatteryAntiTheftTimeoutThe anti-theft timeout time of battery.
The invalid value -1 indicates that the device can not get the value, e.g. the EMU does not support this operation.
hourInteger32r/w
Constraints:
range: 8-720
range: -1--1
.1.3.6.1.4.1.2011.6.2.1.6.3.1.18
hwBatterySequenceThe sequence of LiBattery.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.19
hwBatteryAddressThe address of LiBattery which corresponds to the subnode of LiBattery.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.20
hwBatteryHeaterStateThe state of battery heater.Enumeration
Enumerated Values:
-1invalid
1on
2off
3noconfig
.1.3.6.1.4.1.2011.6.2.1.6.3.1.21
hwBatteryHealthStateThe health state of battery.
Unit:%
invalid:-1
%Integer32
Constraints:
range: -1-100
.1.3.6.1.4.1.2011.6.2.1.6.3.1.22
.1.3.6.1.4.1.2011.6.2.1.6.4 · 1 row entry · 11 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBatteryTestTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryTestTable'
Battery test table. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex. 
hwEnvEmuIndex is the index of the monitored unit, 
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryTestEntry row .1.3.6.1.4.1.2011.6.2.1.6.4.1
Battery test table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Column Syntax OID
hwBatteryTestAdminStatusBattery test admin status.
Options:
1. start(1) - indicates that the Battery starts testing
2. terminate(2) - indicates that the Battery terminates testing
3. enableAutoTest(3) - indicates that th…
Enumerationr/w
Enumerated Values:
1start
2terminate
3enableAutoTest
4disableAutoTest
5timeautoTest
6offautoTest
7timeoffautoTest
.1.3.6.1.4.1.2011.6.2.1.6.4.1.1
hwBatteryTestAutoDischargePeriodAuto discharge test period.
Effective range is 30 -240 days.
Default: 120
Unit: day
daySNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.2
Test result:
Options:
1. testing(1) - indicates that the Battery test is in operation
2. complete(2) - indicates that the Battery test is completed normally
3. alarmTerminated(3) - indicates…
Enumeration
Enumerated Values:
1testing
2complete
3alarmTerminated
4hostTerminated
5overtimeTerminated
6normal
7supplyRecoverAutotestTerminated
.1.3.6.1.4.1.2011.6.2.1.6.4.1.3
Time of starting testSNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.2011.6.2.1.6.4.1.4
hwBatteryTestDurationBattery discharge test duration.
Effective range is 1-100 hours.
Default :value is 10 hours
Unit: hour
hourSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.5
hwBatteryTestTerminateVoltageBattery discharge test end voltage.
Effective range (DC lack alarm voltage+0.5V-voltage of floating charge).
Default: 45600
Unit: mV
mVSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.6
Total discharge AH.
Unit: mAH
mAHSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.7
hwBatteryTestOperStatusBattery discharge test operate status.
Options:
1. autoTestPermit(1) - indicates that auto discharge test is enabled
2. autoTestForbid(2) - indicates that auto discharge test is disabled
3. timeautoTestPer…
Enumeration
Enumerated Values:
1autoTestPermit
2autoTestForbid
3timeautoTestPermit
4offautoTestPermit
5timeoffautoTestPermit
.1.3.6.1.4.1.2011.6.2.1.6.4.1.8
hwBatteryTestPhaseBattery test phase.
Options:
1. charge(1) - indicates the batter test phase is charge
2. discharge(2) - indicates the batter test phase is discharge
3. record(3) - indicates the powe…
Enumeration
Enumerated Values:
1charge
2discharge
3record
4finish
5waitingfordischarge
.1.3.6.1.4.1.2011.6.2.1.6.4.1.9
hwBatteryTestStartHourDischarge start time.
Effective range is 0 23
Default: 0
Unit: hour
hourSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.10
hwBatteryTestAlarmThresholdThe battery discharge test alarm threshold in ratio of the range:1~79.percentSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.11
.1.3.6.1.4.1.2011.6.2.1.6.5 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBatteryLogTestTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryLogTestTable'
Battery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuIndex is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit. 
hwBatteryLogTestIndex is the index of the monitored battery.
hwBatteryLogTestEntry row .1.3.6.1.4.1.2011.6.2.1.6.5.1
Battery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuInd…
Column Syntax OID
hwBatteryLogTestIndexBattery discharge test result indexInteger32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.6.5.1.1
hwBatteryLogTestStartTimeBattery discharge test start timeSNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.2011.6.2.1.6.5.1.2
hwBatteryLogTestDischargeDurationDuration of discharge.
Unit: minute
minuteSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.3
hwBatteryLogTestTerminateVoltageEnd voltage of battery discharge test .
Unit: mV
mVSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.4
hwBatteryLogTestBatteryStatusBattery status.
Options:
1. expectant(1) - indicates the batter test state is expectant
2. unexpected(2) - indicates the batter test state is unexpected
3. unknown(3) - indicates the batter test state is unknown
Enumeration
Enumerated Values:
1expectant
2unexpected
3unknown
.1.3.6.1.4.1.2011.6.2.1.6.5.1.5
hwBatteryLogTestTotalDischargeAHDischarge cumulate AH.
Unit: mAH
mAHSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.6
hwBatteryLogTestFinishBattery Test result.
Options:
1. testing(1) - indicates that it is during testing
2. completed(2) - indicates that the test is completed normally
3. alarmTerminated(3) - indicates that the test is …
Enumeration
Enumerated Values:
1testing
2completed
3alarmTerminated
4hostTerminated
5overtimeTerminated
6notTest
7supplyRecoverAutotestTerminated
.1.3.6.1.4.1.2011.6.2.1.6.5.1.7
hwBatteryLogTestEfficiencyThe information of battery test efficiency.percentSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.8
hwBatteryLogTestBatteryTemperatureBattery discharge test end Temperature.
Unit: 0.01 Degree
Invaild: 0X7FFFFFFF
0.01 DegreeSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.9
hwBatteryLogTestBatteryCurrentBattery discharge test average Current.
Unit: mA
mASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.10
.1.3.6.1.4.1.2011.6.2.1.6.6 · 1 row entry · 3 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBatteryCellTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwBatteryCellTable'
The state of battery cell.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit. 
hwBatteryCellIndex is the index of the battery cell.
hwBatteryCellEntry row .1.3.6.1.4.1.2011.6.2.1.6.6.1
The state of battery cell.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by…
Column Syntax OID
hwBatteryCellIndexThe index of battery cell.Integer32
Constraints:
range: 0-15
.1.3.6.1.4.1.2011.6.2.1.6.6.1.1
hwBatteryCellTemperatureThe temperature of battery cell.
Unit: C
Non-value: 0x7FFFFFFF
CSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.6.1.2
hwBatteryCellVoltageThe voltage of battery cell.
Unit: mV
Non-value: -1
mVSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.6.1.3
.1.3.6.1.4.1.2011.6.2.1.7 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRemoteProvidePowerInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteProvidePowerInfoTable'
Remote provide power basic information table. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit, 
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwRemoteProvidePowerInfoEntry row .1.3.6.1.4.1.2011.6.2.1.7.1
Remote provide power basic information table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored…
Column Syntax OID
hwPowerCentralStateState of the central module.
Options:
1. normal(1) - indicates the normal state
2. temOver(2) - indicates the over-temperature
Enumeration
Enumerated Values:
1normal
2temOver
.1.3.6.1.4.1.2011.6.2.1.7.1.1
hwPowerCentralDCInPutStateState of central module DC input:
Options:
1.normal(1) - indicates the normal state
2.lack(2) - indicates the voltage underflow
3.over(3) - indicates the voltage overflow
Enumeration
Enumerated Values:
1normal
2lack
3over
.1.3.6.1.4.1.2011.6.2.1.7.1.2
hwPowerCentralDCOutputStateState of central module DC output.
Options:
1. normal(1) - indicates the normal state
2. volLack(2) - indicates the voltage underflow
3. volOver(3) - indicates the voltage overflow
4. loadOver(4) …
Enumeration
Enumerated Values:
1normal
2volLack
3volOver
4loadOver
5shortCircuit
6noLoad
.1.3.6.1.4.1.2011.6.2.1.7.1.3
hwPowerCentralDCOutputModeMode of central module DC output.
Options:
1. highVolMode(1) - indicates the high voltage output mode
2. lowVolMode(2) - indicates the low voltage output mode
Enumeration
Enumerated Values:
1highVolMode
2lowVolMode
.1.3.6.1.4.1.2011.6.2.1.7.1.4
hwPowerRemoteCommStateRemote power module communications state.
Options:
1. normal(1) - indicates the normal state
2. revfault(2) - indicates the receiving of fault
3. sendfault(3) - indicates the sending of fault
Enumerationr/w
Enumerated Values:
1normal
2revfault
3sendfault
.1.3.6.1.4.1.2011.6.2.1.7.1.5
hwPowerRemoteDCInputStateState of remote module DC input.
Options:
1. normal(1) - indicates the normal state
2. lack(2) - indicates that the voltage is underflow
Enumerationr/w
Enumerated Values:
1normal
2lack
.1.3.6.1.4.1.2011.6.2.1.7.1.6
hwPowerRemoteLineCurStatestate of line between central and remote module.
Options:
1.normal(1) - indicates the normal state
2.cablejoining(2) - indicates the cable joining
3.curLeakage(3) - indicates the cur Leakage
4.curOver(4) - …
Enumerationr/w
Enumerated Values:
1normal
2cablejoining
3curLeakage
4curOver
.1.3.6.1.4.1.2011.6.2.1.7.1.7
hwPowerRemotePowerStatestate of remote UA60 power.
Options:
1. normal(1) - indicates the normal state
2. fault(2) - indicates the faulty state
Enumerationr/w
Enumerated Values:
1normal
2fault
.1.3.6.1.4.1.2011.6.2.1.7.1.8
hwPowerRemoteLineStateState of line U1.
Options:
1. u1state(0) - indicates the power remote line state is u1 state
2. u2state(1) - indicates the power remote line state is u2 state
3. u3state(2) - indicates the power remote line state is u3 …
Bitsr/w
Enumerated Values:
0u1state
1u2state
2u3state
3u4state
4a1state
5a2state
6a3state
7a4state
.1.3.6.1.4.1.2011.6.2.1.7.1.9
hwPowerCentralLoadStatestate of central load.
Options:
1. normal(1) - indicates the normal state
2. overload(2) - indicates overload
3. nonload(3) - indicates non-load
Enumerationr/w
Enumerated Values:
1normal
2overload
3nonload
.1.3.6.1.4.1.2011.6.2.1.7.1.10
.1.3.6.1.4.1.2011.6.2.1.8 · 1 row entry · 6 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwACInfomationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwACInfomationTable'
AC infomation table.  The table is not supported.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwACInfomationEntry row .1.3.6.1.4.1.2011.6.2.1.8.1
AC infomation table. The table is not supported.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
Column Syntax OID
hwACInfoCommStatecommunication state of AC input module.
The node is not supported.
Options:
1. normal(0) - indicates the communication state of AC is normal
2. fault(1) - indicates the communication state of AC is fault
Enumeration
Enumerated Values:
0normal
1fault
.1.3.6.1.4.1.2011.6.2.1.8.1.1
hwACInfoThunderStateThunder's state.
The node is not supported.
Options:
1. normal(0) - indicates the state of Thunder is normal
2. fault(1) - indicates the state of Thunder is fault
Enumeration
Enumerated Values:
0normal
1fault
.1.3.6.1.4.1.2011.6.2.1.8.1.2
hwACInfoCurrentLoopCurrent AC input working loop.
The leaf is not supported.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.8.1.3
hwACInfoMCBTriggerAC input MCB trigger state.
The leaf is not supported.
Options:
1. normal(0) - indicates the AC input MCB trigger state is normal
2. breakDown(1)- indicates the AC input MCB trigger state is break-down
Enumeration
Enumerated Values:
0normal
1breakDown
.1.3.6.1.4.1.2011.6.2.1.8.1.4
hwACInfoFrequencyThe infomation of AC input frequency.
This leaf is not supported.
Unit: HZ
HZSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.8.1.5
hwACInfoRowStatusRowStatus standard operation
The leaf is not supported.
SNMPv2-TCRowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.2011.6.2.1.8.1.6
.1.3.6.1.4.1.2011.6.2.5.1 · 1 row entry · 4 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRemoteUnitSysInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteUnitSysInfoTable'
Remote power system, remote unit basic information table. The indexes of 
this entry is hwEnvEmuIndex.
hwRemoteUnitSysInfoEntry row .1.3.6.1.4.1.2011.6.2.5.1.1
Remote power system, remote unit basic information table. The indexes of
this entry is hwEnvEmuIndex.
Column Syntax OID
hwRemoteUnitPowerSystypeType of the remote unit power system.
Options:
1.rftv(1) - Type of the remote unit power system is RFT-V
2.rftc(2) - Type of the remote unit power system is RFT-C …
Enumeration
Enumerated Values:
1rftv
2rftc
255invalid
.1.3.6.1.4.1.2011.6.2.5.1.1.1
hwRemoteUnitDCOutputVolThe remote unit DC output voltage.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mVSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.1.1.2
hwRemoteUnitDCOutputCurThe remote unit DC output current.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.1.1.3
hwRemoteUnitSlotNumThe remote unit slot number.
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.1.1.4
.1.3.6.1.4.1.2011.6.2.5.2 · 1 row entry · 8 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRemoteUnitSlotTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteUnitSlotTable'
Remote power system, remote unit slot information table. The indexes of 
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
hwRemoteUnitSlotEntry row .1.3.6.1.4.1.2011.6.2.5.2.1
Remote power system, remote unit slot information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
Column Syntax OID
hwRemoteUnitSlotIndexThe remote unit slot index.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.1
hwRemoteUnitSlotCircuitNumThe remote unit slot circuit number.
Invalid:-1.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.2
hwRemoteUnitSlotHardVersionThe remote unit slot hard version.
Invalid: null string.
OctetString
Constraints:
range: 1-128
.1.3.6.1.4.1.2011.6.2.5.2.1.3
hwRemoteUnitSlotSoftVersionThe remote unit slot soft version.
Invalid: null string.
OctetString
Constraints:
range: 1-128
.1.3.6.1.4.1.2011.6.2.5.2.1.4
hwRemoteUnitSlotStatusThe state of the remote unit slot.
Options:
1.normal(1) - The state of the remote unit slot is normal
2.fault(2) - The state of the remote unit slot is fault
3.null(3) - The sta…
Enumeration
Enumerated Values:
1normal
2fault
3null
255invalid
.1.3.6.1.4.1.2011.6.2.5.2.1.5
hwRemoteUnitSlotAdminStatusDelete the remote unit slot.
Options:
1.delete(1) - Delete the remote unit slot
2.invalid(255) - Unknown
Enumerationr/w
Enumerated Values:
1delete
255invalid
.1.3.6.1.4.1.2011.6.2.5.2.1.6
hwRemoteUnitSlotDCOutputVolThe remote unit slot DC output voltage.
Invalid:-1.
mVSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.7
hwRemoteUnitSlotDCOutputCurThe remote unit slot DC output current.
Invalid:-1.
mASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.8
.1.3.6.1.4.1.2011.6.2.5.3 · 1 row entry · 4 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRemoteUnitCircuitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HUAWEI-POWER-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HUAWEI-POWER-MIB::hwRemoteUnitCircuitTable'
Remote power system, remote unit circuit information table. The indexes of 
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
hwRemoteUnitCircuitEntry row .1.3.6.1.4.1.2011.6.2.5.3.1
Remote power system, remote unit circuit information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
Column Syntax OID
hwRemoteUnitCircuitIndexThe remote unit circuit index.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.3.1.1
hwRemoteUnitCircuitInputVolThe remote unit circuit input voltage.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mVSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.3.1.2
hwRemoteUnitCircuitInputCurThe remote unit circuit input current.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.3.1.3
hwRemoteUnitCircuitStateThe state of the remote unit circuit.
Options:
1.normal(1) - The state of the remote unit circuit is normal
2.fault(2) - The state of the remote unit circuit is fault
3.null(3) -…
Enumeration
Enumerated Values:
1normal
2fault
3null
255invalid
.1.3.6.1.4.1.2011.6.2.5.3.1.4