CPS-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
76
Rows
76
Columns
482

upsBaseConfigDeviceTable

table mandatory
.1.3.6.1.4.1.3808.1.1.1.5.1.2 · 1 row entry · 4 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk upsBaseConfigDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::upsBaseConfigDeviceTable'
A list of equipment plugged into the UPS.
The numbers of entries are given by the value of
upsBaseConfigNumDevices.
upsBaseConfigDeviceEntry row .1.3.6.1.4.1.3808.1.1.1.5.1.2.1
The equipment plugged in to the UPS.
Indexes
Column Syntax OID
deviceIndexmandatory
The index of the equipment plugged into the UPS.
Integer32
Constraints:
range: 1-255
.1.3.6.1.4.1.3808.1.1.1.5.1.2.1.1
deviceNamemandatory
The name of the equipment plugged into the UPS.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.1.5.1.2.1.2
vaRatingmandatory
The VA rating of the equipment plugged into the UPS.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.5.1.2.1.3
An equipment is plugged if yes, unplugged if no.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.3808.1.1.1.5.1.2.1.4

upsBankOutletControlTable

table mandatory
.1.3.6.1.4.1.3808.1.1.1.8.1.1 · 1 row entry · 2 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk upsBankOutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::upsBankOutletControlTable'
Allows for control of the outlet banks.
upsBankOutletControlEntry row .1.3.6.1.4.1.3808.1.1.1.8.1.1.1
The outlet to control.
Column Syntax OID
The index to the outlet entry.
Integer32
Constraints:
range: 1-24
.1.3.6.1.4.1.3808.1.1.1.8.1.1.1.1
Getting this variable will return the outlet bank state. If
the outlet bank is on, the immediateOn (1) value will be returned.
If the outlet bank is off, the immediateOff (2) value will be
returned. If the outlet bank i…
Enumerationr/w
Enumerated Values:
1immediateOn
2immediateOff
3bankNotExist
4criticalBank
.1.3.6.1.4.1.3808.1.1.1.8.1.1.1.2
.1.3.6.1.4.1.3808.1.1.1.8.2.2 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk upsIndividualOutletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::upsIndividualOutletConfigTable'
A table of switched outlet configuration data.
upsIndividualOutletConfigEntry row .1.3.6.1.4.1.3808.1.1.1.8.2.2.1
Configuration data from currently queried switched outlet.
Column Syntax OID
The index to the switched outlet configuration table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.1.8.2.2.1.1
The user-defined switched outlet name string.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.1.8.2.2.1.2
The amount of time (in seconds) the outlet will delay
powering on at coldstart or when a command that requires
a turn-on delay is issued.
Allowed values are:
-1 - never power on.
0 - power on immediately.
1 to 72…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.8.2.2.1.3
The amount of time (in seconds) the outlet will delay
powering off when a command that requires a
turn-off delay is issued.
Allowed values are:
-1 - never power off.
0 - power off immediately.
1 to 7200 - power o…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.8.2.2.1.4
During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait,
in seconds, after turning the power off, at the start
of the sequence, before turning power back on, at the…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.8.2.2.1.5
.1.3.6.1.4.1.3808.1.1.1.8.2.3 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk upsIndividualOutletInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::upsIndividualOutletInfoTable'
A table of switched outlet information.
upsIndividualOutletInfoEntry row .1.3.6.1.4.1.3808.1.1.1.8.2.3.1
Information of the currently queried switched outlet.
Column Syntax OID
The index to the switched outlet information table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.1.8.2.3.1.1
The numeric switched outlet name.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.1.8.2.3.1.2
The numeric bank ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.8.2.3.1.3
.1.3.6.1.4.1.3808.1.1.1.8.2.4 · 1 row entry · 4 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk upsIndividualOutletStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::upsIndividualOutletStatusTable'
A table of switched outlet status information.
upsIndividualOutletStatusEntry row .1.3.6.1.4.1.3808.1.1.1.8.2.4.1
Status information for currently queried switched outlet.
Column Syntax OID
The index to the switched outlet status information table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.1.8.2.4.1.1
The user-defined switched outlet name string.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.1.8.2.4.1.2
Indicates the present switch state of the switched outlet being queried.
Enumeration
Enumerated Values:
1outletStatusOn
2outletStatusOff
.1.3.6.1.4.1.3808.1.1.1.8.2.4.1.3
Getting this variable will return the command pending state of the outlet.
If a command is pending on the outlet, the outletStatusCommandPending (1)
value will be returned. If there is not a command pending on the out…
Enumeration
Enumerated Values:
1outletStatusCommandPending
2outletStatusNoCommandPending
.1.3.6.1.4.1.3808.1.1.1.8.2.4.1.4
.1.3.6.1.4.1.3808.1.1.1.8.2.5 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk upsIndividualOutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::upsIndividualOutletControlTable'
A table of switched outlet control data.
upsIndividualOutletControlEntry row .1.3.6.1.4.1.3808.1.1.1.8.2.5.1
Control data for currently queried switched outlet.
Column Syntax OID
The index to the switched outlet control data table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.1.8.2.5.1.1
The user-defined switched outlet name string.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.1.8.2.5.1.2
Getting this variable will return the outlet state.
If the outlet is on, the immediateOn (1) value will be returned.
If the outlet is off, the immediateOff (2) value will be returned.

Setting this vari…
Enumerationr/w
Enumerated Values:
1immediateOn
2immediateOff
3immediateReboot
4delayedOn
5delayedOff
6delayedReboot
7cancelPendingCommand
.1.3.6.1.4.1.3808.1.1.1.8.2.5.1.3

upsPhaseInputTable

table mandatory
.1.3.6.1.4.1.3808.1.1.1.9.1.2 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk upsPhaseInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::upsPhaseInputTable'
Allows for getting the Phase Input in the UPS
upsPhaseInputEntry row .1.3.6.1.4.1.3808.1.1.1.9.1.2.1
The UPS Phase Input Access.
Column Syntax OID
The index to the UPS Phase Input entry.
Integer32
Constraints:
range: 3-3
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1.1
Getting this OID will return the input voltage that each phase of the UPS can provide. It is represented in 1/10 VAC.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1.2
Getting this OID will return the input current that each phase of the UPS can provide. It is represented in 1/10 Amps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1.3
Getting this OID will return the input frequency that each phase of the UPS can provide. It is represented in 1/10 Hz.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1.4
Getting this OID will return the input power factor that each phase of the UPS can provide. It is represented in 1/100.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1.5

upsPhaseOutputTable

table mandatory
.1.3.6.1.4.1.3808.1.1.1.9.2.2 · 1 row entry · 6 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk upsPhaseOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::upsPhaseOutputTable'
Allows for getting the Phase Output in the UPS
upsPhaseOutputEntry row .1.3.6.1.4.1.3808.1.1.1.9.2.2.1
The UPS Phase Output Access.
Column Syntax OID
The index to the UPS Phase Output entry.
Integer32
Constraints:
range: 3-3
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.1
Getting this OID will return the output voltage that each phase of the UPS can provide. It is represented in 1/10 VAC.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.2
Getting this OID will return the output current that each phase of the UPS can provide. It is represented in 1/10 Amps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.3
Getting this OID will return the output frequency that each phase of the UPS can provide. It is represented in 1/10 Hz.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.4
Getting this OID will return the output power factor that each phase of the UPS can provide. It is represented in 1/100.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.5
Getting this OID will return the output power that each phase of the UPS can provide. It is represented in Watt.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.6

upsPhaseBypassTable

table mandatory
.1.3.6.1.4.1.3808.1.1.1.9.3.2 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk upsPhaseBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::upsPhaseBypassTable'
Allows for getting the Phase Bypass in the UPS
upsPhaseBypassEntry row .1.3.6.1.4.1.3808.1.1.1.9.3.2.1
The UPS Phase Bypass Access.
Column Syntax OID
The index to the UPS Phase Bypass entry.
Integer32
Constraints:
range: 3-3
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1.1
Getting this OID will return the bypass voltage that each phase of the UPS can provide. It is represented in 1/10 VAC.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1.2
Getting this OID will return the bypass current that each phase of the UPS can provide. It is represented in 1/10 Amps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1.3
Getting this OID will return the bypass frequency that each phase of the UPS can provide. It is represented in 1/10 Hz.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1.4
Getting this OID will return the bypass power factor that each phase of the UPS can provide. It is represented in 1/100.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1.5

eSwitchBaseTable

table mandatory
.1.3.6.1.4.1.3808.1.1.2.2.2 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk eSwitchBaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::eSwitchBaseTable'
A list of switch information. The number of entries is given
by the value of eSwitchNumber.
eSwitchBaseEntry row .1.3.6.1.4.1.3808.1.1.2.2.2.1
An entry information of the individual switch.
Indexes
Column Syntax OID
eSwitchIDmandatory
The power switch ID number.
Integer32
Constraints:
range: 0-16
.1.3.6.1.4.1.3808.1.1.2.2.2.1.1
The number of outlets provided in the switch.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.2.2.2.1.2
Getting this OID will reply the status of all outlets in the switch.
'0' for outlet off, '1' for outlet on.
The index from left to right is outlet#8, #7, #6, #5, #4, #3, #2, #1.
For Example:
If the string is '01011010',…
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.2.2.2.1.3

eSwitchBaseCtrTable

table mandatory
.1.3.6.1.4.1.3808.1.1.2.2.3 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk eSwitchBaseCtrTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::eSwitchBaseCtrTable'
A list of switch control parameters. The number of entries is given
by the value of eSwitchNumber.
eSwitchBaseCtrEntry row .1.3.6.1.4.1.3808.1.1.2.2.3.1
An entry control information of individual switches.
Indexes
Column Syntax OID
eSwitchCtrIDmandatory
Select the switch ID to be controlled.
Integer32r/w
Constraints:
range: 0-16
.1.3.6.1.4.1.3808.1.1.2.2.3.1.1
The action outlets to be controlled.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.2.2.3.1.2
The on/off type of the action outlets.
1 for duration off, 2 for duration on,
3 for immediately off, 4 for immediately on,
and 5 for reboot.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.2.2.3.1.3

ePDULoadDevBankTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.2.1.6 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDULoadDevBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDULoadDevBankTable'
Allows for getting the Bank Max Load in the Rack PDU.
ePDULoadDevBankEntry row .1.3.6.1.4.1.3808.1.1.3.2.1.6.1
The Rack PDU Banks Access.
Column Syntax OID
The index to the Rack PDU bank entry.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.3.2.1.6.1.1
Getting this OID will return the bank number.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.1.6.1.2
Getting this OID will return the maximum rated power
that each bank of the Rack PDU can provide. It is
represented in Amps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.1.6.1.3

ePDULoadDevMaxOutletTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.2.1.8 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDULoadDevMaxOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDULoadDevMaxOutletTable'
Allows for getting the Max Outlet Load in an Outlet Monitored Rack PDU.
ePDULoadDevMaxOutletEntry row .1.3.6.1.4.1.3808.1.1.3.2.1.8.1
This gives access to Max Outlet Load of an Outlet Monitored Rack PDU
Column Syntax OID
The index to the Outlet Monitored Rack PDU Max Outlet Load entry.
Integer32
Constraints:
range: 1-24
.1.3.6.1.4.1.3808.1.1.3.2.1.8.1.1
Getting this OID will return the Outlet number.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.1.8.1.2
Getting this OID will return the maximum rated power
that each Outlet of an Outlet Monitored Rack PDU can provide. It is
represented in Amps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.1.8.1.3

ePDULoadPhaseConfigTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.2.2.1 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDULoadPhaseConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDULoadPhaseConfigTable'
Allows for configuration of each Rack PDU phase.
The number of entries is contained in the
ePDULoadDevNumPhases OID.
ePDULoadPhaseConfigEntry row .1.3.6.1.4.1.3808.1.1.3.2.2.1.1
The Rack PDU phase to configure.
Column Syntax OID
The index to the Rack PDU phase entry.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1.1
A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in Amps. A warning will be issued when the
load is less than the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1.2
A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1.3
A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1.4
Getting this OID will return the current Phase Alarm.
Enumeration
Enumerated Values:
1noLoadAlarm
2underCurrentAlarm
3nearOverCurrentAlarm
4overCurrentAlarm
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1.5

ePDULoadStatusTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.2.3.1 · 1 row entry · 11 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDULoadStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDULoadStatusTable'
Allows for getting of status of each Rack PDU phase/bank.
The number of entries is calculated by adding
the number of phases (ePDULoadDevNumPhases OID) and
the number of banks of outlets (ePDULoadDevNumBanks)
Number of entries = #phases + #banks.
NOTE: If a device has phase and bank information, all phase information
shall precede the bank information.
ePDULoadStatusEntry row .1.3.6.1.4.1.3808.1.1.3.2.3.1.1
The Rack PDU phase/bank to gather status from.
Column Syntax OID
The index to the Rack PDU phase/bank entry. All phase information will precede
any bank information
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.1
Getting this OID will return the phase/bank load measured
in tenths of Amps.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.2
Getting this OID will return the phase/bank load state.

loadNormal(1) indicates that the phase/bank is operating
properly within the ePDULoadConfigLowLoadThreshold
and ePDULoadConfigNearOverloadThreshol…
Enumeration
Enumerated Values:
1loadNormal
2loadLow
3loadNearOverload
4loadOverload
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.3
The phase number to which this record refers.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.4
The bank number to which this record refers. A value of 0 will be returned if
any bank is not present or if it is phase related.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.5
Getting this OID will return the phase/bank voltage measured
in 0.1 volts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.6
Getting this OID will return the phase/bank active power measured
in watts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.7
Getting this OID will return the phase/bank apparent power measured
in VA.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.8
Getting this OID will return power factor of the output measured in hundredths.
A value of 100 representing a unity power factor (1.00).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.9
Getting this OID will return the phase/bank apparent power measured
in 0.1 kilowatt-hours.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.10
Getting this OID will return the date and time of the last energy
meter reset
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.3.2.3.1.1.11

ePDULoadBankConfigTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.2.4.1 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDULoadBankConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDULoadBankConfigTable'
Allows for configuration of each Rack PDU bank.
The number of entries is contained in the 
ePDULoadDevNumBanks OID.
ePDULoadBankConfigEntry row .1.3.6.1.4.1.3808.1.1.3.2.4.1.1
The Rack PDU bank to configure.
Column Syntax OID
The index to the Rack PDU bank entry.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1.1
A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in Amps. A warning will be issued when the
load is less than the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1.2
A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1.3
A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1.4
Getting this OID will return the current Bank Alarm.
Enumeration
Enumerated Values:
1noLoadAlarm
2underCurrentAlarm
3nearOverCurrentAlarm
4overCurrentAlarm
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1.5

ePDUOutletPhaseTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.3.2.1 · 1 row entry · 2 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDUOutletPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDUOutletPhaseTable'
Allows for management of outlets on a per phase basis.
ePDUOutletPhaseEntry row .1.3.6.1.4.1.3808.1.1.3.3.2.1.1
The phase to manage.
Column Syntax OID
The index to the Switched Rack PDU phase entry.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
.1.3.6.1.4.1.3808.1.1.3.3.2.1.1.1
This OID controls the behavior of a Switched Rack PDU
phase when an overload condition is possible and
additional outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will al…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
.1.3.6.1.4.1.3808.1.1.3.3.2.1.1.2

ePDUOutletControlTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.3.3.1 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDUOutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDUOutletControlTable'
Allows for control of the individual outlets.
The number of entries is contained in the 
ePDUOutletDevNumCntrlOutlets OID.
ePDUOutletControlEntry row .1.3.6.1.4.1.3808.1.1.3.3.3.1.1
The outlet to control.
Column Syntax OID
The index to the outlet entry.
Integer32
Constraints:
range: 1-24
.1.3.6.1.4.1.3808.1.1.3.3.3.1.1.1
The name of the outlet. The maximum string size is device dependent.
An error will be returned if the set request exceeds the max size.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.3.3.3.1.1.2
The phase/s associated with this outlet.

For single phase devices, this object will always
return phase1(1).

For 3-phase devices, this object will return phase1 (1),
phase2 (2), or phase3…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.3808.1.1.3.3.3.1.1.3
Getting this variable will return the outlet state. If
the outlet is on, the immediateOn (1) value will be returned.
If the outlet is off, the immediateOff (2) value will be
returned.


Set…
Enumerationr/w
Enumerated Values:
1immediateOn
2immediateOff
3immediateReboot
4delayedOn
5delayedOff
6delayedReboot
7cancelPendingCommand
8outletIdentify
.1.3.6.1.4.1.3808.1.1.3.3.3.1.1.4
The bank associated with this outlet.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.3.3.1.1.5

ePDUOutletConfigTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.3.4.1 · 1 row entry · 7 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDUOutletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDUOutletConfigTable'
Allows for configuration of individual outlets. The number of
entries is contained in the ePDUOutletDevNumCntrlOutlets OID.
ePDUOutletConfigEntry row .1.3.6.1.4.1.3808.1.1.3.3.4.1.1
The outlet to configure.
Column Syntax OID
The index to the outlet entry.
Integer32
Constraints:
range: 1-24
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.1
The name of the outlet. The maximum string size is device dependent.
An error will be returned if the set request exceeds the max size.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.3.3.4.1.1.2
The phase/s associated with this outlet.

For single phase devices, this object will always
return phase1(1).

For 3-phase devices, this object will return phase1 (1),
phase2 (2), or phase3…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.3
The amount of time (in seconds) the outlet will delay
powering on at coldstart or when a command that requires
a turn-on delay is issued.

Allowed values are:

-1 - never powe…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.4
The amount of time (in seconds) the outlet will delay
powering off when a command that requires
a turn-off delay is issued.

Allowed values are:

-1 - never power off.
0 - po…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.5
During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait,
in seconds, after turning the power off, at the start
of the sequence, before turning power back on, at the
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.6
The bank associated with this outlet.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.7
.1.3.6.1.4.1.3808.1.1.3.3.4.3 · 1 row entry · 8 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDUOutletConfigMonitoredTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDUOutletConfigMonitoredTable'
Allows for getting/setting of outlet thresholds of an Outlet Monitored Rack PDU.
ePDUOutletConfigMonitoredEntry row .1.3.6.1.4.1.3808.1.1.3.3.4.3.1
This gives access to Monitored Outlet entries
Column Syntax OID
The index to the RACK PDU Phase entry.
Integer32
Constraints:
range: 1-24
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.1
The name of the Monitored Outlet. The maximum string size is device dependent.
An error will be returned if the set request exceeds the max size.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.3.3.4.3.1.2
The outlet number of an Outlet Monitored RACK PDU.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.3
A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in watts. A warning will be issued when
the load is less than the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4
A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in watts. A warning
will be issued when the load is greater than or equal
to the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.5
A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in watts. A warning
will be issued when the load is greater than or equal
to the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.6
Setting this OID to reset (2) will cause the existing peak power value
to be replaced by the current load power value.

Getting this oid will do nothing and return noAction (1) if the PDU
support this fe…
Enumerationr/w
Enumerated Values:
1noAction
2reset
3notSupport
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.7
Setting this OID to reset (2) will cause the device energy meter value
to be reset to zero.

Getting this oid will do nothing and return noAction (1) if the PDU
support this feature, return notSupport (3…
Enumerationr/w
Enumerated Values:
1noAction
2reset
3notSupport
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.8

ePDUOutletStatusTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.3.5.1 · 1 row entry · 14 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDUOutletStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDUOutletStatusTable'
Allows for getting of status of individual outlets. The number of
entries is contained in the ePDUOutletDevNumCntrlOutlets OID.
ePDUOutletStatusEntry row .1.3.6.1.4.1.3808.1.1.3.3.5.1.1
The outlet to gather status from.
Column Syntax OID
The index to the outlet entry.
Integer32
Constraints:
range: 1-24
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.1
The name of the outlet. The maximum string size is device dependent.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.2
The phase/s associated with this outlet.

For single phase devices, this object will always
return phase1(1).

For 3-phase devices, this object will return phase1 (1),
phase2 (2), or phase3…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.3
Getting this variable will return the outlet state. If
the outlet is on, the outletStatusOn (1) value will be returned.
If the outlet is off, the outletStatusOff (2) value will be
returned.
Enumeration
Enumerated Values:
1outletStatusOn
2outletStatusOff
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.4
Getting this variable will return the command pending
state of the outlet. If a command is pending on the
outlet, the outletStatusCommandPending (1) value
will be returned. If there is not a command pending
on the outl…
Enumeration
Enumerated Values:
1outletStatusCommandPending
2outletStatusNoCommandPending
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.5
The bank associated with this outlet.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.6
Getting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU
in tenths of Amps.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.7
Getting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU
in watts
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.8
Getting this OID will return the current outlet alarm
Enumeration
Enumerated Values:
1noLoadAlarm
2underCurrentAlarm
3nearOverCurrentAlarm
4overCurrentAlarm
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.9
The peak power consumption of the Rack PDU load in watts.
This value can be reset by setting the oid
ePDUOutletConfigMonitoredPeakLoadReset to reset (2)
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.10
Get this oid shows the date and time that peak power consumption occurred
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.11
Get this oid shows the date and time that peak power consumption started
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.12
Energy meter measuring Rack PDU load energy consumption
in tenths of kilowatt-hours. This value can be reset by setting
the oid ePDUOutletConfigMonitoredEnergyReset to reset (2)
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.13
Indicates the date and time of the last device energy
meter reset
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.14

ePDUOutletBankTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.3.6.1 · 1 row entry · 2 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDUOutletBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDUOutletBankTable'
Allows for management of outlets on a per bank basis.
ePDUOutletBankEntry row .1.3.6.1.4.1.3808.1.1.3.3.6.1.1
The bank to manage.
Column Syntax OID
The index to the Switched Rack PDU bank entry.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.3.3.6.1.1.1
This OID controls the behavior of a Switched Rack PDU
bank when an overload condition is possible and
additional outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will al…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
.1.3.6.1.4.1.3808.1.1.3.3.6.1.1.2

ePDUStatusBankTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.5.2 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDUStatusBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDUStatusBankTable'
Allows for getting of status of each Rack PDU Bank
ePDUStatusBankEntry row .1.3.6.1.4.1.3808.1.1.3.5.2.1
This gives access to Bank entries
Column Syntax OID
The index to the RACK PDU Bank entry.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.3.5.2.1.1
Getting this OID will return the bank number.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.5.2.1.2
Getting this OID will return the bank load state.

bankLoadNormal(1) indicates that the bank is
operating properly within the ePDULoadBankConfigLowLoadThreshold
and ePDULoadBankConfigNearOverloadThreshol…
Enumeration
Enumerated Values:
1bankLoadNormal
2bankLoadLow
3bankLoadNearOverload
4bankLoadOverload
.1.3.6.1.4.1.3808.1.1.3.5.2.1.3

ePDUStatusPhaseTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.5.4 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDUStatusPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDUStatusPhaseTable'
Allows for getting of status of each Rack PDU Phase
ePDUStatusPhaseEntry row .1.3.6.1.4.1.3808.1.1.3.5.4.1
This gives access to Phase entries
Column Syntax OID
The index to the RACK PDU Phase entry.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.3.5.4.1.1
Getting this OID will return the phase number.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.5.4.1.2
Getting this OID will return the Phase load state.

phaseLoadNormal(1) indicates that the Phase is
operating properly within the ePDULoadPhaseConfigLowLoadThreshold
and ePDULoadPhaseConfigNearOverloadThr…
Enumeration
Enumerated Values:
1phaseLoadNormal
2phaseLoadLow
3phaseLoadNearOverload
4phaseLoadOverload
.1.3.6.1.4.1.3808.1.1.3.5.4.1.3

ePDUStatusOutletTable

table mandatory
.1.3.6.1.4.1.3808.1.1.3.5.6 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDUStatusOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDUStatusOutletTable'
Allows for getting of status of each Outlet of an Outlet Monitored Rack PDU.
ePDUStatusOutletEntry row .1.3.6.1.4.1.3808.1.1.3.5.6.1
This gives access to Outlet entries
Column Syntax OID
The index to the RACK PDU Outlet entry.
Integer32
Constraints:
range: 1-24
.1.3.6.1.4.1.3808.1.1.3.5.6.1.1
Getting this OID will return the Outlet number.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.3.5.6.1.2
Getting this OID will return the Outlet load state.

outletLoadNormal(1) indicates that the Outlet is
operating properly within the ePDUOutletConfigMonitoredLowLoadThreshold
and ePDUOutletConfigMonitored…
Enumeration
Enumerated Values:
1outletLoadNormal
2outletLoadLow
3outletLoadNearOverload
4outletLoadOverload
.1.3.6.1.4.1.3808.1.1.3.5.6.1.3

envirContactTable

table mandatory
.1.3.6.1.4.1.3808.1.1.4.4.2 · 1 row entry · 4 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk envirContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::envirContactTable'
Allows for getting of information of each contact of the environment sensor.
envirContactEntry row .1.3.6.1.4.1.3808.1.1.4.4.2.1
This gives access to contact entries.
Column Syntax OID
The index to the contact of the environment sensor.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.4.4.2.1.1
Getting or setting the name of the contact of the environment sensor.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.4.4.2.1.2
Getting this OID will return the Contact Status.
Enumeration
Enumerated Values:
1contactNormal
2contactAbnormal
.1.3.6.1.4.1.3808.1.1.4.4.2.1.3
Set the contact normal state.
Enumerationr/w
Enumerated Values:
1normalOpen
2normalClose
.1.3.6.1.4.1.3808.1.1.4.4.2.1.4

atsStatusPowerSupplyTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.2.1.10 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsStatusPowerSupplyTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsStatusPowerSupplyTable'
A list of power supply table entries.
atsStatusPowerSupplyEntry row .1.3.6.1.4.1.3808.1.1.5.2.1.10.1
An entry containing power supply information applicable to a
particular input.
Column Syntax OID
The input identifier.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1.1
The input source to the power supply.
Enumeration
Enumerated Values:
1sourceA
2sourceB
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1.2
This variable returns the status of the power supply A 12V in system.
Enumeration
Enumerated Values:
1powerSupplyOK
2powerSupplyFailure
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1.3
This variable returns the status of the power supply A 5V in system.
Enumeration
Enumerated Values:
1powerSupplyOK
2powerSupplyFailure
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1.4
This variable returns the status of the power supply A 3.3V in system.
Enumeration
Enumerated Values:
1powerSupplyOK
2powerSupplyFailure
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1.5

atsStatusInputTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.2.2.2 · 1 row entry · 8 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsStatusInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsStatusInputTable'
A list of input table entries.  The number of entries
is given by the value of atsNumInputs.
atsStatusInputEntry row .1.3.6.1.4.1.3808.1.1.5.2.2.2.1
An entry containing information applicable to a
particular input.
Column Syntax OID
The input identifier.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.1
A name given to a particular input.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.5.2.2.2.1.2
The number of input phases utilized in this device.
The sum of all the atsStatusNumInputPhase variable
indicates the number of rows in the status input
phase table.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.3
The input voltage orientation:
1: unknown for this Source
2: singlePhase - phase 1 voltage is between Phase 1
and Neutral.
3: splitPhase - phase 1 voltage is between Phase 1 and
Neutral; phase 2 voltage is between Pha…
Enumeration
Enumerated Values:
1unknown
2singlePhase
3splitPhase
4threePhasePhaseToNeutral
5threePhasePhaseToPhase
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.4
The input voltage in 0.1 Volt.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.5
The input frequency in 0.1 Hertz.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.6
The input voltage status.
Enumeration
Enumerated Values:
1normal
2overVoltage
3underVoltage
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.7
The input frequency status.
Enumeration
Enumerated Values:
1normal
2overFrequency
3underFrequency
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.8

atsStatusInputPhaseTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.2.2.3 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsStatusInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsStatusInputPhaseTable'
A list of input table entries.  The number of entries
is given by the sum of the atsNumInputPhases.
atsStatusInputPhaseEntry row .1.3.6.1.4.1.3808.1.1.5.2.2.3.1
An entry containing information applicable to a
particular input phase.
Column Syntax OID
The input identifier.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1.1
The input phase identifier.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1.2
The input voltage in VAC, or -1 if it's unsupported
by this Source.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1.3
The input current in amperes, or -1 if it's
unsupported by this Source.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1.4
The input power in Watts, or -1 if it's unsupported
by this Source.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1.5

atsLoadDevPhaseTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.5.1.2 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsLoadDevPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsLoadDevPhaseTable'
Allows for getting the Phase Max Load in the ATS.
atsLoadDevPhaseEntry row .1.3.6.1.4.1.3808.1.1.5.5.1.2.1
The ATS Phases Access.
Column Syntax OID
The index to ATS phase entry.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.5.5.1.2.1.1
For single phase devices, this object will always
return phase1(1).

For 3-phase devices, this object will return phase1 (1),
phase2 (2), phase3 (3), phase1-2 (4) for phases 1 and 2,
phase2-3 (5) for ph…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.3808.1.1.5.5.1.2.1.2
Getting this OID will return the maximum rated power that each
phase of the ATS can provide. It is represented in Amps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.1.2.1.3

atsLoadDevBankTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.5.1.4 · 1 row entry · 2 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsLoadDevBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsLoadDevBankTable'
Allows for getting the Bank Max Load in the ATS.
atsLoadDevBankEntry row .1.3.6.1.4.1.3808.1.1.5.5.1.4.1
The ATS Banks Access.
Column Syntax OID
The index to the ATS bank entry.
Enumeration
Enumerated Values:
1total
2bank1
3bank2
4bank3
.1.3.6.1.4.1.3808.1.1.5.5.1.4.1.1
Getting this OID will return the maximum rated power
that each bank of the ATS can provide. It is
represented in Amps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.1.4.1.2

atsLoadStatusPhaseTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.5.2.2 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsLoadStatusPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsLoadStatusPhaseTable'
Allows for getting the Phase Load status in the ATS.
atsLoadStatusPhaseEntry row .1.3.6.1.4.1.3808.1.1.5.5.2.2.1
The ATS Phases Access.
Column Syntax OID
The index to ATS phase entry.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1.1
For single phase devices, this object will always
return phase1(1).

For 3-phase devices, this object will return phase1 (1),
phase2 (2), phase3 (3), phase1-2 (4) for phases 1 and 2,
phase2-3 (5) for ph…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1.2
The output current in 0.1 amperes drawn
by the load on the ATS
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1.3
Getting this OID will return the phase load state.
Enumeration
Enumerated Values:
1normal
2lowLoad
3nearOverLoad
4overLoad
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1.4
The output power in Watts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1.5

atsLoadStatusBankTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.5.2.4 · 1 row entry · 7 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsLoadStatusBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsLoadStatusBankTable'
Allows for getting the Bank Load status in the ATS.
atsLoadStatusBankEntry row .1.3.6.1.4.1.3808.1.1.5.5.2.4.1
The ATS Bank Access.
Column Syntax OID
The index to ATS bank entry.
Enumeration
Enumerated Values:
1total
2bank1
3bank2
4bank3
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.1
Getting this OID will return the phase number.
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.2
The output current in 0.1 amperes drawn
by the load on the ATS
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.3
Getting this OID will return the bank load state.
Enumeration
Enumerated Values:
1normal
2lowLoad
3nearOverLoad
4overLoad
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.4
The output power in Watts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.5
Getting this OID will return the phase/bank apparent power measured in 0.1 kilowatt-hours.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.6
Getting this OID will return the date and time of the last energy meter reset
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.7

atsLoadCfgPhaseTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.5.3.2 · 1 row entry · 6 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsLoadCfgPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsLoadCfgPhaseTable'
Allows for configuration of each ATS phase.
atsLoadCfgPhaseEntry row .1.3.6.1.4.1.3808.1.1.5.5.3.2.1
The ATS phase to configure.
Column Syntax OID
The index to the ATS phase entry.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.1
For single phase devices, this object will always
return phase1(1).

For 3-phase devices, this object will return phase1 (1),
phase2 (2), phase3 (3), phase1-2 (4) for phases 1 and 2,
phase2-3 (5) for ph…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.2
A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in Amps. A warning will be issued when the
load is less than the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.3
A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.4
A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.5
This OID controls the behavior of a ATS phase when an overload
condition is possible and additional outlets are requested to be
turned on.

Setting this OID to alwaysAllowTurnON (1) will always allow
t…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.6

atsLoadCfgBankTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.5.3.4 · 1 row entry · 6 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsLoadCfgBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsLoadCfgBankTable'
Allows for configuration of each ATS bank.
atsLoadCfgBankEntry row .1.3.6.1.4.1.3808.1.1.5.5.3.4.1
The ATS phase to configure.
Column Syntax OID
The index to the ATS bank entry.
Enumeration
Enumerated Values:
1total
2bank1
3bank2
4bank3
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.1
A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in Amps. A warning will be issued when the
load is less than the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.2
A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.3
A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than or equal to the threshold value.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.4
This OID controls the behavior of a ATS phase when an overload
condition is possible and additional outlets are requested to be
turned on.

Setting this OID to alwaysAllowTurnON (1) will always allow
t…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.5
Setting this OID to reset (2) will cause the bank energy meter value to be reset to zero.
Getting this OID will do nothing and return the noOperation(1) value.
Enumerationr/w
Enumerated Values:
1noOperation
2reset
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.6

atsOutletStatusTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.6.3 · 1 row entry · 6 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsOutletStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsOutletStatusTable'
Allows for getting of status of individual outlets.
atsOutletStatusEntry row .1.3.6.1.4.1.3808.1.1.5.6.3.1
The outlet to gather status from.
Column Syntax OID
The index to the outlet entry.
Integer32
Constraints:
range: 1-19
.1.3.6.1.4.1.3808.1.1.5.6.3.1.1
The name of the outlet. The maximum string size is device dependent.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.5.6.3.1.2
Getting this variable will return the outlet state. If
the outlet is on, the outletStatusOn (1) value will be returned.
If the outlet is off, the outletStatusOff (2) value will be
returned.
Enumeration
Enumerated Values:
1outletStatusOn
2outletStatusOff
.1.3.6.1.4.1.3808.1.1.5.6.3.1.3
Getting this variable will return the command pending
state of the outlet. If a command is pending on the
outlet, the outletStatusCommandPending (1) value
will be returned. If there is not a command pending
on the outl…
Enumeration
Enumerated Values:
1outletStatusCommandPending
2outletStatusNoCommandPending
.1.3.6.1.4.1.3808.1.1.5.6.3.1.4
The phase/s associated with this outlet.

For single phase devices, this object will always
return phase1(1).

For 3-phase devices, this object will return phase1 (1),
phase2 (2), or phase3…
Enumeration
Enumerated Values:
1phase1
2phase2
3phase3
4phase1-2
5phase2-3
6phase3-1
.1.3.6.1.4.1.3808.1.1.5.6.3.1.5
The bank associated with this outlet.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.6.3.1.6

atsOutletCtrlTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.6.5 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsOutletCtrlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsOutletCtrlTable'
Allows for control of the individual outlets.
atsOutletCtrlEntry row .1.3.6.1.4.1.3808.1.1.5.6.5.1
The outlet to control.
Column Syntax OID
The index to the outlet entry.
Integer32
Constraints:
range: 1-19
.1.3.6.1.4.1.3808.1.1.5.6.5.1.1
The name of the outlet. The maximum string size is device dependent.
An error will be returned if the set request exceeds the max size.
This OID is provided for informational purposes only.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.5.6.5.1.2
Getting this variable will return the outlet state. If
the outlet is on, the immediateOn (2) value will be returned.
If the outlet is off, the immediateOff (2) value will be
returned.

Setting this varia…
Enumerationr/w
Enumerated Values:
1none
2immediateOn
3immediateOff
4immediateReboot
5delayedOn
6delayedOff
7delayedReboot
8cancelPendingCommand
.1.3.6.1.4.1.3808.1.1.5.6.5.1.3

atsOutletCfgTable

table mandatory
.1.3.6.1.4.1.3808.1.1.5.6.7 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk atsOutletCfgTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::atsOutletCfgTable'
Allows for configuration of individual outlets.
atsOutletCfgEntry row .1.3.6.1.4.1.3808.1.1.5.6.7.1
The outlet to configure.
Column Syntax OID
The index to the outlet entry.
Integer32
Constraints:
range: 1-19
.1.3.6.1.4.1.3808.1.1.5.6.7.1.1
The name of the outlet. The maximum string size is device dependent.
An error will be returned if the set request exceeds the max size.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.5.6.7.1.2
The amount of time (in seconds) the outlet will delay
powering on at coldstart or when a command that requires
a turn-on delay is issued.

Allowed values are:
-1 - never power on.
0 - powe…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.6.7.1.3
The amount of time (in seconds) the outlet will delay
powering off when a command that requires
a turn-off delay is issued.

Allowed values are:

-1 - never power off.
0 - po…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.6.7.1.4
During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait,
in seconds, after turning the power off, at the start
of the sequence, before turning power back on, at the
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.5.6.7.1.5

ePDU2IdentTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.2.2 · 1 row entry · 11 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2IdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2IdentTable'
A table of Rack PDU identification information.
ePDU2IdentEntry row .1.3.6.1.4.1.3808.1.1.6.2.2.1
Identification data from Rack PDU being queried.
Indexes
Column Syntax OID
The index to the Rack PDU identification table entry.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.6.2.2.1.1
The Rack PDU identification table entry numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.2.2.1.2
A user-defined string identifying the name of the Rack PDU.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.2.2.1.3
A user-defined string identifying the location of the Rack PDU.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.2.2.1.4
A user-defined string identifying the person to contact of the Rack PDU.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.2.2.1.5
The Rack PDU hardware version.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.2.2.1.6
The Rack PDU firmware version.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.2.2.1.7
The date the Rack PDU was manufactured in mm/dd/yyyy format.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.2.2.1.8
The Rack PDU model number.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.2.2.1.9
The Rack PDU serial number.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.2.2.1.10
PDU will perform a panel indicator test when the variable
is set to testIndicators(2).

It is no effective to set this value to noTestIndicators(1).
Enumerationr/w
Enumerated Values:
1noTestIndicators
2testIndicators
.1.3.6.1.4.1.3808.1.1.6.2.2.1.11

ePDU2DeviceConfigTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.3.2 · 1 row entry · 15 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2DeviceConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2DeviceConfigTable'
A table of Rack PDU configuration data.
ePDU2DeviceConfigEntry row .1.3.6.1.4.1.3808.1.1.6.3.2.1
Configuration data from Rack PDU being queried.
Column Syntax OID
The index to the Rack PDU table entry.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.6.3.2.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.2.1.2
A user-defined string identifying the name of Rack PDU.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.6.3.2.1.3
A user-defined string identifying the location of the Rack PDU.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.6.3.2.1.4
A user-defined string identifying the person to contact of the Rack PDU.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.6.3.2.1.5
Getting this OID will return the intended physical orientation of the Seven-Segment Display.

displayNormal(1) indicates Normal.
displayReverse(2)indicates Upside-Down.
displayRotate90(3) indicates rotate …
Enumerationr/w
Enumerated Values:
1displayNormal
2displayReverse
3displayRotate90
4displayRotate270
5displayAuto
.1.3.6.1.4.1.3808.1.1.6.3.2.1.6
The amount of delay, measured in seconds, between
when power is provided to the Rack PDU and when
the Rack PDU provides basic master power to the
outlets.

Allowed values are:
-1 - never apply power autom…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.2.1.7
User-defined low current draw alarm threshold, measured in Amps.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.2.1.8
User-defined near overload current threshold, measured in Amps.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.2.1.9
User-defined current overload threshold, measured in Amps.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.2.1.10
Setting this OID to resetAll (2) will cause the existing peak current value
of Rack PDU and its outlets to be replaced by the current load current value.
Setting this OID to resetDevice (3) to reset the Rack PDU only.
Enumerationr/w
Enumerated Values:
1noOperation
2resetAll
3resetDevice
4resetOutlets
.1.3.6.1.4.1.3808.1.1.6.3.2.1.11
Setting this OID to resetAll (2) will cause the device energy meter value
to be reset to zero.
Setting this OID to resetDevice (3) to reset the Rack PDU only.
Setting this OID to resetOutlets (4) to reset the PDU outle…
Enumerationr/w
Enumerated Values:
1noOperation
2resetAll
3resetDevice
4resetOutlets
.1.3.6.1.4.1.3808.1.1.6.3.2.1.12
User-defined low power draw alarm threshold, measured in Watts.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.2.1.13
User-defined near overload power threshold, measured in Watts.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.2.1.14
User-defined power overload threshold, measured in Watts.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.2.1.15

ePDU2DeviceInfoTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.3.3 · 1 row entry · 13 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2DeviceInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2DeviceInfoTable'
A table of Rack PDU information.
ePDU2DeviceInfoEntry row .1.3.6.1.4.1.3808.1.1.6.3.3.1
Information of the Rack PDU being queried.
Column Syntax OID
The index to the Rack PDU Information table entry.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.6.3.3.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.3.1.2
A user-defined string identifying the name of the Rack PDU.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.3.3.1.3
The electrical rating of the Rack PDU.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.3.1.4
The number of outlets on the Rack PDU.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.3.1.5
The number of switched outlets on the Rack PDU.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.3.1.6
The number of metered outlets on the Rack PDU.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.3.1.7
The number of phases present in the Rack PDU.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.3.1.8
The number of metered banks present in the Rack PDU.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.3.1.9
The maximum current rating, measured in Amps, for the Rack PDU.
Getting this OID will return rating of the circuit breakers on
the device if it has any.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.3.1.10
Rack PDU orientation.
Enumeration
Enumerated Values:
1orientHorizontal
2orientVertical
.1.3.6.1.4.1.3808.1.1.6.3.3.1.11
Getting this OID will return outlet layout for the device.

SeqPhaseToNeutral(1) indicates outlet layout as follows:
Outlet(1-5 and 16-20):1-N,
outlet(6-10 and 21-25):2-N,
outlet(11-15 and 26-30):3-N,4:…
Enumeration
Enumerated Values:
1seqPhaseToNeutral
2seqPhaseToPhase
3seqOther
.1.3.6.1.4.1.3808.1.1.6.3.3.1.12
The maximum power limit, measured in Watt, for the Rack PDU.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.3.1.13

ePDU2DeviceStatusTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.3.4 · 1 row entry · 19 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2DeviceStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2DeviceStatusTable'
A table of Rack PDU current status.
ePDU2DeviceStatusEntry row .1.3.6.1.4.1.3808.1.1.6.3.4.1
Status data from the Rack PDU being queried.
Column Syntax OID
The index to the Rack PDU status table entry.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.6.3.4.1.1
The Rack PDU numeric ID
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.4.1.2
A user-defined string identifying the name of the Rack PDU.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.3.4.1.3
Indicates the present load status of the Rack PDU.
Enumeration
Enumerated Values:
1noLoadAlarm
2underCurrentAlarm
3nearOverCurrentAlarm
4overCurrentAlarm
.1.3.6.1.4.1.3808.1.1.6.3.4.1.4
The power consumption of the Rack PDU load in tenths of Amps.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.3.4.1.5
The peak power consumption of the Rack PDU load in tenths of Amps.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.3.4.1.6
Indicates the date and time that peak load occurred.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.3.4.1.7
Indicates the date and time of the last device peak load reset.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.3.4.1.8
A user resettable energy meter measuring Rack PDU load
energy consumption in tenths of kilowatt-hours.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.3.4.1.9
Indicates the date and time of the last device energy
meter reset.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.3.4.1.10
Indicates whether or not the device
is processing a pending command.
Enumeration
Enumerated Values:
1commandPending
2noCommandPending
.1.3.6.1.4.1.3808.1.1.6.3.4.1.11
Indicates a power supply alarm is active when value
equals alarm (2).
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.3808.1.1.6.3.4.1.12
Indicates whether or not an alarm is active in Power
Supply 1.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.3808.1.1.6.3.4.1.13
Indicates whether or not an alarm is active in Power
Supply 2.
Enumeration
Enumerated Values:
1normal
2alarm
.1.3.6.1.4.1.3808.1.1.6.3.4.1.14
The apparent power consumption of the Rack PDU
load in VoltAmps (VA).
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.3.4.1.15
The power factor of the Rack PDU load in hundredths.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.3.4.1.16
Get this oid shows the role the PDU played on Daisy Chain Group.
The PDU as a Host can access whole ePDU2 content, and the PDU be standalong
or a Slave can access itself instead.
Enumeration
Enumerated Values:
1standalone
2host
3slave
.1.3.6.1.4.1.3808.1.1.6.3.4.1.17
The power consumption of the Rack PDU load in Watts.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.3.4.1.18
The peak power consumption of the Rack PDU load in Watts.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.3.4.1.19

ePDU2DeviceControlTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.3.5 · 1 row entry · 4 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2DeviceControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2DeviceControlTable'
A table of Rack PDU control data.
ePDU2DeviceControlEntry row .1.3.6.1.4.1.3808.1.1.6.3.5.1
Control data from Rack PDU being queried.
Column Syntax OID
The index to the Rack PDU control table entry.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.6.3.5.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.3.5.1.2
A user-defined string identifying the name of the Rack PDU.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.3.5.1.3
Setting this OID to immediateAllOn (1) will turn all outlets on immediately.

Setting this OID to immediateAllOff (2) will turn all outlets off immediately.

Setting this OID to immediateAllR…
Enumerationr/w
Enumerated Values:
1immediateAllOn
2immediateAllOff
3immediateAllReboot
4delayedAllOn
5delayedAllOff
6delayedAllReboot
7cancelAllPendingCommand
8noCommand
.1.3.6.1.4.1.3808.1.1.6.3.5.1.4

ePDU2PhaseConfigTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.4.2 · 1 row entry · 8 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2PhaseConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2PhaseConfigTable'
A table of Rack PDU phase configuration data.
ePDU2PhaseConfigEntry row .1.3.6.1.4.1.3808.1.1.6.4.2.1
Configuration data from currently queried
Rack PDU phase.
Column Syntax OID
The index to the Rack PDU phase configuration
table entry.
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.3808.1.1.6.4.2.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.4.2.1.2
The numeric phase ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.4.2.1.3
This OID controls the behavior of a Switched Rack PDU
phase when an overload condition is possible and
additional outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will a…
Enumerationr/w
Enumerated Values:
-1notSupported
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
.1.3.6.1.4.1.3808.1.1.6.4.2.1.4
User-defined low load phase current threshold in Amps.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.4.2.1.5
User-defined near phase overload current warning
threshold in Amps.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.4.2.1.6
User-defined phase overload current threshold
in Amps
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.4.2.1.7
Setting this OID to reset (2) will cause the existing peak current value
to be replaced by the present load current value.

Getting this OID will do nothing and return the noOperation(1) value.
Enumerationr/w
Enumerated Values:
1noOperation
2reset
.1.3.6.1.4.1.3808.1.1.6.4.2.1.8

ePDU2PhaseInfoTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.4.3 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2PhaseInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2PhaseInfoTable'
A table of Rack PDU phase information.
ePDU2PhaseInfoEntry row .1.3.6.1.4.1.3808.1.1.6.4.3.1
Information data from currently queried Rack PDU phase.
Column Syntax OID
The index to the Rack PDU phase properties table entry.
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.3808.1.1.6.4.3.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.4.3.1.2
The numeric phase ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.4.3.1.3

ePDU2PhaseStatusTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.4.4 · 1 row entry · 13 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2PhaseStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2PhaseStatusTable'
A table of Rack PDU phase status data
ePDU2PhaseStatusEntry row .1.3.6.1.4.1.3808.1.1.6.4.4.1
Status data from currently queried Rack PDU phase
Column Syntax OID
The index to the Rack PDU phase status table entry.
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.3808.1.1.6.4.4.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.4.4.1.2
The numeric phase ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.4.4.1.3
Indicates the present load status of the Rack
PDU phase being queried.
Enumeration
Enumerated Values:
1normal
2lowLoad
3nearOverload
4overload
.1.3.6.1.4.1.3808.1.1.6.4.4.1.4
Indicates the current draw, in tenths of Amps, of the load
on the Rack PDU phase being queried.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.4.4.1.5
Indicates the Voltage, in tenths of Volts, of the Rack PDU phase being queried.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.4.4.1.6
Indicates the load power, in watts,
consumed on the Rack PDU phase being queried
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.4.4.1.7
Indicates the load apparent power, in VoltAmps (VA),
consumed on the Rack PDU phase being queried
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.4.4.1.8
Indicates the load power factor, in hundredths,
of the Rack PDU phase being queried
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.4.4.1.9
The peak current of the Rack PDU phase load in tenths of Amps
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.4.4.1.10
Indicates the date and time the phase peak current occurred.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.4.4.1.11
Indicates the date and time of the last phase peak current reset.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.4.4.1.12
Indicates the Line to Line Voltage, in tenths of Volts, of the Rack
PDU phase being queried
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.4.4.1.13

ePDU2BankConfigTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.5.2 · 1 row entry · 8 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2BankConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2BankConfigTable'
A table of Rack PDU bank configuration data.
ePDU2BankConfigEntry row .1.3.6.1.4.1.3808.1.1.6.5.2.1
Configuration data from currently queried
Rack PDU bank.
Column Syntax OID
The index to the Rack PDU bank configuration
table entry.
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.3808.1.1.6.5.2.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.5.2.1.2
The numeric bank ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.5.2.1.3
This OID controls the behavior of a Switched Rack PDU
bank when an overload condition is possible and
additional outlets are requested to be turned on.

Setting this OID to alwaysAllowTurnON (1) will al…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload
.1.3.6.1.4.1.3808.1.1.6.5.2.1.4
User-defined low load bank current threshold in Amps.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.5.2.1.5
User-defined near bank overload current warning
threshold in Amps.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.5.2.1.6
User-defined bank overload current threshold
in Amps
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.5.2.1.7
Setting this OID to reset (2) will cause the existing peak current value
to be replaced by the present load current value.

Getting this OID will do nothing and return the noOperation(1) value.
Enumerationr/w
Enumerated Values:
1noOperation
2reset
.1.3.6.1.4.1.3808.1.1.6.5.2.1.8

ePDU2BankInfoTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.5.3 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2BankInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2BankInfoTable'
A table of Rack PDU bank information.
ePDU2BankInfoEntry row .1.3.6.1.4.1.3808.1.1.6.5.3.1
Information data from currently queried Rack PDU bank.
Column Syntax OID
The index to the Rack PDU bank properties table entry.
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.3808.1.1.6.5.3.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.5.3.1.2
The numeric bank ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.5.3.1.3

ePDU2BankStatusTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.5.4 · 1 row entry · 8 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2BankStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2BankStatusTable'
A table of Rack PDU bank status data
ePDU2BankStatusEntry row .1.3.6.1.4.1.3808.1.1.6.5.4.1
Status data from currently queried Rack PDU bank
Column Syntax OID
The index to the Rack PDU bank status table entry.
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.3808.1.1.6.5.4.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.5.4.1.2
The numeric bank ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.5.4.1.3
Indicates the present load status of the Rack
PDU bank being queried.
Enumeration
Enumerated Values:
1normal
2lowLoad
3nearOverload
4overload
.1.3.6.1.4.1.3808.1.1.6.5.4.1.4
Indicates the current draw, in tenths of Amps, of the load
on the Rack PDU bank being queried.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.5.4.1.5
The peak current of the Rack PDU bank load in tenths of Amps.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.5.4.1.6
Indicates the date and time the bank peak current occurred.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.5.4.1.7
Indicates the date and time of the last bank peak current reset.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.5.4.1.8
.1.3.6.1.4.1.3808.1.1.6.6.1.2 · 1 row entry · 7 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2OutletSwitchedConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2OutletSwitchedConfigTable'
A table of Rack PDU switched outlet configuration data.
ePDU2OutletSwitchedConfigEntry row .1.3.6.1.4.1.3808.1.1.6.6.1.2.1
Configuration data from currently queried Rack PDU
switched outlet.
Column Syntax OID
The index to the Rack PDU switched outlet configuration table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.2
The numeric switched outlet ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.3
The user-defined switched outlet name string.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.6.6.1.2.1.4
The amount of time (in seconds) the outlet will delay
powering on at coldstart or when a command that requires
a turn-on delay is issued.

Allowed values are:
-1 - never power on.
0 - power on immedia…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.5
The amount of time (in seconds) the outlet will delay
powering off when a command that requires a
turn-off delay is issued.

Allowed values are:
-1 - never power off.
0 - power off immediately.
1 t…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.6
During a reboot sequence, power is turned off and then
back on. This OID defines the amount of time to wait,
in seconds, after turning the power off, at the start
of the sequence, before turning power back on, at the…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.7
.1.3.6.1.4.1.3808.1.1.6.6.1.3 · 1 row entry · 6 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2OutletSwitchedInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2OutletSwitchedInfoTable'
A table of Rack PDU switched outlet information.
ePDU2OutletSwitchedInfoEntry row .1.3.6.1.4.1.3808.1.1.6.6.1.3.1
Information of the currently queried Rack PDU
switched outlet.
Column Syntax OID
The index to the Rack PDU switched outlet information table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.2
The numeric switched outlet ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.3
The numeric switched outlet name.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.6.1.3.1.4
This OID describes the phase connections of the referenced outlet as follows:
seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.
seqPhase2ToNeutral(2) indicates that the outlet is wired fr…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.5
The numeric bank ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.6
.1.3.6.1.4.1.3808.1.1.6.6.1.4 · 1 row entry · 6 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2OutletSwitchedStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2OutletSwitchedStatusTable'
A table of Rack PDU switched outlet status information.
ePDU2OutletSwitchedStatusEntry row .1.3.6.1.4.1.3808.1.1.6.6.1.4.1
Status information for currently queried Rack PDU switched outlet.
Column Syntax OID
The index to the Rack PDU switched outlet status information table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.2
The numeric switched outlet ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.3
The user-defined switched outlet name string.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.6.1.4.1.4
Indicates the present switch state of the Rack PDU switched outlet being queried.
Enumeration
Enumerated Values:
1outletStatusOn
2outletStatusOff
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.5
Getting this variable will return the command pending state of the outlet.
If a command is pending on the outlet, the outletStatusCommandPending (1)
value will be returned. If there is not a command pending on the out…
Enumeration
Enumerated Values:
1outletStatusCommandPending
2outletStatusNoCommandPending
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.6
.1.3.6.1.4.1.3808.1.1.6.6.1.5 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2OutletSwitchedControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2OutletSwitchedControlTable'
A table of Rack PDU switched outlet control data.
ePDU2OutletSwitchedControlEntry row .1.3.6.1.4.1.3808.1.1.6.6.1.5.1
Control data for currently queried Rack PDU switched outlet.
Column Syntax OID
The index to the Rack PDU switched outlet control data table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.6.6.1.5.1.1
The user-defined Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.5.1.2
The numeric switched outlet ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.1.5.1.3
The user-defined switched outlet name string.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.6.1.5.1.4
Getting this variable will return the outlet state. If
the outlet is on, the immediateOn (1) value will be returned.
If the outlet is off, the immediateOff (2) value will be returned.

Setting this vari…
Enumerationr/w
Enumerated Values:
1immediateOn
2immediateOff
3immediateReboot
4delayedOn
5delayedOff
6delayedReboot
7cancelPendingCommand
8outletIdentify
.1.3.6.1.4.1.3808.1.1.6.6.1.5.1.5
.1.3.6.1.4.1.3808.1.1.6.6.2.2 · 1 row entry · 7 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2OutletMeteredConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2OutletMeteredConfigTable'
A table of Rack PDU metered outlet configuration data.
ePDU2OutletMeteredConfigEntry row .1.3.6.1.4.1.3808.1.1.6.6.2.2.1
Configuration data from currently queried Rack PDU metered outlet.
Column Syntax OID
The index to the Rack PDU metered outlet configuration table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.1
The user-defined Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.2
The numeric metered outlet ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.3
The user-defined metered outlet name string.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.6.6.2.2.1.4
User-defined outlet low load current threshold in Watts.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.5
User-defined outlet near overload warning threshold in Watts.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.6
User-defined outlet overload current threshold in Watts.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.7

ePDU2OutletMeteredInfoTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.6.2.3 · 1 row entry · 7 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2OutletMeteredInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2OutletMeteredInfoTable'
A table of Rack PDU metered outlet information.
ePDU2OutletMeteredInfoEntry row .1.3.6.1.4.1.3808.1.1.6.6.2.3.1
Information of currently queried Rack PDU metered outlet.
Column Syntax OID
The index to the Rack PDU metered information table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.2
The numeric metered outlet ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.3
The user-defined metered outlet name string.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.6.2.3.1.4
This OID describes the phase connections of the referenced outlet as follows:
seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.
seqPhase2ToNeutral(2) indicates that the outlet is wired fr…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.5
Maximum power rating of Rack PDU metered outlet.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.6
This outlet's numeric bank ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.7
.1.3.6.1.4.1.3808.1.1.6.6.2.4 · 1 row entry · 12 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2OutletMeteredStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2OutletMeteredStatusTable'
A table of Rack PDU metered outlet status data.
ePDU2OutletMeteredStatusEntry row .1.3.6.1.4.1.3808.1.1.6.6.2.4.1
Status data from currently queried Rack PDU metered outlet.
Column Syntax OID
The index to the Rack PDU metered status table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.2
The numeric metered outlet ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.3
The user-defined metered outlet name string.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.6.2.4.1.4
Getting this OID will return the current outlet alarm.
Enumeration
Enumerated Values:
1noLoadAlarm
2underCurrentAlarm
3nearOverCurrentAlarm
4overCurrentAlarm
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.5
Getting this OID will return the measured Outlet load
for an Outlet Monitored Rack PDU in tenths of Amps.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.6
Getting this OID will return the measured Outlet load for
an Outlet Monitored Rack PDU in watts.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.7
The peak power consumption of the Rack PDU load in watts.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.8
Get this oid shows the date and time that peak power
consumption occurred.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.6.2.4.1.9
Get this oid shows the date and time that peak power
consumption started.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.6.2.4.1.10
Energy meter measuring Rack PDU load energy consumption
in tenths of kilowatt-hours.
RFC1155-SMIGauge
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.11
Indicates the date and time of the last device energy
meter reset.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.6.2.4.1.12
.1.3.6.1.4.1.3808.1.1.6.6.3.2 · 1 row entry · 4 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2OutletMonitoredConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2OutletMonitoredConfigTable'
A table of Rack PDU monitored outlet configuration data.
ePDU2OutletMonitoredConfigEntry row .1.3.6.1.4.1.3808.1.1.6.6.3.2.1
Configuration data from currently queried Rack PDU monitored outlet.
Column Syntax OID
The index to the Rack PDU monitored outlet configuration table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.6.6.3.2.1.1
The user-defined Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.3.2.1.2
The numeric monitored outlet ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.3.2.1.3
The user-defined monitored outlet name string.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.6.6.3.2.1.4
.1.3.6.1.4.1.3808.1.1.6.6.3.3 · 1 row entry · 7 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2OutletMonitoredInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2OutletMonitoredInfoTable'
A table of Rack PDU monitored outlet information.
ePDU2OutletMonitoredInfoEntry row .1.3.6.1.4.1.3808.1.1.6.6.3.3.1
Information of currently queried Rack PDU monitored outlet.
Column Syntax OID
The index to the Rack PDU monitored information table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.6.6.3.3.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.3.3.1.2
The numeric monitored outlet ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.3.3.1.3
The user-defined monitored outlet name string.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.6.3.3.1.4
This OID describes the phase connections of the referenced outlet as follows:
seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.
seqPhase2ToNeutral(2) indicates that the outlet is wired fr…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.3.3.1.5
Maximum power rating of Rack PDU monitored outlet.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.3.3.1.6
This outlet's numeric bank ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.3.3.1.7
.1.3.6.1.4.1.3808.1.1.6.6.3.4 · 1 row entry · 4 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2OutletMonitoredStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2OutletMonitoredStatusTable'
A table of Rack PDU monitored outlet status data.
ePDU2OutletMonitoredStatusEntry row .1.3.6.1.4.1.3808.1.1.6.6.3.4.1
Status data from currently queried Rack PDU monitored outlet.
Column Syntax OID
The index to the Rack PDU monitored status table entry.
Integer32
Constraints:
range: 1-96
.1.3.6.1.4.1.3808.1.1.6.6.3.4.1.1
The Rack PDU numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.3.4.1.2
The numeric monitored outlet ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.6.3.4.1.3
The user-defined monitored outlet name string.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.6.6.3.4.1.4

ePDU2SourceConfigTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.9.2 · 1 row entry · 11 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2SourceConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2SourceConfigTable'
A table of Source configuration data.
ePDU2SourceConfigEntry row .1.3.6.1.4.1.3808.1.1.6.9.2.1
Configuration data from Source being queried.
Column Syntax OID
The index to the Automatic Transfer Switch table entry.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.6.9.2.1.1
The Automatic Transfer Switch numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.2.1.2
This variable returns the preferred source of power when both sources are OK
Enumerationr/w
Enumerated Values:
1sourceA
2sourceB
3none
.1.3.6.1.4.1.3808.1.1.6.9.2.1.3
To configure the frequency deviation.
Integer32r/w
Constraints:
range: 1-3
.1.3.6.1.4.1.3808.1.1.6.9.2.1.4
This variable defines the sensitivity to changes in voltage:
high(1) for best protection, low(3) for frequent small line
voltage changes.
Enumerationr/w
Enumerated Values:
1high
2medium
3low
.1.3.6.1.4.1.3808.1.1.6.9.2.1.5
This variable returns the nominal voltage of the input.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.2.1.6
This variable defines the range of acceptable voltage from a power source.
If the voltage measured from the selected input source is not within this
range, the Automatic Transfer Switch will switch over (transfer) to th…
Enumerationr/w
Enumerated Values:
1wide
2medium
3narrow
.1.3.6.1.4.1.3808.1.1.6.9.2.1.7
To configure the Narrow Range value of acceptable voltage
from a power source.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.2.1.8
To configure the Medium Range value of acceptable voltage
from a power source.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.2.1.9
To configure the Wide Range value of acceptable voltage
from a power source.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.2.1.10
Setting this variable will clear all event counts in Automatic Transfer Switch.
Enumerationr/w
Enumerated Values:
1none
2clear
.1.3.6.1.4.1.3808.1.1.6.9.2.1.11

ePDU2SourceInfoTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.9.3 · 1 row entry · 10 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2SourceInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2SourceInfoTable'
A table of Automatic Transfer Switch information.
ePDU2SourceInfoEntry row .1.3.6.1.4.1.3808.1.1.6.9.3.1
Information of the Automatic Transfer Switch being queried.
Column Syntax OID
The index to the Automatic Transfer Switch Information table entry.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.6.9.3.1.1
The Automatic Transfer Switch numeric ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.3.1.2
The Source Switch event counts of Automatic Transfer Switch.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.3.1.3
The Source Preference Change event counts of Automatic Transfer Switch.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.3.1.4
The Preferred Source Frequency Out of Range event counts of Automatic Transfer Switch.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.3.1.5
The Preferred Source Voltage Out of Range event counts of Automatic Transfer Switch.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.3.1.6
The Device Current Overload event counts of Automatic Transfer Switch.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.3.1.7
The Bank 1 Current Overload event counts of Automatic Transfer Switch.
Models that do not support this feature will respond to this OID
with a value of (-1).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.3.1.8
The Bank 2 Current Overload event counts of Automatic Transfer Switch.
Models that do not support this feature will respond to this OID
with a value of (-1).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.3.1.9
The Bank 3 Current Overload event counts of Automatic Transfer Switch.
Models that do not support this feature will respond to this OID
with a value of (-1).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.3.1.10

ePDU2SourceStatusTable

table mandatory
.1.3.6.1.4.1.3808.1.1.6.9.4 · 1 row entry · 16 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk ePDU2SourceStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::ePDU2SourceStatusTable'
A table of Automatic Transfer Switch current status.
ePDU2SourceStatusEntry row .1.3.6.1.4.1.3808.1.1.6.9.4.1
Status data from the Automatic Transfer Switch being queried.
Column Syntax OID
The index to the Automatic Transfer Switch status table entry.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.6.9.4.1.1
The Automatic Transfer Switch numeric ID
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.4.1.2
This variable returns the current source of power.
Enumeration
Enumerated Values:
1sourceA
2sourceB
3none
.1.3.6.1.4.1.3808.1.1.6.9.4.1.3
The Nominal Frequency in 0.1 Hertz.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.4.1.4
The input voltage of source A in 0.1 Volt.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.4.1.5
The input voltage of source B in 0.1 Volt.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.4.1.6
The input frequency of source A in 0.1 Hertz.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.4.1.7
The input frequency of source B in 0.1 Hertz.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.6.9.4.1.8
The input voltage status of source A.
Enumeration
Enumerated Values:
1normal
2overVoltage
3underVoltage
.1.3.6.1.4.1.3808.1.1.6.9.4.1.9
The input voltage status of source B.
Enumeration
Enumerated Values:
1normal
2overVoltage
3underVoltage
.1.3.6.1.4.1.3808.1.1.6.9.4.1.10
The input frequency status of source A.
Enumeration
Enumerated Values:
1normal
2overFrequency
3underFrequency
.1.3.6.1.4.1.3808.1.1.6.9.4.1.11
The input frequency status of source B.
Enumeration
Enumerated Values:
1normal
2overFrequency
3underFrequency
.1.3.6.1.4.1.3808.1.1.6.9.4.1.12
This variable returns the status of the phase sync.
Enumeration
Enumerated Values:
1inSync
2outOfSync
.1.3.6.1.4.1.3808.1.1.6.9.4.1.13
This variable returns the status of the power supply in system.
normal(1) indicates the power supply of source A in normal.
3.3vFailed(2) indicates the power supply 3.3v of source A is failed.
24vFailed(3) indicates the…
Enumeration
Enumerated Values:
1normal
2failed3p3v
3failed24v
4failed3p3and24v
.1.3.6.1.4.1.3808.1.1.6.9.4.1.14
This variable returns the status of the power supply in system.
normal(1) indicates the power supply of source B in normal.
3.3vFailed(2) indicates the power supply 3.3v of source B is failed.
24vFailed(3) indicates the…
Enumeration
Enumerated Values:
1normal
2failed3p3v
3failed24v
4failed3p3and24v
.1.3.6.1.4.1.3808.1.1.6.9.4.1.15
This variable returns the current redundancy state of the ATS.
atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power source if the current source fails.
atsFullyRedundant(2) indicat…
Enumeration
Enumerated Values:
1atsRedundancyLost
2atsFullyRedundant
.1.3.6.1.4.1.3808.1.1.6.9.4.1.16

bmProbesTable

table mandatory
.1.3.6.1.4.1.3808.1.1.7.5.3 · 1 row entry · 4 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk bmProbesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::bmProbesTable'
The battery probes installation information.
bmProbesEntry row .1.3.6.1.4.1.3808.1.1.7.5.3.1
The battery probes installation information.
Indexes
Column Syntax OID
bmProbesIndexmandatory
The index of the bmProbesEntry entry.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.3.1.1
The pack number the battery probe installed.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.3808.1.1.7.5.3.1.2
The string number the battery probe installed.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.3808.1.1.7.5.3.1.3
The battery number the battery probe installed.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.3.1.4

bmProbesVoltageTable

table mandatory
.1.3.6.1.4.1.3808.1.1.7.5.5 · 1 row entry · 10 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk bmProbesVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::bmProbesVoltageTable'
The batteries voltage information.
bmProbesVoltageEntry row .1.3.6.1.4.1.3808.1.1.7.5.5.1
The batteries voltage information.
Column Syntax OID
The index of the BmProbesVoltageEntry entry.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.5.1.1
The battery pack number the battery voltage reading belongs to.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.3808.1.1.7.5.5.1.2
The battery string number the battery voltage reading belongs to.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.3808.1.1.7.5.5.1.3
The battery index to the voltage record within its string.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.5.1.4
The probe index to the voltage record.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.5.1.5
The battery voltage alarm status.
Enumeration
Enumerated Values:
1voltageNormal
2voltageWarnLow
3voltageWarnHigh
4voltageAlarmLow
5voltageAlarmHigh
.1.3.6.1.4.1.3808.1.1.7.5.5.1.6
Getting this oid to get battery voltage, unit in 10mV (0.01 volt).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.7.5.5.1.7
Getting this oid to get battery voltage equalizing power, unit in percentage.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.7.5.5.1.8
The battery soc alarm status.
Enumeration
Enumerated Values:
1voltageSocNormal
2voltageSocWarnLow
3voltageSocWarnHigh
4voltageSocAlarmLow
5voltageSocAlarmHigh
.1.3.6.1.4.1.3808.1.1.7.5.5.1.9
Getting this oid to get battery soc, unit in percentage.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.7.5.5.1.10

bmProbesTempTable

table mandatory
.1.3.6.1.4.1.3808.1.1.7.5.7 · 1 row entry · 7 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk bmProbesTempTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::bmProbesTempTable'
The batteries temperature information.
bmProbesTempEntry row .1.3.6.1.4.1.3808.1.1.7.5.7.1
The batteries temperature information.
Column Syntax OID
The index of the BmProbesTempEntry entry.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.7.1.1
The battery pack number the battery temperature reading belongs to.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.3808.1.1.7.5.7.1.2
The battery string number the battery temperature reading belongs to.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.3808.1.1.7.5.7.1.3
The index to the battery.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.7.1.4
The index to the probe.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.7.1.5
The alarm status of the temperature.
Enumeration
Enumerated Values:
1temperatureNormal
2temperatureWarnLow
3temperatureWarnHigh
4temperatureAlarmLow
5temperatureAlarmHigh
.1.3.6.1.4.1.3808.1.1.7.5.7.1.6
The temperature record, measure in 0.1 degree C.
Integer32
Constraints:
range: -40-100
.1.3.6.1.4.1.3808.1.1.7.5.7.1.7

bmProbesResTable

table mandatory
.1.3.6.1.4.1.3808.1.1.7.5.9 · 1 row entry · 8 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk bmProbesResTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::bmProbesResTable'
The batteries resistance information.
bmProbesResEntry row .1.3.6.1.4.1.3808.1.1.7.5.9.1
The batteries resistance information.
Column Syntax OID
The index of the BmProbesResEntry entry.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.9.1.1
The battery pack number the battery resistance reading belongs to.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.3808.1.1.7.5.9.1.2
The battery string number the battery resistance reading belongs to.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.3808.1.1.7.5.9.1.3
The index to the battery.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.9.1.4
The index to the probe.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.5.9.1.5
The alarm status of the battery resistance.
Enumeration
Enumerated Values:
1resistanceNormal
2resistanceWarnLow
3resistanceWarnHigh
4resistanceAlarmLow
5resistanceAlarmHigh
.1.3.6.1.4.1.3808.1.1.7.5.9.1.6
The resistance of the battery, unit in 0.01 mOhm.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.3808.1.1.7.5.9.1.7
The resistance health status, unit in percentage.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.3808.1.1.7.5.9.1.8

bmStringsTable

table mandatory
.1.3.6.1.4.1.3808.1.1.7.10.3 · 1 row entry · 3 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk bmStringsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::bmStringsTable'
Allows for getting of status of strings.
bmStringsEntry row .1.3.6.1.4.1.3808.1.1.7.10.3.1
The status of strings installation to gather status from.
Indexes
Column Syntax OID
Strings table index
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.7.10.3.1.1
The battery pack number the string installed.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.7.10.3.1.2
The probe number installed in string.
Integer32
Constraints:
range: 1-960
.1.3.6.1.4.1.3808.1.1.7.10.3.1.3

bmStringsVoltageTable

table mandatory
.1.3.6.1.4.1.3808.1.1.7.10.5 · 1 row entry · 6 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk bmStringsVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::bmStringsVoltageTable'
Allows for getting of voltage of strings.
bmStringsVoltageEntry row .1.3.6.1.4.1.3808.1.1.7.10.5.1
The status of string voltage installation to gather status from.
Column Syntax OID
Strings table index
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.7.10.5.1.1
The battery pack number the string installed.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.1.1.7.10.5.1.2
The string voltage alarm status.
Enumeration
Enumerated Values:
1stringvoltageNormal
2stringvoltageWarnLow
3stringvoltageWarnHigh
4stringvoltageAlarmLow
5stringvoltageAlarmHigh
.1.3.6.1.4.1.3808.1.1.7.10.5.1.3
Getting this oid to get string voltage, unit in 10mV (0.01 V).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.7.10.5.1.4
The string soc alarm status.
Enumeration
Enumerated Values:
1stringvoltageSocNormal
2stringvoltageSocWarnLow
3stringvoltageSocWarnHigh
4stringvoltageSocAlarmLow
5stringvoltageSocAlarmHigh
.1.3.6.1.4.1.3808.1.1.7.10.5.1.5
Getting this oid to get string soc, unit in 1%.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.7.10.5.1.6

envir2IdentTable

table mandatory
.1.3.6.1.4.1.3808.1.1.8.1.2 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk envir2IdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::envir2IdentTable'
A table of environment sensor identification information.
envir2IdentEntry row .1.3.6.1.4.1.3808.1.1.8.1.2.1
Identification data from environment sensor being queried.
Column Syntax OID
The index to the environment sensor table entry.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.3808.1.1.8.1.2.1.1
The position of environment sensor.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.1.2.1.2
The name of the environment sensor.
The maximum string size is device dependent.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.8.1.2.1.3
The location of the environment sensor.
The maximum string size is device dependent.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.8.1.2.1.4
The serial number of the environment sensor.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.8.1.2.1.5

envir2TempTable

table mandatory
.1.3.6.1.4.1.3808.1.1.8.2.3 · 1 row entry · 7 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk envir2TempTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::envir2TempTable'
A table of environment sensor identification information in temperature.
envir2TempEntry row .1.3.6.1.4.1.3808.1.1.8.2.3.1
Identification data from environment sensor being queried.
Column Syntax OID
The index to the environment sensor table entry.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.3808.1.1.8.2.3.1.1
The position of environment sensor.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.2.3.1.2
The environment temperature expressed in 1/100.
The value is determined by temperature unit which can be changed in envir2TempUnit.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.2.3.1.3
The high temperature threshold of the environment sensor.
The value is determined by temperature unit which can be changed in envir2TempUnit.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.2.3.1.4
The low temperature threshold of the environment sensor.
The value is determined by temperature unit which can be changed in envir2TempUnit.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.2.3.1.5
The rate of change of the temperature.
The value expressed in degree per 5 minute.
The value is determined by temperature unit which can be changed in envir2TempUnit.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.2.3.1.6
The number of degrees beyond the temperature thresholds
at which an active temperature alarm will be cleared.
This configuration setting applies to all temperature thresholds.
The value is determined by temperature …
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.2.3.1.7

envir2HumidTable

table mandatory
.1.3.6.1.4.1.3808.1.1.8.3.2 · 1 row entry · 7 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk envir2HumidTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::envir2HumidTable'
A table of environment sensor identification information in humidity.
envir2HumidEntry row .1.3.6.1.4.1.3808.1.1.8.3.2.1
Identification data from environment sensor being queried.
Column Syntax OID
The index to the environment sensor table entry.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.3808.1.1.8.3.2.1.1
The position of environment sensor.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.3.2.1.2
The environment relative humidity expressed in 1/100.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.3.2.1.3
The high relative humidity threshold of the environment sensor.
The value expressed in persentage.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.3.2.1.4
The low relative humidity threshold of the environment sensor.
The value expressed in persentage.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.3.2.1.5
The rate of change of the relative humidity.
The value expressed in persentage per 5 minute.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.3.2.1.6
The number of degrees beyond the relative humidity thresholds
at which an active relative humidity alarm will be cleared.
This configuration setting applies to all relative humidity
thresholds.
Units are displayed in pe…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.3.2.1.7

envir2ContactTable

table mandatory
.1.3.6.1.4.1.3808.1.1.8.4.2 · 1 row entry · 6 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk envir2ContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::envir2ContactTable'
Allows for getting of information of each contact of the environment sensor.
envir2ContactEntry row .1.3.6.1.4.1.3808.1.1.8.4.2.1
This gives access to contact entries
Column Syntax OID
The index to the contact of the environment sensor.
Integer32
Constraints:
range: 1-32
.1.3.6.1.4.1.3808.1.1.8.4.2.1.1
The position of environment sensor.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.4.2.1.2
The numeric contact ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.8.4.2.1.3
Getting or setting the name of the contact of the environment sensor.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.8.4.2.1.4
Getting this OID will return the Contact Status.
Enumeration
Enumerated Values:
1contactNormal
2contactAbnormal
.1.3.6.1.4.1.3808.1.1.8.4.2.1.5
Set the contact normal state.
Enumerationr/w
Enumerated Values:
1normalOpen
2normalClose
.1.3.6.1.4.1.3808.1.1.8.4.2.1.6

currIdentTable

table mandatory
.1.3.6.1.4.1.3808.1.1.50.1.6 · 1 row entry · 4 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk currIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::currIdentTable'
Current probe identification table.
currIdentEntry row .1.3.6.1.4.1.3808.1.1.50.1.6.1
Current probe identification entry.
Indexes
Column Syntax OID
The current probe ident index.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.50.1.6.1.1
currIdentNamemandatory
The current probe ident name.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.50.1.6.1.2
The current probe ident location.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.50.1.6.1.3
Number of the current flow measure by the current probe.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.1.6.1.4

currConfigTable

table mandatory
.1.3.6.1.4.1.3808.1.1.50.2.2 · 1 row entry · 14 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk currConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::currConfigTable'
Table provides current flow's configuration parameters.
currConfigEntry row .1.3.6.1.4.1.3808.1.1.50.2.2.1
The current flow's configration parameters entry.
Indexes
Column Syntax OID
Entry index.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.50.2.2.1.1
Connecting current sensor element's rating, unit in 1 A.
Sets to 0 if you do not use current sensor for this measure channel.
Gets as 0 if this measure channel had not used.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.2
Warning threshold for low charge current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.3
Warning threshold for high charge current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.4
Alarm threshold for low charge current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.5
Alarm threshold for high charge current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.6
Warning threshold for low discharge current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.7
Warning threshold for high discharge current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.8
Alarm threshold for low discharge current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.9
Alarm threshold for high discharge current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.10
Warning threshold for low RMS current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.11
Warning threshold for high RMS current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.12
Alarm threshold for low RMS current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.13
Alarm threshold for high RMS current, unit in 0.01A.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.2.2.1.14

currMeasureTable

table mandatory
.1.3.6.1.4.1.3808.1.1.50.3.2 · 1 row entry · 7 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk currMeasureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::currMeasureTable'
Table for the current probe's measurement.
currMeasureEntry row .1.3.6.1.4.1.3808.1.1.50.3.2.1
The status of current sensors installation to gather status from.
Column Syntax OID
The current measurement's index.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.3808.1.1.50.3.2.1.1
The current measurement's current probe name.
RFC1213-MIBDisplayString .1.3.6.1.4.1.3808.1.1.50.3.2.1.2
Current flow measurement's description.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.1.1.50.3.2.1.3
The current alarm status.
For battery system, abnormal value can be (2) to (9).
For AC measure condition, abnormal value can be (50) to (53).
Enumeration
Enumerated Values:
1currentNormal
2chargeCurrentWarnLow
3chargeCurrentWarnHigh
4chargeCurrentAlarmLow
5chargeCurrentAlarmHigh
6dischargeCurrentWarnLow
7dischargeCurrentWarnHigh
8dischargeCurrentAlarmLow
9dischargeCurrentAlarmHigh
10rmsCurrentWarnLow
11rmsCurrentWarnHigh
12rmsCurrentAlarmLow
13rmsCurrentAlarmHigh
.1.3.6.1.4.1.3808.1.1.50.3.2.1.4
For battery system to get battery charging state.
Enumeration
Enumerated Values:
1batteryCharging
2batteryDischarging
3notDetermine
.1.3.6.1.4.1.3808.1.1.50.3.2.1.5
Getting this oid to get current measurement, unit in 10mA (0.01 A).
For battery system, negative value indicates the discharge state.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3808.1.1.50.3.2.1.6
Getting this oid to check the configuration be matched with actual installation.
Setting this oid to tell system what the measure target is.
For the DC current(prefix as dc), charge/discharge threshold would be consid…
Enumerationr/w
Enumerated Values:
1dcBatteryStringA
2dcBatteryStringB
3dcBatteryStringC
4dcBatteryStringD
5dcBatteryStringE
6dcBatteryStringF
7dcBatteryStringG
8dcBatteryStringH
9dcReserved
20acInputCurrent
.1.3.6.1.4.1.3808.1.1.50.3.2.1.7

mconfigTrapAccepterTable

table mandatory
.1.3.6.1.4.1.3808.2.1.2 · 1 row entry · 5 columns
Uses the cyberpower variant from /opt/observium/mibs/cyberpower.
Command help
Walk mconfigTrapAccepterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPS-MIB' -M '/opt/observium/mibs/cyberpower:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPS-MIB::mconfigTrapAccepterTable'
A list of receivers to send traps to. The numbers of
entries are given by the value of mconfigNumTrapAccepters.
mconfigTrapAccepterEntry row .1.3.6.1.4.1.3808.2.1.2.1
The receivers to send traps to.
Indexes
Column Syntax OID
trapIndexmandatory
The trap receiver entry index.
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.3808.2.1.2.1.1
accepterAddrmandatory
The trap receiver IP address.
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.3808.2.1.2.1.2
The trap receiver community name.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.3808.2.1.2.1.3
The trap receiver severity level. Traps are marked in severity level
as informational(1), warning(2), severe(3). Only send the traps of
equal or greater severity than this value to the receiver.
Enumeration
Enumerated Values:
1information
2warning
3severe
.1.3.6.1.4.1.3808.2.1.2.1.4
A receiver will accept traps if yes, and none if no.
Enumerationr/w
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.3808.2.1.2.1.5