.1.3.6.1.4.1.232.167.2.3.5.2 · 1 row entry · 10 columns
Headline of sensor table
cpqWcrmInternalSensorEntry entry .1.3.6.1.4.1.232.167.2.3.5.2.1
Entries of sensor table
Indexes
internalSensorIndex
Column Syntax OID
internalSensorIndex mandatory
Index for the list of value entries. Its value ranges
between 1 and the value of cpqWcrmInternalNumberOfSensors.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.232.167.2.3.5.2.1.1
internalSensorType mandatory
Type of sensor which is connected to internal sensor to sensor[internalSensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor…
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4access
5vibration
6motion
7smoke
8airFlow
9type6
10temperature
11current4to20
12humidity
13userNO
14userNC
17voltOK
18voltage
19fanOK
20leakage
.1.3.6.1.4.1.232.167.2.3.5.2.1.2
internalSensorText mandatory
Descriptional text for each sensor (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.232.167.2.3.5.2.1.3
internalSensorStatus mandatory
Actual status of the sensor
Enumeration
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7warning
8tooLow
9tooHigh
.1.3.6.1.4.1.232.167.2.3.5.2.1.4
internalSensorValue mandatory
Value of sensor
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.3.5.2.1.5
internalSensorSetHigh mandatory
Value for high setpoint of sensor
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.3.5.2.1.6
internalSensorSetLow mandatory
Value for low setpoint of sensor,
also used as alarm delay
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.3.5.2.1.7
internalSensorSetWarn mandatory
Value for warning setpoint of sensor,
also used as fan threshold
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.3.5.2.1.8
internalSensorValueScale mandatory
Scaling factor for scaled sensor value, e. g.
-100 -> value has to be divided by 100
+100 -> value has to be multiplied by 100.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.3.5.2.1.9
internalSensorScaledValue mandatory
Scaled value of sensor
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.3.5.2.1.10
.1.3.6.1.4.1.232.167.2.3.6.2 · 1 row entry · 9 columns
Headline of output table
cpqWcrmInternalOutputEntry entry .1.3.6.1.4.1.232.167.2.3.6.2.1
Entries of output table
Indexes
internalOutputIndex
Column Syntax OID
internalOutputIndex mandatory
Index for the list of output entries. Its value ranges
between 1 and the value of cpqWcrmInternalNumberOfOutputs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.232.167.2.3.6.2.1.1
internalOutputType mandatory
Type of output which is connected to internal sensor to output[internalOutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 6, universal relay output
5: …
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4universalOut
5powerOut
.1.3.6.1.4.1.232.167.2.3.6.2.1.2
internalOutputText mandatory
Descriptional text for each output (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.232.167.2.3.6.2.1.3
internalOutputStatus mandatory
Actual status of the output
Enumerationr/w
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7setOff
8setOn
.1.3.6.1.4.1.232.167.2.3.6.2.1.4
internalOutputValue mandatory
Value for output
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.3.6.2.1.5
internalOutputSet mandatory
Command for output
Enumerationr/w
Enumerated Values:
1off
2on
3lock
4unlock
5unlockDelay
.1.3.6.1.4.1.232.167.2.3.6.2.1.6
internalOutputConfig mandatory
Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control
Enumerationr/w
Enumerated Values:
1disRemote
2enRemote
.1.3.6.1.4.1.232.167.2.3.6.2.1.7
internalOutputDelay mandatory
Unsigned Value for delay,
after this time the output will fall into the previous state
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.3.6.2.1.8
internalOutputTimeoutAction mandatory
State for output if timeout (RS422) occurs
Enumerationr/w
Enumerated Values:
1stay
2off
3on
.1.3.6.1.4.1.232.167.2.3.6.2.1.9
.1.3.6.1.4.1.232.167.2.3.7.2 · 1 row entry · 10 columns
Headline of message table
cpqWcrmInternalMsgEntry entry .1.3.6.1.4.1.232.167.2.3.7.2.1
Entries of message table
Indexes
internalMsgIndex
Column Syntax OID
internalMsgIndex mandatory
Index for the list of message entries. Its value ranges
between 1 and the value of cpqWcrmInternalNumberOfMsgs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.232.167.2.3.7.2.1.1
internalMsgText mandatory
Descriptional text for each message (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.232.167.2.3.7.2.1.2
internalMsgStatus mandatory
Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog val…
Enumeration
Enumerated Values:
1notAvail
2configChanged
3error
4ok
5alarm
6warning
7tooLow
8tooHigh
9setOff
10setOn
.1.3.6.1.4.1.232.167.2.3.7.2.1.3
internalMsgRelay mandatory
Setup of Alarm relay for this message/alarm
1: no switching of alarm relay
2: switching of alarm relay
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.3.7.2.1.4
internalMsgBeeper mandatory
Setup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarm
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.3.7.2.1.5
internalMsgTrap1 mandatory
Trap receiver 1 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.3.7.2.1.6
internalMsgTrap2 mandatory
Trap receiver 2 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.3.7.2.1.7
internalMsgTrap3 mandatory
Trap receiver 3 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.3.7.2.1.8
internalMsgTrap4 mandatory
Trap receiver 4 and Event Logging activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.3.7.2.1.9
internalMsgReset mandatory
Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key
Enumerationr/w
Enumerated Values:
1auto
2manual
.1.3.6.1.4.1.232.167.2.3.7.2.1.10
.1.3.6.1.4.1.232.167.2.4.5.2 · 1 row entry · 10 columns
Headline of sensor table
cpqWcrmWaterCoolUnitSensorEntry entry .1.3.6.1.4.1.232.167.2.4.5.2.1
Entries of sensor table
Indexes
waterCoolUnitSensorIndex
Column Syntax OID
waterCoolUnitSensorIndex mandatory
Index for the list of value entries. Its value ranges
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfSensors.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.232.167.2.4.5.2.1.1
waterCoolUnitSensorType mandatory
Type of sensor which is connected to internal sensor to sensor[internalSensorIndex]
1: no sensor connected -- Type 1 is not reported by the agent in this table.
2: sensor failure -- Type 2 is not reported by the a…
Enumeration
Enumerated Values:
4tempIn
5tempOut
6heatFlow
7alarm
8warning
9rpmFan1
10rpmFan2
11rpmFan3
12fanSpeed
13tempIn1
14tempOut1
15tempIn2
16tempOut2
17tempIn3
18tempOut3
19tempWaterIn
20tempWaterOut
21waterFlow
22valve
23status
24condensateDuration
25condensateCycles
26rpmFan4
27rpmFan5
28rpmFan6
29transfSwitch
30valveActValue
31dewPointValue
32foundFans
33isolationValveInlet
34isolationValveFacility
35isolationValveInfrastructure
36controlValveFacility
37controlValveInfrastructure
38tempIn4
39tempIn5
40tempIn6
41waterPressureSupply
42waterPressureReturn
43airDiffPressure1
44airDiffPressure2
45acInput1
46acInput2
47frontDoor
48rearDoor
49leakMidLevel
50leakOverflow1
51leakOverflow2
52condensate
53dewPointValue2
54humidityValue
55humidityValue2
56pump
57tempeValue1
58tempeValue2
59dewPointAverage
60percentFan1
61percentFan2
62percentFan3
63percentFan4
64percentFan5
65percentFan6
.1.3.6.1.4.1.232.167.2.4.5.2.1.2
waterCoolUnitSensorText mandatory
Descriptional text for each sensor (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.232.167.2.4.5.2.1.3
waterCoolUnitSensorStatus mandatory
Actual status of the sensor
Enumeration
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7warning
8tooLow
9tooHigh
.1.3.6.1.4.1.232.167.2.4.5.2.1.4
waterCoolUnitSensorValue mandatory
Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex)

If msg index = 1, 5 or 6
This value represents the actual Server Intake Temperature.

If msg index = 2:
This valu…
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.4.5.2.1.5
waterCoolUnitSensorSetHigh mandatory
Value for high setpoint of sensor
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.4.5.2.1.6
waterCoolUnitSensorSetLow mandatory
Value for low setpoint of sensor,
also used as alarm delay
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.4.5.2.1.7
waterCoolUnitSensorSetWarn mandatory
Value for warning setpoint of sensor,
also used as fan threshold
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.4.5.2.1.8
waterCoolUnitSensorValueScale mandatory
Scaling factor for scaled sensor value to get the unscaled value, e. g.
-100 -> waterCoolUnitSensorScaledValue has to be divided by 100
+100 -> waterCoolUnitSensorScaledValue has to be multiplied by 100.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.4.5.2.1.9
waterCoolUnitSensorScaledValue mandatory
Scaled value of sensor
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.4.5.2.1.10
.1.3.6.1.4.1.232.167.2.4.6.2 · 1 row entry · 9 columns
Headline of output table
cpqWcrmWaterCoolUnitOutputEntry entry .1.3.6.1.4.1.232.167.2.4.6.2.1
Entries of output table
Indexes
waterCoolUnitOutputIndex
Column Syntax OID
waterCoolUnitOutputIndex mandatory
Index for the list of output entries. Its value ranges
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfOutputs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.232.167.2.4.6.2.1.1
waterCoolUnitOutputType mandatory
Type of output which is connected to water cool unit to output[waterCoolUnitOutputIndex]
1: no output connected
2: output failure
3: value overflow
4: water valve setpoint
5: water valve hysteresis
6: command for man…
Enumeration
Enumerated Values:
1notAvail
2failure
3overflow
4setpoint
5hysteresis
6command
7controlMode
8fanSpeedMin
9dTmin
10dTmax
11cpWatert
12setHeatload
13setEdoFlow
14setEdoHeat
15setCondCycles
16setCondRun
17doorControl
18pidContrKP
19pidContrKI
20pidContrKD
21pidSampleTime
22installedFans
23offsetCW
24offsetHW
25valveControlMode
26isolationValveInletManual
27isolationValveFacilityManual
28isolationValveInfrastructureManual
29controlValveFacilityManual
30controlValveInfrastructureManual
31fanControlMode
32fan1Manual
33fan2Manual
34fan3Manual
35fan4Manual
36setpointAirDifPressure
37pidContrKPFan
38pidContrKIFan
39pidContrKDFan
40pidSampleTimeFan
41dewpointOffset
42maxItAirTemperature
43dewpointControlMode
.1.3.6.1.4.1.232.167.2.4.6.2.1.2
waterCoolUnitOutputText mandatory
Descriptional text for each output (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.232.167.2.4.6.2.1.3
waterCoolUnitOutputStatus mandatory
Actual status of the output
Enumerationr/w
Enumerated Values:
1notAvail
2lost
3changed
4ok
5off
6on
7setOff
8setOn
.1.3.6.1.4.1.232.167.2.4.6.2.1.4
waterCoolUnitOutputValue mandatory
Signed value for output
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.4.6.2.1.5
waterCoolUnitOutputSet mandatory
Command for output
Enumerationr/w
Enumerated Values:
1off
2on
3lock
4unlock
5unlockDelay
.1.3.6.1.4.1.232.167.2.4.6.2.1.6
waterCoolUnitOutputConfig mandatory
Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control
Enumerationr/w
Enumerated Values:
1disRemote
2enRemote
.1.3.6.1.4.1.232.167.2.4.6.2.1.7
waterCoolUnitOutputDelay mandatory
Unsigned Value for delay,
after this time the output will fall into the previous state
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.167.2.4.6.2.1.8
waterCoolUnitOutputTimeoutAction mandatory
State for output if timeout (RS422) occurs
Enumerationr/w
Enumerated Values:
1stay
2off
3on
.1.3.6.1.4.1.232.167.2.4.6.2.1.9
.1.3.6.1.4.1.232.167.2.4.7.2 · 1 row entry · 10 columns
Headline of message table
cpqWcrmWaterCoolUnitMsgEntry entry .1.3.6.1.4.1.232.167.2.4.7.2.1
Entries of message table
Indexes
waterCoolUnitMsgIndex
Column Syntax OID
waterCoolUnitMsgIndex mandatory
Index for the list of alarm entries. Its value ranges
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfMsgs.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.232.167.2.4.7.2.1.1
waterCoolUnitMsgText mandatory
Descriptional text for each message (entry in the table)
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.232.167.2.4.7.2.1.2
waterCoolUnitMsgStatus mandatory
Actual message status
4: OK
5: alarm
6: warning
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
Enumeration
Enumerated Values:
1notAvail
2configChanged
3error
4ok
5alarm
6warning
7tooLow
8tooHigh
9setOff
10setOn
.1.3.6.1.4.1.232.167.2.4.7.2.1.3
waterCoolUnitMsgRelay mandatory
Setup of Alarm relay for this alarm
2: no switching of alarm relay
1: switching of alarm relay
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.4.7.2.1.4
waterCoolUnitMsgBeeper mandatory
Setup of Alarm beeper for this alarm
2: no audible alarm
1: audible alarm
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.4.7.2.1.5
waterCoolUnitMsgTrap1 mandatory
Trap receiver 1 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.4.7.2.1.6
waterCoolUnitMsgTrap2 mandatory
Trap receiver 2 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.4.7.2.1.7
waterCoolUnitMsgTrap3 mandatory
Trap receiver 3 activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.4.7.2.1.8
waterCoolUnitMsgTrap4 mandatory
Trap receiver 4 and Event Logging activated
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.232.167.2.4.7.2.1.9
waterCoolUnitMsgReset mandatory
Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key
Enumerationr/w
Enumerated Values:
1auto
2manual
.1.3.6.1.4.1.232.167.2.4.7.2.1.10

cpqWcrmTimerTable

table mandatory
.1.3.6.1.4.1.232.167.3.1.8.2 · 1 row entry · 7 columns
Headline of status-table
cpqWcrmTimerEntry entry .1.3.6.1.4.1.232.167.3.1.8.2.1
Entries of timer-table
Indexes
cpqWcrmTimerIndex
Column Syntax OID
cpqWcrmTimerIndex mandatory
Index for the list of timer entries. Its value ranges
between 1 and the value of cpqWcrmTimerNumber.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.232.167.3.1.8.2.1.1
cpqWcrmTimerStatus mandatory
Actual status of the timer
Enumeration
Enumerated Values:
1switchedOff
2switchedOn
3noTime
.1.3.6.1.4.1.232.167.3.1.8.2.1.2
cpqWcrmTimerDayOfWeek mandatory
Selection of day of week for timer to switch
Enumerationr/w
Enumerated Values:
1sun
2mon
3tue
4wed
5thu
6fri
7sat
8sat-sun
9mon-fri
10mon-sun
.1.3.6.1.4.1.232.167.3.1.8.2.1.3
cpqWcrmTimeOn mandatory
Time to switch on current function,
Format: HH:MM
OctetStringr/w
Constraints:
range: 0-5
.1.3.6.1.4.1.232.167.3.1.8.2.1.4
cpqWcrmTimeOff mandatory
Time to switch off current function,
Format: HH:MM
OctetStringr/w
Constraints:
range: 0-5
.1.3.6.1.4.1.232.167.3.1.8.2.1.5
cpqWcrmTimeControl mandatory
Control via RTC
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.232.167.3.1.8.2.1.6
cpqWcrmTimerFunction mandatory
Function which is controlled via timer
1-4: sending Traps to this Trap receiver will be disabled
5 - 8: scheduled alarm off
Enumerationr/w
Enumerated Values:
1disTrapRec1
2disTrapRec2
3disTrapRec3
4disTrapRec4
5schedule1
6schedule2
7schedule3
8schedule4
.1.3.6.1.4.1.232.167.3.1.8.2.1.7

cpqWcrmTrapTableTable

table mandatory
.1.3.6.1.4.1.232.167.4.7.2 · 1 row entry · 4 columns
A list of trap-receiver entries
cpqWcrmTrapTableEntry entry .1.3.6.1.4.1.232.167.4.7.2.1
Entries of trapTable
Indexes
trapIndex
Column Syntax OID
trapIndex mandatory
Index for the trap-receiver-table. Its value ranges between
1 and the value of traptableNumber
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.232.167.4.7.2.1.1
trapStatus mandatory
Enable or disable trap receiver
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.232.167.4.7.2.1.2
trapIPaddress mandatory
IP-address of trap-receiver
OctetStringr/w
Constraints:
range: 0-15
.1.3.6.1.4.1.232.167.4.7.2.1.3
trapIPV4V6address mandatory
IP-address of trap-receiver
OctetStringr/w
Constraints:
range: 0-64