waterCoolUnitOutputType

CPQWCRM-MIB · .1.3.6.1.4.1.232.167.2.4.6.2.1.2

Object

column mandatory Enumeration
Type of output which is connected to water cool unit to output[waterCoolUnitOutputIndex]
1: no output connected
2: output failure   
3: value overflow
4: water valve setpoint
5: water valve hysteresis
6: command for manual control
7: Flow Meter Model, 0=SIKA, 1=Chemline
8: minimum fan speed
9: min delta T, used for fan control
10: max delta T, used for fan control 
11: specific heat capacity
12: setpoint heatload warning
13: setpoint Water Flow Loss Emergency Door Opening
14: setpoint High Temperature Emergency Door Opening
15: setpoint Condensation Pump Cycles (Warning)
16: setpoint Condensation Pump Running Time (Warning)
17: command for door opening, 0=lock door, 1=unlock door
18: KP parameter for PID controller
19: KI parameter for PID controller
20: KD parameter for PID controller
21: sampling time PID controller
22: number of installed fans
23: offset for cold water temperature
24: offset for hot water temperature
25: valve control mode
26: isolation valve inlet, manual control
27: isolation valve facility, manual control
28: isolation valve infrastructure, manual control
29: control valve facility, manual setting
30: control valve infrastructure, manual setting
31: fan control mode
32: fan 1, manual setting
33: fan 2, manual setting
34: fan 3, manual setting
35: fan 4: manual setting
36: setpoint for air difference pressure (fan control), 
  this value is scaled with 1000 
  (e. g. 0.1 inch H2O are entered as 100)
37: KP parameter for Fan PID controller
38: KI parameter for Fan PID controller
39: KD parameter for Fan PID controller
40: sampling time Fan PID controller			  
41: dewpoint Offset for dewpoint average Value
42: max IT Air Temperature, Limit for dewpoint control
43: dewpoint control mode, 0 = off, 1 = On

Context

MIB
CPQWCRM-MIB
OID
.1.3.6.1.4.1.232.167.2.4.6.2.1.2
Type
column
Access
readonly
Status
mandatory
Parent
cpqWcrmWaterCoolUnitOutputEntry
Table
cpqWcrmWaterCoolUnitOutputTable
Siblings
8

Syntax

Enumeration

Values & Constraints

Enumerated Values
1notAvail
2failure
3overflow
4setpoint
5hysteresis
6command
7controlMode
8fanSpeedMin
9dTmin
10dTmax
11cpWatert
12setHeatload
13setEdoFlow
14setEdoHeat
15setCondCycles
16setCondRun
17doorControl
18pidContrKP
19pidContrKI
20pidContrKD
21pidSampleTime
22installedFans
23offsetCW
24offsetHW
25valveControlMode
26isolationValveInletManual
27isolationValveFacilityManual
28isolationValveInfrastructureManual
29controlValveFacilityManual
30controlValveInfrastructureManual
31fanControlMode
32fan1Manual
33fan2Manual
34fan3Manual
35fan4Manual
36setpointAirDifPressure
37pidContrKPFan
38pidContrKIFan
39pidContrKDFan
40pidSampleTimeFan
41dewpointOffset
42maxItAirTemperature
43dewpointControlMode

Related Objects