INFORMATIONAL: Communication with a Rack PDU has been established.
The first argument is the serial number.
The second argument is the device name.
ePDUCommunicationLost
.1.3.6.1.4.1.3808.0.101
SEVERE: Communication with a Rack PDU has been lost.
The first argument is the serial number.
The second argument is the device name.
ePDUOutletOn
.1.3.6.1.4.1.3808.0.102
INFORMATIONAL: An outlet on a Switched Rack PDU has turned on.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
ePDUOutletOff
.1.3.6.1.4.1.3808.0.103
INFORMATIONAL: An outlet on a Switched Rack PDU has turned off.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
ePDUDeviceConfigChange
.1.3.6.1.4.1.3808.0.104
INFORMATIONAL: A device configuration change has been made on a
Rack PDU.
The first argument is the serial number.
The second argument is the device name.
ePDUOutletConfigChange
.1.3.6.1.4.1.3808.0.105
INFORMATIONAL: An outlet configuration change has been made on a
Switched Rack PDU.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
ePDULowLoad
.1.3.6.1.4.1.3808.0.106
WARNING: A Rack PDU has violated the low load threshold.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
ePDULowLoadCleared
.1.3.6.1.4.1.3808.0.107
INFORMATIONAL: The low load condition on a Rack PDU has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
ePDUNearOverload
.1.3.6.1.4.1.3808.0.108
WARNING: A Rack PDU is near an overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
ePDUNearOverloadCleared
.1.3.6.1.4.1.3808.0.109
INFORMATIONAL: The near overload condition on a Rack PDU has
been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
returnFromLowBattery
.1.3.6.1.4.1.3808.0.11
INFORMATIONAL: The UPS has returned from a low battery condition.
ePDUOverload
.1.3.6.1.4.1.3808.0.110
SEVERE: A Rack PDU is in an overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
ePDUOverloadCleared
.1.3.6.1.4.1.3808.0.111
INFORMATIONAL: The overload condition on a Rack PDU has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
ePDUDelayOutletOnCommand
.1.3.6.1.4.1.3808.0.112
INFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to turn on.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
ePDUDelayOutletOffCommand
.1.3.6.1.4.1.3808.0.113
INFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to turn off.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
ePDUDelayOutletRebootCommand
.1.3.6.1.4.1.3808.0.114
INFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to reboot.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
ePDUCancelPendingCommand
.1.3.6.1.4.1.3808.0.115
INFORMATIONAL: A cancel pending command has been made on a
Switched Rack PDU.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number (0 indicates all outlets).
The fourth argument is the outlet name (or device name if all outlets).
ePDULineUndervoltage
.1.3.6.1.4.1.3808.0.116
SEVERE: Utility Line Undervoltage
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
ePDULineUndervoltageCleared
.1.3.6.1.4.1.3808.0.117
INFORMATIONAL: Utility Line Undervoltage Cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
ePDULineOvervoltage
.1.3.6.1.4.1.3808.0.118
SEVERE: Utility Line Overvoltage.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
ePDULineOvervoltageCleared
.1.3.6.1.4.1.3808.0.119
INFORMATIONAL: Utility Line Overvoltage Cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
upsTurnedOff
.1.3.6.1.4.1.3808.0.12
WARNING: The UPS has been turned off.
ePDUPowerSupply1Fail
.1.3.6.1.4.1.3808.0.120
SEVERE: Power Supply 1 on Rack PDU is in FAIL state.
The first argument is the serial number.
The second argument is the device name.
ePDUPowerSupply1Ok
.1.3.6.1.4.1.3808.0.121
INFORMATIONAL: Power Supply 1 on Rack PDU is operating normally.
The first argument is the serial number.
The second argument is the device name.
ePDUPowerSupply2Fail
.1.3.6.1.4.1.3808.0.122
SEVERE: Power Supply 2 on Rack PDU is in FAIL state.
The first argument is the serial number.
The second argument is the device name.
ePDUPowerSupply2Ok
.1.3.6.1.4.1.3808.0.123
INFORMATIONAL: Power Supply 2 on Rack PDU is operating normally.
The first argument is the serial number.
The second argument is the device name.
ePDUBankLowLoad
.1.3.6.1.4.1.3808.0.124
WARNING: A Rack PDU bank has violated the low load threshold.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank number.
ePDUBankLowLoadCleared
.1.3.6.1.4.1.3808.0.125
INFORMATIONAL: The low load condition on a Rack PDU bank has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank number.
ePDUBankNearOverload
.1.3.6.1.4.1.3808.0.126
WARNING: A Rack PDU bank is near an overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank number.
ePDUBankNearOverloadCleared
.1.3.6.1.4.1.3808.0.127
INFORMATIONAL: The near overload condition on a Rack PDU bank has
been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase/bank number.
ePDUBankOverload
.1.3.6.1.4.1.3808.0.128
SEVERE: A Rack PDU bank is in an overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank number.
ePDUBankOverloadCleared
.1.3.6.1.4.1.3808.0.129
INFORMATIONAL: The overload condition on a Rack PDU bank has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank number.
upsSleeping
.1.3.6.1.4.1.3808.0.13
WARNING: The UPS entered sleep mode. Output power will not be provided.
ePDUComponentCommunicationEstablished
.1.3.6.1.4.1.3808.0.130
INFORMATIONAL: Component communication lost has been cleared.
The first argument is the serial number.
The second argument is the device name.
ePDUComponentCommunicationLost
.1.3.6.1.4.1.3808.0.131
SEVERE: Component communication lost.
The first argument is the serial number.
The second argument is the device name.
ePDUOutletLowLoad
.1.3.6.1.4.1.3808.0.132
WARNING: A Rack PDU has violated the outlet low load threshold.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
The fourth argument is the outlet name.
ePDUOutletLowLoadCleared
.1.3.6.1.4.1.3808.0.133
INFORMATIONAL: The outlet low load condition on a Rack PDU has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
The fourth argument is the outlet name.
ePDUOutletNearOverload
.1.3.6.1.4.1.3808.0.134
WARNING: A Rack PDU is near an outlet overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
The fourth argument is the outlet name.
ePDUOutletNearOverloadCleared
.1.3.6.1.4.1.3808.0.135
INFORMATIONAL: The outlet near overload condition on a Rack PDU has
been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
The fourth argument is the outlet name.
ePDUOutletOverload
.1.3.6.1.4.1.3808.0.136
SEVERE: A Rack PDU is in an overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
The fourth argument is the outlet name.
ePDUOutletOverloadCleared
.1.3.6.1.4.1.3808.0.137
INFORMATIONAL: The outlet overload condition on a Rack PDU has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
The fourth argument is the outlet name.
upsWokeUp
.1.3.6.1.4.1.3808.0.14
INFORMATION: The UPS woke up from sleep mode. Output power is being provided.
upsRebootStarted
.1.3.6.1.4.1.3808.0.15
WARNING: The UPS started reboot sequence.
upsOverTemp
.1.3.6.1.4.1.3808.0.16
SEVERE: The UPS inner temperature is too high.
returnFromOverTemp
.1.3.6.1.4.1.3808.0.17
INFORMATIONAL: The UPS over temperature condition cleared.
upsBuckOn
.1.3.6.1.4.1.3808.0.18
WARNING: The UPS has enabled buck, high utility voltage.
returnFromOverLoad
.1.3.6.1.4.1.3808.0.19
INFORMATIONAL: The UPS has returned from an overload condition.
upsOverload
.1.3.6.1.4.1.3808.0.2
SEVERE: The UPS has sensed an overload condition.
returnFromDischarged
.1.3.6.1.4.1.3808.0.20
INFORMATIONAL: The UPS runtime estimation completed.
envHighTemperatureViolation
.1.3.6.1.4.1.3808.0.200
WARNING: The environment high temperature threshold has been violated.
envHighTemperatureBack
.1.3.6.1.4.1.3808.0.201
INFORMATION: The environment temperature returned from high value.
envLowTemperatureViolation
.1.3.6.1.4.1.3808.0.202
WARNING: The environment low temperature threshold has been violated.
envLowTempBack
.1.3.6.1.4.1.3808.0.203
INFORMATION: The environment temperature returned from low value.
envHighHumidityViolation
.1.3.6.1.4.1.3808.0.204
WARNING: The environment high humidity threshold has been violated.
envHighHumidityBack
.1.3.6.1.4.1.3808.0.205
INFORMATION: The environment humidity return from high value.
envLowHumidityViolation
.1.3.6.1.4.1.3808.0.206
WARNING: The environment low humidity threshold has been violated.
envLowHumdBack
.1.3.6.1.4.1.3808.0.207
INFORMATION: The environment humidity return from low value.
envDryContactAbnormal
.1.3.6.1.4.1.3808.0.208
INFORMATION: The Contact is abnormal.
envDryContactNormal
.1.3.6.1.4.1.3808.0.209
INFORMATION: The Contact has returned from abnormal.
upsScheduleShutdown
.1.3.6.1.4.1.3808.0.21
WARNING: The UPS has started its schedule shutdown sequence.
envConntected
.1.3.6.1.4.1.3808.0.210
INFORMATION: The Environment Sensor has been connected.
envDisconntected
.1.3.6.1.4.1.3808.0.211
INFORMATION: The Environment Sensor has been disconnected.
envRateOfTemperatureChangeAbnormal
.1.3.6.1.4.1.3808.0.212
INFORMATION: The rate of temperature change is abnormal.
envRateOfHumdChangeAbnormal
.1.3.6.1.4.1.3808.0.213
INFORMATION: The rate of humidity change is abnormal.
upsEnterSleep
.1.3.6.1.4.1.3808.0.22
WARNING: The UPS started sleep sequence.
upsChargerFailure
.1.3.6.1.4.1.3808.0.23
WARNING: The battery charger is abnormal.
returnFromChargerFailure
.1.3.6.1.4.1.3808.0.24
INFORMATIONAL: The charger returned from a failure condition.
upsTurnoffStarted
.1.3.6.1.4.1.3808.0.25
WARNING: The UPS started turn off sequence.
accessoryDeviceEvent
.1.3.6.1.4.1.3808.0.250
INFORMATIONAL: An accessory event has been happened.
accessoryDeviceAlarm
.1.3.6.1.4.1.3808.0.251
Alarm: An accessory alarm has been detected.
accessoryDeviceAlarmClear
.1.3.6.1.4.1.3808.0.252
INFORMATIONAL: An accessory alarm has been cleared.
envTemperatureEvent
.1.3.6.1.4.1.3808.0.253
INFORMATIONAL: An environment sensor Temperature event has been happened.
The first argument is the sensor serial number.
The second argument is the sensor name.
The third argument is the sensor location.
The foutrh argument is the temperture table index.
The fifth argument is the temperture.
envTemperatureAlarm
.1.3.6.1.4.1.3808.0.254
Alarm: An environment sensor Temperature alarm has been detected.
The first argument is the sensor serial number.
The second argument is the sensor name.
The third argument is the sensor location.
The foutrh argument is the temperture table index.
The fifth argument is the temperture.
envTemperatureAlarmClear
.1.3.6.1.4.1.3808.0.255
INFORMATIONAL: An environment sensor Temperature alarm has been cleared.
The first argument is the sensor serial number.
The second argument is the sensor name.
The third argument is the sensor location.
The foutrh argument is the temperture table index.
The fifth argument is the temperture.
envHumidityEvent
.1.3.6.1.4.1.3808.0.256
INFORMATIONAL: An environment sensor Humidity event has been happened.
The first argument is the sensor serial number.
The second argument is the sensor name.
The third argument is the sensor location.
The foutrh argument is the humidity table index.
The fifth argument is the humidity.
envHumidityAlarm
.1.3.6.1.4.1.3808.0.257
Alarm: An environment sensor Humidity alarm has been detected.
The first argument is the sensor serial number.
The second argument is the sensor name.
The third argument is the sensor location.
The foutrh argument is the humidity table index.
The fifth argument is the humidity.
envHumidityAlarmClear
.1.3.6.1.4.1.3808.0.258
INFORMATIONAL: An environment sensor Humidity alarm has been cleared.
The first argument is the sensor serial number.
The second argument is the sensor name.
The third argument is the sensor location.
The foutrh argument is the humidity table index.
The fifth argument is the humidity.
envContactEvent
.1.3.6.1.4.1.3808.0.259
INFORMATIONAL: An environment sensor Contact event has been happened.
The first argument is the sensor serial number.
The second argument is the sensor name.
The third argument is the sensor location.
The foutrh argument is the contect table index.
The fifth argument is the contact name.
upsTurnedOn
.1.3.6.1.4.1.3808.0.26
WARNING: The UPS has been turned on.
envContactAlarm
.1.3.6.1.4.1.3808.0.260
Alarm: An environment sensor Contact alarm has been detected.
The first argument is the sensor serial number.
The second argument is the sensor name.
The third argument is the sensor location.
The foutrh argument is the contect table index.
The fifth argument is the contact name.
envContactAlarmClear
.1.3.6.1.4.1.3808.0.261
INFORMATIONAL: An environment sensor Contact alarm has been cleared.
The first argument is the sensor serial number.
The second argument is the sensor name.
The third argument is the sensor location.
The foutrh argument is the contect table index.
The fifth argument is the contact name.
upsRemoteCommandFailed
.1.3.6.1.4.1.3808.0.27
WARNING: The UPS remote command failed.
upsLostRedundant
.1.3.6.1.4.1.3808.0.28
WARNING: Not enough power redundancy modules.
upsSignalClientShutdown
.1.3.6.1.4.1.3808.0.29
SEVERE: The UPS has signaled clients to shutdown.
upsDiagnosticsFailed
.1.3.6.1.4.1.3808.0.3
SEVERE: The UPS battery test failed.
upsEmergencyPowerOff
.1.3.6.1.4.1.3808.0.30
Emergency Power Off (EPO)
atsSwitchSource
.1.3.6.1.4.1.3808.0.301
INFORMATIONAL: ATS has switched source.
The first argument is the device name.
The second argument is the serial number.
The third argument is the selected source.
atsSourceFault
.1.3.6.1.4.1.3808.0.302
WARNING: Source fault occurs.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
atsSourceFaultCleared
.1.3.6.1.4.1.3808.0.303
INFORMATIONAL: Source fault has been cleared.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
atsRedundancyFail
.1.3.6.1.4.1.3808.0.304
WARNING: Redundancy fails.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
atsRedundancyRestored
.1.3.6.1.4.1.3808.0.305
INFORMATIONAL: Redundancy has been restored.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
atsInputHighVoltage
.1.3.6.1.4.1.3808.0.306
WARNING: The upper voltage limit has been crossed.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
The fourth argument is the phase voltage.
atsInputHighVoltageCleared
.1.3.6.1.4.1.3808.0.307
INFORMATIONAL: The upper voltage condition has been cleared.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
The fourth argument is the phase voltage.
atsInputLowVoltage
.1.3.6.1.4.1.3808.0.308
WARNING: The lower voltage limit has been crossed.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
The fourth argument is the phase voltage.
atsInputLowVoltageCleared
.1.3.6.1.4.1.3808.0.309
INFORMATIONAL: The lower voltage condition has been cleared.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
The fourth argument is the phase voltage.
nclBankOn
.1.3.6.1.4.1.3808.0.31
INFORMATIONAL: Non-Critical bank has been turned on.
atsInputHighFrequency
.1.3.6.1.4.1.3808.0.310
WARNING: The upper frequency limit has been crossed.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
The fourth argument is the input frequency.
atsInputHighFrequencyCleared
.1.3.6.1.4.1.3808.0.311
INFORMATIONAL: The upper frequency condition has been cleared.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
The fourth argument is the input frequency.
atsInputLowFrequency
.1.3.6.1.4.1.3808.0.312
WARNING: The lower frequency limit has been crossed.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
The fourth argument is the input frequency.
atsInputLowFrequencyCleared
.1.3.6.1.4.1.3808.0.313
INFORMATIONAL: The lower frequency condition has been cleared.
The first argument is the device name.
The second argument is the serial number.
The third argument is the source name.
The fourth argument is the input frequency.
atsCommunicationLost
.1.3.6.1.4.1.3808.0.314
MAJOR: ATS communication lost.
The first argument is the device name.
The second argument is the serial number.
atsCommunicationEstablished
.1.3.6.1.4.1.3808.0.315
INFORMATIONAL: ATS communication has been established.
The first argument is the device name.
The second argument is the serial number.
atsLCDCommunicationLost
.1.3.6.1.4.1.3808.0.316
WARNING: LCD communication lost.
The first argument is the device name.
The second argument is the serial number.
atsLCDCommunicationLostCleared
.1.3.6.1.4.1.3808.0.317
INFORMATIONAL: LCD communication lost has been cleared.
The first argument is the device name.
The second argument is the serial number.
atsDB9CommunicationLost
.1.3.6.1.4.1.3808.0.318
WARNING: DB9 communication lost.
The first argument is the device name.
The second argument is the serial number.
atsDB9CommunicationLostCleared
.1.3.6.1.4.1.3808.0.319
INFORMATIONAL: DB9 communication lost has been cleared.
The first argument is the device name.
The second argument is the serial number.
nclBankOff
.1.3.6.1.4.1.3808.0.32
INFORMATIONAL: Non-Critical bank has been turned off.
atsPowerSupplyFault
.1.3.6.1.4.1.3808.0.320
CRITICAL: Power supply failure.
The first argument is the device name.
The second argument is the serial number.
The third argument is the input source of the power supply.
atsPowerSupplyFaultCleared
.1.3.6.1.4.1.3808.0.321
CRITICAL: Power supply failure.
The first argument is the device name.
The second argument is the serial number.
The third argument is the input source of the power supply.
atsDevHardwareFault
.1.3.6.1.4.1.3808.0.322
CRITICAL: Device hardware failure.
The first argument is the device name.
The second argument is the serial number.
atsDevHardwareFaultCleared
.1.3.6.1.4.1.3808.0.323
INFORMATIONAL: Device hardware failure has been cleared.
The first argument is the device name.
The second argument is the serial number.
atsSourceConfigChanged
.1.3.6.1.4.1.3808.0.324
INFORMATIONAL: A source configuration change has been made.
The first argument is the device name.
The second argument is the serial number.
atsDeviceConfigChanged
.1.3.6.1.4.1.3808.0.325
INFORMATIONAL: A device configuration change has been made.
The first argument is the device name.
The second argument is the serial number.
atsOutletConfigChanged
.1.3.6.1.4.1.3808.0.326
INFORMATIONAL: A outlet configuration change has been made.
The first argument is the device name.
The second argument is the serial number.
atsEventCountsCleared
.1.3.6.1.4.1.3808.0.327
INFORMATIONAL: Event counts has been cleared.
The first argument is the device name.
The second argument is the serial number.
atsOverload
.1.3.6.1.4.1.3808.0.328
WARNING: The load has exceeded overload threshold.
The first argument is the device name.
The second argument is the serial number.
The third argument is the bank number.
The third argument is the load.
atsOverloadCleared
.1.3.6.1.4.1.3808.0.329
INFORMATIONAL: The overload condition has been cleared.
The first argument is the device name.
The second argument is the serial number.
The third argument is the bank number.
The third argument is the load.
upsCommandCancel
.1.3.6.1.4.1.3808.0.33
INFORMATION: The cancel command has been executed.
atsNearOverload
.1.3.6.1.4.1.3808.0.330
WARNING: The load has exceeded near overload threshold.
The first argument is the device name.
The second argument is the serial number.
The third argument is the bank number.
The third argument is the load.
atsNearOverloadCleared
.1.3.6.1.4.1.3808.0.331
INFORMATIONAL: The near overload condition has beed cleared.
The first argument is the device name.
The second argument is the serial number.
The third argument is the bank number.
The third argument is the load.
atsLowLoad
.1.3.6.1.4.1.3808.0.332
WARNING: The load has been lower than low load threshold.
The first argument is the device name.
The second argument is the serial number.
The third argument is the bank number.
The third argument is the load.
atsLowLoadCleared
.1.3.6.1.4.1.3808.0.333
INFORMATIONAL: The low load condition has been cleared.
The first argument is the device name.
The second argument is the serial number.
The third argument is the bank number.
The third argument is the load.
atsOutletOnCommand
.1.3.6.1.4.1.3808.0.334
INFORMATIONAL: An outlet on ATS has been assigned to turn on.
The first argument is the device name.
The second argument is the serial number.
The third argument is the outlet index number.
The fourth argument is the outlet name.
atsOutletOffCommand
.1.3.6.1.4.1.3808.0.335
INFORMATIONAL: An outlet on ATS has been assigned to turn off.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
atsOutletRebootCommand
.1.3.6.1.4.1.3808.0.336
INFORMATIONAL: An outlet on ATS has been assigned to reboot.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
atsCancelPendingCommand
.1.3.6.1.4.1.3808.0.337
INFORMATIONAL: A cancel pending command has been made on ATS.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number (0 indicates all outlets).
The fourth argument is the outlet name (or device name if all outlets).
atsOutletOn
.1.3.6.1.4.1.3808.0.338
INFORMATIONAL: An outlet on ATS has turned on.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
atsOutletOff
.1.3.6.1.4.1.3808.0.339
INFORMATIONAL: An outlet on ATS has turned off.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
upsStartBatteryTest
.1.3.6.1.4.1.3808.0.34
INFORMATION: The UPS has started a battery test process.
upsRemainRuntimeLowThanThreshold
.1.3.6.1.4.1.3808.0.35
WARNING: The UPS remaining runtime is lower than threshold.
nclBankStartScheduleOff
.1.3.6.1.4.1.3808.0.36
INFORMATION: Non-Critial bank has started its schedule off sequence.
upsEstimationAbort
.1.3.6.1.4.1.3808.0.37
WARNING: The UPS runtime estimation aborted.
upsHardwareFault
.1.3.6.1.4.1.3808.0.38
WARNING: The UPS hardware fault.
upsBatteryNotPresent
.1.3.6.1.4.1.3808.0.39
WARNING: Battery is not present.
upsDischarged
.1.3.6.1.4.1.3808.0.4
SEVERE: The UPS has started a runtime estimation process.
upsWiringFault
.1.3.6.1.4.1.3808.0.40
WARNING: The UPS wiring fault has been detected.
pduDeviceEvent
.1.3.6.1.4.1.3808.0.400
INFORMATIONAL: A PDU device event has been happened.
The first argument is the serial number.
The second argument is the device name.
The third argument is the device table index.
pduDeviceAlarm
.1.3.6.1.4.1.3808.0.401
Alarm: A PDU device alarm has been detected.
The first argument is the serial number.
The second argument is the device name.
The third argument is the device table index.
pduDeviceAlarmClear
.1.3.6.1.4.1.3808.0.402
INFORMATIONAL: A PDU device alarm has been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the device table index.
pduPhaseEvent
.1.3.6.1.4.1.3808.0.403
INFORMATIONAL: A PDU phase event has been happened.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase table index.
The foutrh argument is the phase number.
pduPhaseAlarm
.1.3.6.1.4.1.3808.0.404
Alarm: A PDU phase alarm has been detected.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase table index.
The foutrh argument is the phase number.
pduPhaseAlarmClear
.1.3.6.1.4.1.3808.0.405
INFORMATIONAL: A PDU phase alarm has been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase table index.
The foutrh argument is the phase number.
pduBankEvent
.1.3.6.1.4.1.3808.0.406
INFORMATIONAL: A PDU bank event has been happened.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank table index.
The foutrh argument is the bank number.
pduBankAlarm
.1.3.6.1.4.1.3808.0.407
Alarm: A PDU bank alarm has been detected.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank table index.
The foutrh argument is the bank number.
pduBankAlarmClear
.1.3.6.1.4.1.3808.0.408
INFORMATIONAL: A PDU bank alarm has been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank table index.
The foutrh argument is the bank number.
pduOutletSwitchedEvent
.1.3.6.1.4.1.3808.0.409
INFORMATIONAL: A PDU switched outlet event has been happened.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet table index.
The foutrh argument is the outlet number.
The fifth argument is the outlet name.
upsWiringFaultCleared
.1.3.6.1.4.1.3808.0.41
INFORMATION: The UPS wiring fault has been cleared.
pduOutletSwitchedAlarm
.1.3.6.1.4.1.3808.0.410
Alarm: A PDU switched outlet alarm has been detected.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet table index.
The foutrh argument is the outlet number.
The fifth argument is the outlet name.
pduOutletSwitchedAlarmClear
.1.3.6.1.4.1.3808.0.411
INFORMATIONAL: A PDU switched outlet alarm has been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet table index.
The foutrh argument is the outlet number.
The fifth argument is the outlet name.
pduOutletMeteredEvent
.1.3.6.1.4.1.3808.0.412
INFORMATIONAL: A PDU metered outlet event has been happened.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet table index.
The foutrh argument is the outlet number.
The fifth argument is the outlet name.
pduOutletMeteredAlarm
.1.3.6.1.4.1.3808.0.413
Alarm: A PDU metered outlet alarm has been detected.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet table index.
The foutrh argument is the outlet number.
The fifth argument is the outlet name.
pduOutletMeteredAlarmClear
.1.3.6.1.4.1.3808.0.414
INFORMATIONAL: A PDU metered outlet alarm has been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet table index.
The foutrh argument is the outlet number.
The fifth argument is the outlet name.
pduDaisyChainEvent
.1.3.6.1.4.1.3808.0.415
INFORMATIONAL: A PDU daisy-chain event has been happened.
The first argument is the host serial number.
The second argument is the host device name.
The third argument is the event device table index.
The foutrh argument is the event device serial number.
The fifth argument is the event device name.
pduDaisyChainAlarm
.1.3.6.1.4.1.3808.0.416
Alarm: A PDU daisy-chain alarm has been detected.
The first argument is the host serial number.
The second argument is the host device name.
The third argument is the alarm device table index.
The foutrh argument is the alarm device serial number.
The fifth argument is the alarm device name.
pduDaisyChainAlarmClear
.1.3.6.1.4.1.3808.0.417
INFORMATIONAL: A PDU daisy-chain alarm has been cleared.
The first argument is the host serial number.
The second argument is the host device name.
The third argument is the alarm device table index.
The foutrh argument is the alarm deice serial number.
The fifth argument is the alarm device name.
pduOutletMonitoredEvent
.1.3.6.1.4.1.3808.0.418
INFORMATIONAL: A PDU metered outlet event has been happened.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet table index.
The foutrh argument is the outlet number.
The fifth argument is the outlet name.
pduSourceEvent
.1.3.6.1.4.1.3808.0.419
INFORMATIONAL: A ATS source event has been happened.
The first argument is the serial number.
The second argument is the device name.
The third argument is the source table index.
upsEnterBypassMode
.1.3.6.1.4.1.3808.0.42
WARNING: The UPS enters bypass mode.
pduSourceAlarm
.1.3.6.1.4.1.3808.0.420
INFORMATIONAL: A ATS source alarm has been detected.
The first argument is the serial number.
The second argument is the device name.
The third argument is the source table index.
pduSourceAlarmClear
.1.3.6.1.4.1.3808.0.421
INFORMATIONAL: A ATS source alarm has been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the source table index.
upsReturnFromBypassMode
.1.3.6.1.4.1.3808.0.43
INFORMATION: The UPS leaves bypass mode.
upsBypassOverload
.1.3.6.1.4.1.3808.0.44
WARNING: The UPS bypass overload.
upsBypassOverloadCleared
.1.3.6.1.4.1.3808.0.45
INFORMATION: The UPS bypass overload has been cleared.
upsEnterECOMode
.1.3.6.1.4.1.3808.0.46
WARNING: The UPS enters ECO mode.
upsReturnFromECOMode
.1.3.6.1.4.1.3808.0.47
WARNING: The UPS leaves ECO mode.
upsBatteryOverThreeYear
.1.3.6.1.4.1.3808.0.48
WARNING: Battery has been 3 years from last Replacement.
upsBatteryExpiration
.1.3.6.1.4.1.3808.0.49
WARNING: The battery may not work well anymore.
upsOnBattery
.1.3.6.1.4.1.3808.0.5
WARNING: Utility power failed, transfer to backup mode.
upsBatteryReplacement
.1.3.6.1.4.1.3808.0.50
WARNING: The battery has been replaced.
upsOutletOn
.1.3.6.1.4.1.3808.0.500
INFORMATIONAL: An outlet has turned on.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
upsOutletOff
.1.3.6.1.4.1.3808.0.501
INFORMATIONAL: An outlet has turned off.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
upsOutletOnCommand
.1.3.6.1.4.1.3808.0.502
INFORMATIONAL: An outlet has been assigned to turn on.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
upsOutletOffCommand
.1.3.6.1.4.1.3808.0.503
INFORMATIONAL: An outlet has been assigned to turn off.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
upsOutletRebootCommand
.1.3.6.1.4.1.3808.0.504
INFORMATIONAL: An outlet has been assigned to reboot.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
upsCancelPendingCommand
.1.3.6.1.4.1.3808.0.505
INFORMATIONAL: A cancel pending command has been made on an outlet.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
upsAutoPingFail
.1.3.6.1.4.1.3808.0.506
SEVERE: AutoPing failed.
upsAutoPingRecovery
.1.3.6.1.4.1.3808.0.507
INFORMATIONAL: AutoPing recovered.
upsModuleInvertorAlarm
.1.3.6.1.4.1.3808.0.51
WARNING: The UPS module invertor alarm.
upsModuleRectifierAlarm
.1.3.6.1.4.1.3808.0.52
WARNING: The UPS module rectifier alarm.
upsModuleFanAlarm
.1.3.6.1.4.1.3808.0.53
WARNING: The UPS module fan alarm.
upsModuleManualShutdown
.1.3.6.1.4.1.3808.0.54
WARNING: The UPS module manual shutdown.
upsModuleOverload
.1.3.6.1.4.1.3808.0.55
WARNING: The UPS module overload.
upsFirmwareUpgradeStart
.1.3.6.1.4.1.3808.0.56
WARNING: UPS firmware starts to update.
upsFirmwareUpgradeEnd
.1.3.6.1.4.1.3808.0.57
WARNING: UPS firmware update is over.
upsRFC1628TrapOnBattery
.1.3.6.1.4.1.3808.0.58
WARNING: RFC1628: UPS is on battery.
upsRFC1628TrapTestCompleted
.1.3.6.1.4.1.3808.0.59
WARNING: RFC1628: UPS test completed.
upsBoostOn
.1.3.6.1.4.1.3808.0.6
WARNING: The UPS has enabled boost, low utility voltage.
upsRFC1628TrapAlarmEntryAdded
.1.3.6.1.4.1.3808.0.60
WARNING: RFC1628: Alarm entry added.
bmSystemAlarm
.1.3.6.1.4.1.3808.0.600
ALARM: System alarm occurance.
The first argument is the bm device serial number.
The second argument is the bm system identification name.
The third argument is the bm system location.
The fourth argument is the alarm event specific identifier.
The fifth argument is the trap information string.
bmSystemWarning
.1.3.6.1.4.1.3808.0.601
WARNING: System warning occurance.
The first argument is the bm device serial number.
The second argument is the bm system identification name.
The third argument is the bm system location.
The fourth argument is the alarm event specific identifier.
The fifth argument is the trap information string.
bmSystemInfo
.1.3.6.1.4.1.3808.0.602
INFO: System information.
The first argument is the bm device serial number.
The second argument is the bm system identification name.
The third argument is the bm system location.
The fourth argument is the alarm event specific identifier.
The fifth argument is the trap information string.
bmProbesAlarm
.1.3.6.1.4.1.3808.0.603
ALARM: Probe alarm event.
The first argument is the bm device serial number.
The second argument is the bm system identification name.
The third argument is the bm system location.
The fourth argument is the string index the probe located.
The fifth argument is the battery index the probe located.
The sixth argument is the alarm event specific identifier.
The seventh argument is the trap information string.
bmSProbesWarning
.1.3.6.1.4.1.3808.0.604
WARNING: Probe warning event.
The first argument is the bm device serial number.
The second argument is the bm system identification name.
The third argument is the bm system location.
The fourth argument is the string index the probe located.
The fifth argument is the battery index the probe located.
The sixth argument is the alarm event specific identifier.
The seventh argument is the trap information string.
bmProbesInfo
.1.3.6.1.4.1.3808.0.605
INFO: Probe information.
The first argument is the bm device serial number.
The second argument is the bm system identification name.
The third argument is the bm system location.
The fourth argument is the string index the probe located.
The fifth argument is the battery index the probe located.
The sixth argument is the alarm event specific identifier.
The seventh argument is the trap information string.
bmStringsAlarm
.1.3.6.1.4.1.3808.0.606
ALARM: String alarm event.
The first argument is the bm device serial number.
The second argument is the bm system identification name.
The third argument is the bm system location.
The fourth argument is the string index.
The fifth argument is the alarm event specific identifier.
The sixth argument is the trap information string.
bmStringsWarning
.1.3.6.1.4.1.3808.0.607
WARNING: String warning event.
The first argument is the bm device serial number.
The second argument is the bm system identification name.
The third argument is the bm system location.
The fourth argument is the string index.
The fifth argument is the alarm event specific identifier.
The sixth argument is the trap information string.
bmStringsInfo
.1.3.6.1.4.1.3808.0.608
INFO: String info event.
The first argument is the bm device serial number.
The second argument is the bm system identification name.
The third argument is the bm system location.
The fourth argument is the string index.
The fifth argument is the alarm event specific identifier.
The sixth argument is the trap information string.
failAuthViaHTTP
.1.3.6.1.4.1.3808.0.61
WARNING: Login authorization failure via HTTP.
passwordChange
.1.3.6.1.4.1.3808.0.62
INFORMATION: The password has been changed.
failAuthViaConsole
.1.3.6.1.4.1.3808.0.63
WARNING: Login authorization failure via Console.
configFileUpload
.1.3.6.1.4.1.3808.0.64
INFORMATION: Configuration file uploaded.
adminLoginInfo
.1.3.6.1.4.1.3808.0.65
INFORMATION: Administrator login.
adminLogoutInfo
.1.3.6.1.4.1.3808.0.66
INFORMATION: Administrator logout.
deviceLoginInfo
.1.3.6.1.4.1.3808.0.67
INFORMATION: Device login.
deviceLogoutInfo
.1.3.6.1.4.1.3808.0.68
INFORMATION: Device logout.
configurationChanged
.1.3.6.1.4.1.3808.0.69
INFORMATION: Configuration has been changed.
lowBattery
.1.3.6.1.4.1.3808.0.7
SEVERE: The UPS battery capacity is low than threshold, soon to be exhausted.
clientRegistered
.1.3.6.1.4.1.3808.0.70
Information: PowerPanel client has been registered.
currProbesAlarm
.1.3.6.1.4.1.3808.0.700
ALARM: Current probe alarm event.
The first argument is the system identification name.
The second argument is the system location.
The third argument is the alarm event specific identifier.
The fourth argument is the trap information string.
currProbesWarning
.1.3.6.1.4.1.3808.0.701
Warning: Current probe warning event.
The first argument is the system identification name.
The second argument is the system location.
The third argument is the alarm event specific identifier.
The fourth argument is the trap information string.
currProbesInfo
.1.3.6.1.4.1.3808.0.702
Info: Current probe info event.
The first argument is the system identification name.
The second argument is the system location.
The third argument is the alarm event specific identifier.
The fourth argument is the trap information string.
clientRemoved
.1.3.6.1.4.1.3808.0.71
Information: PowerPanel client has been removed.
testEvent
.1.3.6.1.4.1.3808.0.72
Information: Test Event.
outletUserLoginInfo
.1.3.6.1.4.1.3808.0.73
Information: Outlet User login.
outletUserLogoutInfo
.1.3.6.1.4.1.3808.0.74
Information: Outlet User logout.
firmwareUpdateSuccess
.1.3.6.1.4.1.3808.0.75
INFORMATION: Firmware update success.
firmwareUpdateFail
.1.3.6.1.4.1.3808.0.76
INFORMATION: Firmware update fail.
communicationEstablished
.1.3.6.1.4.1.3808.0.8
INFORMATIONAL: Communication to the UPS has been established.
powerRestored
.1.3.6.1.4.1.3808.0.9
INFORMATIONAL: Utility power restored, return from backup mode.