psStringFloat
SCTE-HMS-PS-MIB ·
.1.3.6.1.4.1.5591.1.4.3.1.5
Object
column
optional
Integer32
Scaled representation of battery 'float' charge current in 1/100 Amps. This field will be '0' under conditions other than during actual float charging. When this field is non-zero (reporting float current), other battery current values (charge and discharge) should be discarded. If multiple strings are installed but only one measurement sensor is used, this field represents the total float current. This item requires an entry in the properties MIB.
Context
- MIB
- SCTE-HMS-PS-MIB
- OID
.1.3.6.1.4.1.5591.1.4.3.1.5- Type
- column
- Access
- readonly
- Status
- optional
- Parent
- psStringEntry
- Table
- psStringTable
- Siblings
- 4
Syntax
Integer32
Values & Constraints
Object Constraints
range: 0-65535
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| psStringDeviceAddress mandatory Index into the psStringTable. Corresponds to psDeviceAddress in psDeviceTable. | column | Integer32 | .1.3.6.1.4.1.5591.1.4.3.1.1 |
| psString mandatory Index into the psStringTable. | column | Integer32 | .1.3.6.1.4.1.5591.1.4.3.1.2 |
| psStringChargeCurrent optional Scaled representation of battery string charge current.
This is an RMS value in 1/100 Amps. When batteries being discharged,
this value will = 0.
This item requires an entry in t… | column | Integer32 | .1.3.6.1.4.1.5591.1.4.3.1.3 |
| psStringDischargeCurrent optional Scaled representation of battery string discharge current. This is
an RMS value in 1/100 Amps.If multiple strings are installed but only
one measurement sensor is used, this valu… | column | Integer32 | .1.3.6.1.4.1.5591.1.4.3.1.4 |