.1.3.6.1.4.1.5591.1.4.2
·
1 row entry
·
35 columns
Table containing information about the individual power supplies being monitored
List of information about each power supply being monitored.
Indexes
psDeviceAddress
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
psDeviceAddress
mandatory
Index into the psDeviceTable.Address of this device on the RS-485 path
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5591.1.4.2.1.1 |
||||||||||
|
psProtocolVersion
mandatory
Version of the SCTE HMS protocol implemented in the monitored
equipment. The 'Protocol Version' implementation will comply with the defined protocol in the SCTE 25-3 (formerly HMS 022) document with the corresponding… |
Integer32 Constraints: range: 1-254 |
.1.3.6.1.4.1.5591.1.4.2.1.2 |
||||||||||
|
psSoftwareVersion
mandatory
The content of this field is vendor specific. The intent is to provide
a text representation of the power supply or generator system software version. Any printable ASCII characters can be included in this field. NULL… |
OctetString Constraints: range: 8-8 |
.1.3.6.1.4.1.5591.1.4.2.1.3 |
||||||||||
|
psDeviceId
mandatory
The content of this field is vendor specific. The intent is to provide
manufacturer and/or product specific ASCII text information that will propagate to the manager's console verbatim. The following special characte… |
OctetString Constraints: range: 32-32 |
.1.3.6.1.4.1.5591.1.4.2.1.4 |
||||||||||
|
psBatteries
mandatory
Current number of batteries per battery string.
|
Integer32 Constraints: range: 0-8 |
.1.3.6.1.4.1.5591.1.4.2.1.5 |
||||||||||
|
psBatteryStrings
mandatory
Current number of battery strings.
|
Integer32 Constraints: range: 0-2 |
.1.3.6.1.4.1.5591.1.4.2.1.6 |
||||||||||
|
psTempSensors
mandatory
Number of Battery temperature sensors.
|
Integer32 Constraints: range: 0-2 |
.1.3.6.1.4.1.5591.1.4.2.1.7 |
||||||||||
|
psOutputs
mandatory
Number of power supply outputs.
|
Integer32 Constraints: range: 1-5 |
.1.3.6.1.4.1.5591.1.4.2.1.8 |
||||||||||
|
psBatteryCurrentSupport
mandatory
Bit Map that defines if battery current is measured in this installation.
Bit set means this particular string supports this measurement. Bits Addresses 0 Not used 1 1 String 1 has battery current suppo… |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5591.1.4.2.1.9 |
||||||||||
|
psFloatCurrentSupport
mandatory
Bit Map that defines if float current is measured in this installation.
Bit set means this particular string supports this measurement. Bits Addresses 0 Not used 1 1 String 1 has float current support … |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5591.1.4.2.1.10 |
||||||||||
|
psOutputVoltageSupport
mandatory
Defines if power supply supports monitoring of output voltage
1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.11 |
||||||||||
|
psInputVoltageSupport
mandatory
Defines if power supply supports monitoring of input or line voltage
1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported - value in psInputVoltagePresence. 3 = Field is su… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.12 |
||||||||||
|
psPowerSupplyTest
mandatory
Defines if power supply supports the remote test feature:
1 = Function not supported. 2 - Function is supported. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.13 |
||||||||||
|
psMajorAlarmSupport
mandatory
Defines if the power supply supports the major alarm indicator:
1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
Constraints: range: 0-255 |
.1.3.6.1.4.1.5591.1.4.2.1.14 |
||||||||||
|
psMinorAlarmSupport
mandatory
Defines if the power supply supports the minor alarm indicator:
1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
Constraints: range: 0-255 |
.1.3.6.1.4.1.5591.1.4.2.1.15 |
||||||||||
|
psTamperSupport
mandatory
Defines if the enclosure door switch is installed in this location:
1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
Constraints: range: 0-255 |
.1.3.6.1.4.1.5591.1.4.2.1.16 |
||||||||||
|
psBatteryVoltageSupport
mandatory
Defines the if batteries or string voltage are available:
1 = No battery voltage monitoring is available. 2 = Only full string battery voltage is available. 3 = Both individual battery and full string voltages are avail… |
Enumeration Enumerated Values:
Constraints: range: 0-127 |
.1.3.6.1.4.1.5591.1.4.2.1.17 |
||||||||||
|
psOutputPowerSupport
mandatory
Defines if the output power measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.18 |
||||||||||
|
psOutputFrequencySupport
mandatory
Defines if the output frequency measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.19 |
||||||||||
|
psInputCurrentSupport
mandatory
Defines if the input current measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.20 |
||||||||||
|
psInputPowerSupport
mandatory
Defines if the input power measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.21 |
||||||||||
|
psOutputVoltage
mandatory
Power supply output voltage in 1/100 Volts units.
This RMS value is common for all outputs in a multiple output system. This item requires an entry in the properties MIB |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.2.1.22 |
||||||||||
|
psInputVoltage
optional
Scaled representation of input 'line' or 'grid' voltage. This is an
RMS value in 1/100 Volts units. This item requires an entry in the properties MIB. |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.2.1.23 |
||||||||||
|
psInverterStatus
optional
Status of power supply inverter. Enumerated value indicates current
status of inverter. 1 = OFF, 2 = ON: AC Line Fail, 3 = ON: Local Test Cycle, 4 = ON: Remote test initiated 5 = ALARM: Last Test Failed … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.24 |
||||||||||
|
psMajorAlarm
optional
Service has been dropped or a service interruption is imminent.
Indicates that an immediate truck roll is appropriate. Specific alarms and alarm nomenclature varies between vendors. Vendors should disclose all conditi… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.25 |
||||||||||
|
psMinorAlarm
optional
A non-service effecting condition has occurred and should
be monitored. Specific alarms and alarm nomenclature varies between vendors. Vendors should disclose all conditions that contribute to this alarm in appropria… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.26 |
||||||||||
|
psTamper
optional
Indicates status of enclosure door. This notification is
NOT included in the 'Major' or 'Minor' alarm fields. Individual users / installations must determine if a door open status represents an alarm and if so, of … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.27 |
||||||||||
|
psTotalStringVoltage
optional
Scaled representation of the full battery string in 1/100 Volts units.
This item requires an entry in the properties MIB. |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.2.1.28 |
||||||||||
|
psEquipmentControl
optional
Equipment control
1 = Discontinue inverter operation, 2 = Begin inverter operation |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.29 |
||||||||||
|
psPowerOut
optional
Representation of power supply output power in 1 W.
This item requires an entry in the properties MIB. |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.2.1.30 |
||||||||||
|
psFrequencyOut
optional
Scaled representation of the power supply output frequency in 1/100 Hz.
This item requires an entry in the properties MIB. |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.2.1.31 |
||||||||||
|
psRMSCurrentIn
optional
Scaled representation of the power supply RMS input current in 1/100 A.
This item requires an entry in the properties MIB. |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.2.1.32 |
||||||||||
|
psPowerIn
optional
Representation of the power supply input power in 1 W.
This item requires an entry in the properties MIB. |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.2.1.33 |
||||||||||
|
psInputVoltagePresence
optional
Digital value indicating that line voltage is present and within
tolerance or not. 1 = lost 2 = ok. This item requires entries in the discrete properties MIB. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.34 |
||||||||||
|
psFrequencyIn
mandatory
Operational frequency for input voltage
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5591.1.4.2.1.35 |
.1.3.6.1.4.1.5591.1.4.3
·
1 row entry
·
5 columns
Table containing strings data
List of information about each string. Indexed by device and string number
Indexes
psStringDeviceAddress psString
| Column | Syntax | OID |
|---|---|---|
|
psStringDeviceAddress
mandatory
Index into the psStringTable. Corresponds to psDeviceAddress in psDeviceTable.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5591.1.4.3.1.1 |
|
psString
mandatory
Index into the psStringTable.
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.5591.1.4.3.1.2 |
|
psStringChargeCurrent
optional
Scaled representation of battery string charge current.
This is an RMS value in 1/100 Amps. When batteries being discharged, this value will = 0. This item requires an entry in the properties MIB. |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.3.1.3 |
|
psStringDischargeCurrent
optional
Scaled representation of battery string discharge current. This is
an RMS value in 1/100 Amps.If multiple strings are installed but only one measurement sensor is used, this value represents the total battery discharge… |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.3.1.4 |
|
psStringFloat
optional
Scaled representation of battery 'float' charge current in 1/100 Amps.
This field will be '0' under conditions other than during actual float charging. When this field is non-zero (reporting float current), other bat… |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.3.1.5 |
.1.3.6.1.4.1.5591.1.4.4
·
1 row entry
·
4 columns
Table containing batteries voltages
List of information about each battery.Indexed by device number and string
Indexes
psBatteryDeviceAddress psBatteryString psBattery
| Column | Syntax | OID |
|---|---|---|
|
psBatteryDeviceAddress
mandatory
Index into the psBatteryTable. Corresponds to psDeviceAddress in psDeviceTable.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5591.1.4.4.1.1 |
|
psBatteryString
mandatory
Index into the psBatteryTable. Corresponds to psString in psStringTable.
|
Integer32 Constraints: range: 3701-3708range: 1-2 |
.1.3.6.1.4.1.5591.1.4.4.1.2 |
|
psBattery
mandatory
Index into the psBatteryTable.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5591.1.4.4.1.3 |
|
psBatteryVoltage
optional
Scaled representation of an individual battery voltage in 1/100 Volts.
String 'A' is used if only one battery string is active. This item requires an entry in the properties MIB. |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.4.1.4 |
.1.3.6.1.4.1.5591.1.4.5
·
1 row entry
·
3 columns
Table containing output currents
List of information about each Output port. Indexed by device and port number
Indexes
psOutputDeviceAddress psOutput
| Column | Syntax | OID |
|---|---|---|
|
psOutputDeviceAddress
mandatory
Index into the psOutputTable.Corresponds to psDeviceAddress in psDeviceTable.
|
Integer32 Constraints: range: 1-8range: 1-8 |
.1.3.6.1.4.1.5591.1.4.5.1.1 |
|
psOutput
mandatory
Index into the psOutputTable. Output number
|
Integer32 Constraints: range: 1-5 |
.1.3.6.1.4.1.5591.1.4.5.1.2 |
|
psOutputCurrent
optional
Scaled representation of power supply RMS output current in 1/100 Amps.
This value is the total power supply output current if only one output is active. If multiple outputs are active, this value represents output #… |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5591.1.4.5.1.3 |
.1.3.6.1.4.1.5591.1.4.6
·
1 row entry
·
3 columns
Table containing temperature sensors information
List of information about each Temperature sensor. Indexed by device and Sensor number
Indexes
psTempDeviceAddress psTemperatureSensor
| Column | Syntax | OID |
|---|---|---|
|
psTempDeviceAddress
mandatory
Index into the psTemperatureSensorTable.Corresponds to psDeviceAddress in psDeviceTable.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5591.1.4.6.1.1 |
|
psTemperatureSensor
mandatory
Index into the psTemperatureSensorTable. Temperature sensor number
|
Integer32 Constraints: range: 3711-3718range: 1-2 |
.1.3.6.1.4.1.5591.1.4.6.1.2 |
|
psTemperature
optional
Scaled representation of temperature.
in degrees C with a range of -40 to + 80 degrees C. This item requires an entry in the properties MIB. |
Integer32 Constraints: range: 1-8range: -40-80 |
.1.3.6.1.4.1.5591.1.4.6.1.3 |