waterCoolUnitSensorValue
CPQWCRM-MIB ·
.1.3.6.1.4.1.232.167.2.4.5.2.1.5
Object
column
mandatory
Integer32
Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex)
If msg index = 1, 5 or 6
This value represents the actual Server Intake Temperature.
If msg index = 2:
This value represents the bit coded warning condition
Bit 0: Top Fan Module Failed
Bit 1: Middle Fan Module Failed
Bit 2: Bottom Fan Module Failed
Bit 3: Top HEX Intake Air Temperature Sensor to Server Failed
Bit 4: Top HEX Exhaust Air Temperature Sensor from Server Failed
Bit 5: Middle HEX Intake Air Temperature Sensor to Server Failed
Bit 6: Middle HEX Exhaust Air Temperature Sensor from Server Failed
Bit 7: Bottom HEX Intake Air Temperature Sensor to Server Failed
Bit 8: Bottom HEX Exhaust Air Temperature Sensor from Server Failed
Bit 9: Air Temperature Sensor Failed
Bit 10: Top Fan not installed
Bit 11: Middle Fan not installed
Bit 12: Bottom Fan not installed
Bit 13: Waterflow low
Bit 14: Water Unit Temperature Input Out of Range
Bit 15: Water Unit Temperature Output Out of Range
Bit 16: Waterflow Sensor Value Out of Range
Bit 17: Water Valve Failed
Bit 18: Leakdetector Failed
Bit 19: Heat Load Warning
Bit 20: The Condensation Pump has exceeded the max. number of cycles
Bit 21: The Condensation Pump has exceeded the max. Running Time
Bit 27: Dewpoint warning
Bit 28: Humidity sensor failed
Bit 29: Front door access sensor failed
Bit 30: Rear door access sensor failed
If msg index = 3:
This value represents the bit coded alarm condition
Bit 0: Leakage Detected
Bit 1: Comm. Failure IIC
Bit 5: Front and Rear Door Opened
Context
- MIB
- CPQWCRM-MIB
- OID
.1.3.6.1.4.1.232.167.2.4.5.2.1.5- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- cpqWcrmWaterCoolUnitSensorEntry
- Table
- cpqWcrmWaterCoolUnitSensorTable
- Siblings
- 9
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| waterCoolUnitSensorIndex mandatory Index for the list of value entries. Its value ranges
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfSensors. | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.1 |
| waterCoolUnitSensorScaledValue mandatory Scaled value of sensor | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.10 |
| waterCoolUnitSensorType mandatory Type of sensor which is connected to internal sensor to sensor[internalSensorIndex]
1: no sensor connected -- Type 1 is not reported by the agent in this table.
2: sensor failure… | column | Enumeration | .1.3.6.1.4.1.232.167.2.4.5.2.1.2 |
| waterCoolUnitSensorText mandatory Descriptional text for each sensor (entry in the table) | column | OctetString | .1.3.6.1.4.1.232.167.2.4.5.2.1.3 |
| waterCoolUnitSensorStatus mandatory Actual status of the sensor | column | Enumeration | .1.3.6.1.4.1.232.167.2.4.5.2.1.4 |
| waterCoolUnitSensorSetHigh mandatory Value for high setpoint of sensor | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.6 |
| waterCoolUnitSensorSetLow mandatory Value for low setpoint of sensor,
also used as alarm delay | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.7 |
| waterCoolUnitSensorSetWarn mandatory Value for warning setpoint of sensor,
also used as fan threshold | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.8 |
| waterCoolUnitSensorValueScale mandatory Scaling factor for scaled sensor value to get the unscaled value, e. g.
-100 -> waterCoolUnitSensorScaledValue has to be divided by 100