waterCoolUnitSensorType
CPQWCRM-MIB ·
.1.3.6.1.4.1.232.167.2.4.5.2.1.2
Object
column
mandatory
Enumeration
Type of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected -- Type 1 is not reported by the agent in this table. 2: sensor failure -- Type 2 is not reported by the agent in this table. 3: value overflow -- Type 3 is not reported by the agent in this table. 4: average temperature of air inlet to rack, average or max/min from each HEX 5: average temperature of air outlet from rack, average or max/min from each HEX 6: heatflow sensor 7: alarm: Bit 0: Leakage Bit 1: IIC Failure Bit 5: Front and Rear Door opened 8: warning: Bit 0..2: Fan Tach 1..3 Bit 3,4: Temp. sensor HEX1 In,Out Bit 5,6: Temp. sensor HEX2 In,Out Bit 7,8: Temp. sensor HEX3 In,Out Bit 9: Air temp. sensor Bit 10..12: IIC failure, HEX1..3 Bit 13: Waterflow low Bit 14,15: Watertemp. In,Out Bit 16: Waterflow sensor fail. Bit 17: Magnetic valve fail. Bit 18: Leakdetector fail. Bit 19: Uneven heat load Bit 20: Condensation Pump Cycles > Max Bit 21: Condensation Pump Running Time > Max Bit 22..24: Fan Tach 4..6 Bit 25: Temperature Warning air inlet Bit 27: Dewpoint warning Bit 28: Humidity sensor failed Bit 29: Front door access sensor failed Bit 30: Rear door access sensor failed 9: rpm speed of Fan1 10: rpm speed of Fan2 11: rpm speed of Fan3 12: fanSpeed setpoint, calculated from average temperatures 13: temperature air inlet to rack, HEX 1 14: temperature air outlet from rack, HEX 1 15: temperature air inlet to rack, HEX 1 16: temperature air outlet from rack, HEX 1 17: temperature air inlet to rack, HEX 1 18: temperature air outlet from rack, HEX 1 19: water temperature In 20: water temperature Out 21: water Flow 22: water valve status: MCS:0: Valve opened, 1: valve closed; MCSS: valve setpoint (%) 23: status: Bit 0..Bit 2: fan module 1..3 available Bit 3: water module available 24: condensation pump number of seconds on counter (last operating time) 25: condensation pump on/off cycle counter 26: rpm speed of Fan4 27: rpm speed of Fan5 28: rpm speed of Fan6 29: status of transfer switch, 1=AC1, 2=AC2, 3=AC1 and AC2 30: water valve actual value (%) 31: dewpoint value 32: found fans: Bit 0..5: Fan 1.. Fan 6 33: isolation valve inlet position 34: isolation valve facility position 35: isolation valve infrastructure position 36: control valve facility position 37: control valve infrastructure position 38: temperature 4 air inlet to rack 39: temperature 5 air inlet to rack 40: temperature 6 air inlet to rack 41: supply side water pressure 42: return side water pressure 43: air differential pressure 1 44: air differential pressure 2 45: AC input 1 46: AC input 2 47: front door status 48: rear door status 49: leakage level middle 50: leakage overflow 1 51: leakage overflow 2 52: condensate status 53: dew point value 2 54: humidity value 1 55: humidity value 2 56: condensation/leakage pump running 57: temperature value 1 58: temperature value 2 59: Dewpoint value average 60: percent speed of Fan1 61: percent speed of Fan2 62: percent speed of Fan3 63: percent speed of Fan4 64: percent speed of Fan5 65: percent speed of Fan6
Context
- MIB
- CPQWCRM-MIB
- OID
.1.3.6.1.4.1.232.167.2.4.5.2.1.2- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- cpqWcrmWaterCoolUnitSensorEntry
- Table
- cpqWcrmWaterCoolUnitSensorTable
- Siblings
- 9
Syntax
Enumeration
Values & Constraints
Enumerated Values
4 | tempIn |
5 | tempOut |
6 | heatFlow |
7 | alarm |
8 | warning |
9 | rpmFan1 |
10 | rpmFan2 |
11 | rpmFan3 |
12 | fanSpeed |
13 | tempIn1 |
14 | tempOut1 |
15 | tempIn2 |
16 | tempOut2 |
17 | tempIn3 |
18 | tempOut3 |
19 | tempWaterIn |
20 | tempWaterOut |
21 | waterFlow |
22 | valve |
23 | status |
24 | condensateDuration |
25 | condensateCycles |
26 | rpmFan4 |
27 | rpmFan5 |
28 | rpmFan6 |
29 | transfSwitch |
30 | valveActValue |
31 | dewPointValue |
32 | foundFans |
33 | isolationValveInlet |
34 | isolationValveFacility |
35 | isolationValveInfrastructure |
36 | controlValveFacility |
37 | controlValveInfrastructure |
38 | tempIn4 |
39 | tempIn5 |
40 | tempIn6 |
41 | waterPressureSupply |
42 | waterPressureReturn |
43 | airDiffPressure1 |
44 | airDiffPressure2 |
45 | acInput1 |
46 | acInput2 |
47 | frontDoor |
48 | rearDoor |
49 | leakMidLevel |
50 | leakOverflow1 |
51 | leakOverflow2 |
52 | condensate |
53 | dewPointValue2 |
54 | humidityValue |
55 | humidityValue2 |
56 | pump |
57 | tempeValue1 |
58 | tempeValue2 |
59 | dewPointAverage |
60 | percentFan1 |
61 | percentFan2 |
62 | percentFan3 |
63 | percentFan4 |
64 | percentFan5 |
65 | percentFan6 |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| waterCoolUnitSensorIndex mandatory Index for the list of value entries. Its value ranges
between 1 and the value of cpqWcrmWaterCoolUnitNumberOfSensors. | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.1 |
| waterCoolUnitSensorScaledValue mandatory Scaled value of sensor | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.10 |
| waterCoolUnitSensorText mandatory Descriptional text for each sensor (entry in the table) | column | OctetString | .1.3.6.1.4.1.232.167.2.4.5.2.1.3 |
| waterCoolUnitSensorStatus mandatory Actual status of the sensor | column | Enumeration | .1.3.6.1.4.1.232.167.2.4.5.2.1.4 |
| waterCoolUnitSensorValue mandatory Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex)
If msg index = 1, 5 or 6
This value represents the actual Server Intake Temperature.
… | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.5 |
| waterCoolUnitSensorSetHigh mandatory Value for high setpoint of sensor | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.6 |
| waterCoolUnitSensorSetLow mandatory Value for low setpoint of sensor,
also used as alarm delay | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.7 |
| waterCoolUnitSensorSetWarn mandatory Value for warning setpoint of sensor,
also used as fan threshold | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.8 |
| waterCoolUnitSensorValueScale mandatory Scaling factor for scaled sensor value to get the unscaled value, e. g.
-100 -> waterCoolUnitSensorScaledValue has to be divided by 100
+100 -> waterCoolUnitSensorScaledValue has… | column | Integer32 | .1.3.6.1.4.1.232.167.2.4.5.2.1.9 |