netBotz-prd-bot-low-trap | .1.3.6.1.4.1.5528.30.10.0.1 | NetBotz Low Trap. This trap indicates that a lower
limit has been exceeded. |
netBotz-prd-bot-high-trap | .1.3.6.1.4.1.5528.30.10.0.2 | NetBotz High Trap. This trap indicates that an upper
limit has been exceeded. |
netBotz-prd-bot-trap-clear | .1.3.6.1.4.1.5528.30.10.0.3 | NetBotz Cleared Trap. The trap has been cleared because
the value has returned to acceptable limits. |
netBotz-prd-bot-offline-trap | .1.3.6.1.4.1.5528.30.10.0.4 | NetBotz Device Offline Trap. This trap indicates that a device or function
has been determined to be offline. |
netBotz-prd-bot-online-trap | .1.3.6.1.4.1.5528.30.10.0.5 | NetBotz Device Online Trap. This trap indicates that a device or function
has been determined to be online. |
netBotz-prd-bot-temperature-low-trap | .1.3.6.1.4.1.5528.30.100.1.0.1 | NetBotz Temperature Low Trap. This trap indicates that the lower
limit for temperature has been exceeded. |
netBotz-prd-bot-temperature-high-trap | .1.3.6.1.4.1.5528.30.100.1.0.2 | NetBotz Temperature High Trap. This trap indicates that the upper
limit for temperature has been exceeded. |
netBotz-prd-bot-temperature-trap-clear | .1.3.6.1.4.1.5528.30.100.1.0.3 | NetBotz Temperature Cleared Trap. The trap has been cleared because
the temperature value has returned to acceptable limits. |
netBotz-prd-bot-amp-total-low-trap | .1.3.6.1.4.1.5528.30.100.10.0.1 | NetBotz Total Amps Low Trap. This trap indicates that the lower
limit for the total amperage has been exceeded. |
netBotz-prd-bot-amp-total-high-trap | .1.3.6.1.4.1.5528.30.100.10.0.2 | NetBotz Total Amps High Trap. This trap indicates that the upper
limit for the total amperage has been exceeded. |
netBotz-prd-bot-amp-total-trap-clear | .1.3.6.1.4.1.5528.30.100.10.0.3 | NetBotz Total Amps Cleared Trap. The trap has been cleared because
the total amperage value has returned to acceptable limits. |
netBotz-prd-bot-ext-temp1-low-trap | .1.3.6.1.4.1.5528.30.100.11.0.1 | NetBotz External Temperature 1 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 1 has been exceeded. |
netBotz-prd-bot-ext-temp1-high-trap | .1.3.6.1.4.1.5528.30.100.11.0.2 | NetBotz External Temperature 1 High Trap. This trap indicates that the upper
limit for external temperature probe on port 1 has been exceeded. |
netBotz-prd-bot-ext-temp1-trap-clear | .1.3.6.1.4.1.5528.30.100.11.0.3 | NetBotz External Temperature 1 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 1 has returned to acceptable limits. |
netBotz-prd-bot-ext-temp1-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.11.0.6 | NetBotz External Temperature 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-temp1-sensor-replugged | .1.3.6.1.4.1.5528.30.100.11.0.7 | NetBotz External Temperature 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-temp2-low-trap | .1.3.6.1.4.1.5528.30.100.12.0.1 | NetBotz External Temperature 2 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 2 has been exceeded. |
netBotz-prd-bot-ext-temp2-high-trap | .1.3.6.1.4.1.5528.30.100.12.0.2 | NetBotz External Temperature 2 High Trap. This trap indicates that the upper
limit for external temperature probe on port 2 has been exceeded. |
netBotz-prd-bot-ext-temp2-trap-clear | .1.3.6.1.4.1.5528.30.100.12.0.3 | NetBotz External Temperature 2 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 2 has returned to acceptable limits. |
netBotz-prd-bot-ext-temp2-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.12.0.6 | NetBotz External Temperature 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-temp2-sensor-replugged | .1.3.6.1.4.1.5528.30.100.12.0.7 | NetBotz External Temperature 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-temp3-low-trap | .1.3.6.1.4.1.5528.30.100.13.0.1 | NetBotz External Temperature 3 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 3 has been exceeded. |
netBotz-prd-bot-ext-temp3-high-trap | .1.3.6.1.4.1.5528.30.100.13.0.2 | NetBotz External Temperature 3 High Trap. This trap indicates that the upper
limit for external temperature probe on port 3 has been exceeded. |
netBotz-prd-bot-ext-temp3-trap-clear | .1.3.6.1.4.1.5528.30.100.13.0.3 | NetBotz External Temperature 3 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 3 has returned to acceptable limits. |
netBotz-prd-bot-ext-temp3-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.13.0.6 | NetBotz External Temperature 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-temp3-sensor-replugged | .1.3.6.1.4.1.5528.30.100.13.0.7 | NetBotz External Temperature 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-temp4-low-trap | .1.3.6.1.4.1.5528.30.100.14.0.1 | NetBotz External Temperature 4 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 4 has been exceeded. |
netBotz-prd-bot-ext-temp4-high-trap | .1.3.6.1.4.1.5528.30.100.14.0.2 | NetBotz External Temperature 4 High Trap. This trap indicates that the upper
limit for external temperature probe on port 4 has been exceeded. |
netBotz-prd-bot-ext-temp4-trap-clear | .1.3.6.1.4.1.5528.30.100.14.0.3 | NetBotz External Temperature 4 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 4 has returned to acceptable limits. |
netBotz-prd-bot-ext-temp4-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.14.0.6 | NetBotz External Temperature 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-temp4-sensor-replugged | .1.3.6.1.4.1.5528.30.100.14.0.7 | NetBotz External Temperature 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-dry1-triggered-trap | .1.3.6.1.4.1.5528.30.100.15.0.2 | NetBotz External Dry Contact 1 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext1 matches the alarm value. |
netBotz-prd-bot-ext-dry1-trap-clear | .1.3.6.1.4.1.5528.30.100.15.0.3 | NetBotz External Dry Contact 1 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext1 no longer matches the alarm value. |
netBotz-prd-bot-ext-dry2-triggered-trap | .1.3.6.1.4.1.5528.30.100.16.0.2 | NetBotz External Dry Contact 2 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext2 matches the alarm value. |
netBotz-prd-bot-ext-dry2-trap-clear | .1.3.6.1.4.1.5528.30.100.16.0.3 | NetBotz External Dry Contact 2 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext2 no longer matches the alarm value. |
netBotz-prd-bot-ext-dry3-triggered-trap | .1.3.6.1.4.1.5528.30.100.17.0.2 | NetBotz External Dry Contact 3 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext3 matches the alarm value. |
netBotz-prd-bot-ext-dry3-trap-clear | .1.3.6.1.4.1.5528.30.100.17.0.3 | NetBotz External Dry Contact 3 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext3 no longer matches the alarm value. |
netBotz-prd-bot-ext-dry4-triggered-trap | .1.3.6.1.4.1.5528.30.100.18.0.2 | NetBotz External Dry Contact 4 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext4 matches the alarm value. |
netBotz-prd-bot-ext-dry4-trap-clear | .1.3.6.1.4.1.5528.30.100.18.0.3 | NetBotz External Dry Contact 4 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext4 no longer matches the alarm value. |
netBotz-prd-bot-amp5-low-trap | .1.3.6.1.4.1.5528.30.100.19.0.1 | NetBotz Amp 5 Low Trap. This trap indicates that the lower
limit for the fifth amp detect has been exceeded. |
netBotz-prd-bot-amp5-high-trap | .1.3.6.1.4.1.5528.30.100.19.0.2 | NetBotz Amp 5 High Trap. This trap indicates that the upper
limit for the fifth amp detect has been exceeded. |
netBotz-prd-bot-amp5-trap-clear | .1.3.6.1.4.1.5528.30.100.19.0.3 | NetBotz Amp 5 Cleared Trap. The trap has been cleared because
the fifth amp detect value has returned to acceptable limits. |
netBotz-prd-bot-amp5-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.19.0.6 | NetBotz Amp 5 Sensor Unplugged Trap. The sensor for the fifth AmpDetect is unplugged or malfunctioning. |
netBotz-prd-bot-amp5-sensor-replugged | .1.3.6.1.4.1.5528.30.100.19.0.7 | NetBotz Amp 5 Sensor Replugged Trap. The sensor for the fifth AmpDetect was unplugged, but has been reconnected. |
netBotz-prd-bot-humidity-low-trap | .1.3.6.1.4.1.5528.30.100.2.0.1 | NetBotz Humidity Low Trap. This trap indicates that the lower
limit for humidity has been exceeded. |
netBotz-prd-bot-humidity-high-trap | .1.3.6.1.4.1.5528.30.100.2.0.2 | NetBotz Humidity High Trap. This trap indicates that the upper
limit for humidity has been exceeded. |
netBotz-prd-bot-humidity-trap-clear | .1.3.6.1.4.1.5528.30.100.2.0.3 | NetBotz Humidity Cleared Trap. The trap has been cleared because
the humidity value has returned to acceptable limits. |
netBotz-prd-bot-amp6-low-trap | .1.3.6.1.4.1.5528.30.100.20.0.1 | NetBotz Amp 6 Low Trap. This trap indicates that the lower
limit for the sixth amp detect has been exceeded. |
netBotz-prd-bot-amp6-high-trap | .1.3.6.1.4.1.5528.30.100.20.0.2 | NetBotz Amp 6 High Trap. This trap indicates that the upper
limit for the sixth amp detect has been exceeded. |
netBotz-prd-bot-amp6-trap-clear | .1.3.6.1.4.1.5528.30.100.20.0.3 | NetBotz Amp 6 Cleared Trap. The trap has been cleared because
the sixth amp detect value has returned to acceptable limits. |
netBotz-prd-bot-amp6-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.20.0.6 | NetBotz Amp 6 Sensor Unplugged Trap. The sensor for the sixth AmpDetect is unplugged or malfunctioning. |
netBotz-prd-bot-amp6-sensor-replugged | .1.3.6.1.4.1.5528.30.100.20.0.7 | NetBotz Amp 6 Sensor Replugged Trap. The sensor for the sixth AmpDetect was unplugged, but has been reconnected. |
netBotz-prd-bot-amp7-low-trap | .1.3.6.1.4.1.5528.30.100.21.0.1 | NetBotz Amp 7 Low Trap. This trap indicates that the lower
limit for the seventh amp detect has been exceeded. |
netBotz-prd-bot-amp7-high-trap | .1.3.6.1.4.1.5528.30.100.21.0.2 | NetBotz Amp 7 High Trap. This trap indicates that the upper
limit for the seventh amp detect has been exceeded. |
netBotz-prd-bot-amp7-trap-clear | .1.3.6.1.4.1.5528.30.100.21.0.3 | NetBotz Amp 7 Cleared Trap. The trap has been cleared because
the seventh amp detect value has returned to acceptable limits. |
netBotz-prd-bot-amp7-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.21.0.6 | NetBotz Amp 7 Sensor Unplugged Trap. The sensor for the seventh AmpDetect is unplugged or malfunctioning. |
netBotz-prd-bot-amp7-sensor-replugged | .1.3.6.1.4.1.5528.30.100.21.0.7 | NetBotz Amp 7 Sensor Replugged Trap. The sensor for the seventh AmpDetect was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-temp5-low-trap | .1.3.6.1.4.1.5528.30.100.22.0.1 | NetBotz External Temperature 5 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 5 has been exceeded. |
netBotz-prd-bot-ext-temp5-high-trap | .1.3.6.1.4.1.5528.30.100.22.0.2 | NetBotz External Temperature 5 High Trap. This trap indicates that the upper
limit for external temperature probe on port 5 has been exceeded. |
netBotz-prd-bot-ext-temp5-trap-clear | .1.3.6.1.4.1.5528.30.100.22.0.3 | NetBotz External Temperature 5 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 5 has returned to acceptable limits. |
netBotz-prd-bot-ext-temp5-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.22.0.6 | NetBotz External Temperature 5 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-temp5-sensor-replugged | .1.3.6.1.4.1.5528.30.100.22.0.7 | NetBotz External Temperature 5 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-temp6-low-trap | .1.3.6.1.4.1.5528.30.100.23.0.1 | NetBotz External Temperature 6 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 6 has been exceeded. |
netBotz-prd-bot-ext-temp6-high-trap | .1.3.6.1.4.1.5528.30.100.23.0.2 | NetBotz External Temperature 6 High Trap. This trap indicates that the upper
limit for external temperature probe on port 6 has been exceeded. |
netBotz-prd-bot-ext-temp6-trap-clear | .1.3.6.1.4.1.5528.30.100.23.0.3 | NetBotz External Temperature 6 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 6 has returned to acceptable limits. |
netBotz-prd-bot-ext-temp6-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.23.0.6 | NetBotz External Temperature 6 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-temp6-sensor-replugged | .1.3.6.1.4.1.5528.30.100.23.0.7 | NetBotz External Temperature 6 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-temp7-low-trap | .1.3.6.1.4.1.5528.30.100.24.0.1 | NetBotz External Temperature 7 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 7 has been exceeded. |
netBotz-prd-bot-ext-temp7-high-trap | .1.3.6.1.4.1.5528.30.100.24.0.2 | NetBotz External Temperature 7 High Trap. This trap indicates that the upper
limit for external temperature probe on port 7 has been exceeded. |
netBotz-prd-bot-ext-temp7-trap-clear | .1.3.6.1.4.1.5528.30.100.24.0.3 | NetBotz External Temperature 7 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 7 has returned to acceptable limits. |
netBotz-prd-bot-ext-temp7-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.24.0.6 | NetBotz External Temperature 7 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-temp7-sensor-replugged | .1.3.6.1.4.1.5528.30.100.24.0.7 | NetBotz External Temperature 7 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-dry5-triggered-trap | .1.3.6.1.4.1.5528.30.100.25.0.2 | NetBotz External Dry Contact 5 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext5 matches the alarm value. |
netBotz-prd-bot-ext-dry5-trap-clear | .1.3.6.1.4.1.5528.30.100.25.0.3 | NetBotz External Dry Contact 5 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext5 no longer matches the alarm value. |
netBotz-prd-bot-ext-dry6-triggered-trap | .1.3.6.1.4.1.5528.30.100.26.0.2 | NetBotz External Dry Contact 6 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext6 matches the alarm value. |
netBotz-prd-bot-ext-dry6-trap-clear | .1.3.6.1.4.1.5528.30.100.26.0.3 | NetBotz External Dry Contact 6 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext6 no longer matches the alarm value. |
netBotz-prd-bot-ext-dry7-triggered-trap | .1.3.6.1.4.1.5528.30.100.27.0.2 | NetBotz External Dry Contact 7 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext7 matches the alarm value. |
netBotz-prd-bot-ext-dry7-trap-clear | .1.3.6.1.4.1.5528.30.100.27.0.3 | NetBotz External Dry Contact 7 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext7 no longer matches the alarm value. |
netBotz-prd-bot-camera-motion-trap-tripped | .1.3.6.1.4.1.5528.30.100.28.0.2 | NetBotz Camera Motion Sensor Tripped Trap. This trap indicates that the camera motion sensor
has been triggered (motion has been detected). |
netBotz-prd-bot-camera-motion-trap-clear | .1.3.6.1.4.1.5528.30.100.28.0.3 | NetBotz Camera Motion Cleared Trap. The trap has been cleared because
the camera motion sensor has returned to normal (no longer is detecting motion). |
netBotz-prd-bot-ext-humi1-low-trap | .1.3.6.1.4.1.5528.30.100.29.0.1 | NetBotz External Humidity 1 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 1 has been exceeded. |
netBotz-prd-bot-ext-humi1-high-trap | .1.3.6.1.4.1.5528.30.100.29.0.2 | NetBotz External Humidity 1 High Trap. This trap indicates that the upper
limit for external humidity probe on port 1 has been exceeded. |
netBotz-prd-bot-ext-humi1-trap-clear | .1.3.6.1.4.1.5528.30.100.29.0.3 | NetBotz External Humidity 1 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 1 has returned to acceptable limits. |
netBotz-prd-bot-ext-humi1-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.29.0.6 | NetBotz External Humidity 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-humi1-sensor-replugged | .1.3.6.1.4.1.5528.30.100.29.0.7 | NetBotz External Humidity 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-airflow-low-trap | .1.3.6.1.4.1.5528.30.100.3.0.1 | NetBotz Airflow Low Trap. This trap indicates that the lower
limit for airflow has been exceeded. |
netBotz-prd-bot-airflow-trap-clear | .1.3.6.1.4.1.5528.30.100.3.0.3 | NetBotz Airflow Cleared Trap. The trap has been cleared because
the airflow value has returned to acceptable limits. |
netBotz-prd-bot-ext-humi2-low-trap | .1.3.6.1.4.1.5528.30.100.30.0.1 | NetBotz External Humidity 2 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 2 has been exceeded. |
netBotz-prd-bot-ext-humi2-high-trap | .1.3.6.1.4.1.5528.30.100.30.0.2 | NetBotz External Humidity 2 High Trap. This trap indicates that the upper
limit for external humidity probe on port 2 has been exceeded. |
netBotz-prd-bot-ext-humi2-trap-clear | .1.3.6.1.4.1.5528.30.100.30.0.3 | NetBotz External Humidity 2 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 2 has returned to acceptable limits. |
netBotz-prd-bot-ext-humi2-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.30.0.6 | NetBotz External Humidity 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-humi2-sensor-replugged | .1.3.6.1.4.1.5528.30.100.30.0.7 | NetBotz External Humidity 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-humi3-low-trap | .1.3.6.1.4.1.5528.30.100.31.0.1 | NetBotz External Humidity 3 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 3 has been exceeded. |
netBotz-prd-bot-ext-humi3-high-trap | .1.3.6.1.4.1.5528.30.100.31.0.2 | NetBotz External Humidity 3 High Trap. This trap indicates that the upper
limit for external humidity probe on port 3 has been exceeded. |
netBotz-prd-bot-ext-humi3-trap-clear | .1.3.6.1.4.1.5528.30.100.31.0.3 | NetBotz External Humidity 3 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 3 has returned to acceptable limits. |
netBotz-prd-bot-ext-humi3-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.31.0.6 | NetBotz External Humidity 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-humi3-sensor-replugged | .1.3.6.1.4.1.5528.30.100.31.0.7 | NetBotz External Humidity 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-humi4-low-trap | .1.3.6.1.4.1.5528.30.100.32.0.1 | NetBotz External Humidity 4 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 4 has been exceeded. |
netBotz-prd-bot-ext-humi4-high-trap | .1.3.6.1.4.1.5528.30.100.32.0.2 | NetBotz External Humidity 4 High Trap. This trap indicates that the upper
limit for external humidity probe on port 4 has been exceeded. |
netBotz-prd-bot-ext-humi4-trap-clear | .1.3.6.1.4.1.5528.30.100.32.0.3 | NetBotz External Humidity 4 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 4 has returned to acceptable limits. |
netBotz-prd-bot-ext-humi4-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.32.0.6 | NetBotz External Humidity 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-humi4-sensor-replugged | .1.3.6.1.4.1.5528.30.100.32.0.7 | NetBotz External Humidity 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-humi5-low-trap | .1.3.6.1.4.1.5528.30.100.33.0.1 | NetBotz External Humidity 5 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 5 has been exceeded. |
netBotz-prd-bot-ext-humi5-high-trap | .1.3.6.1.4.1.5528.30.100.33.0.2 | NetBotz External Humidity 5 High Trap. This trap indicates that the upper
limit for external humidity probe on port 5 has been exceeded. |
netBotz-prd-bot-ext-humi5-trap-clear | .1.3.6.1.4.1.5528.30.100.33.0.3 | NetBotz External Humidity 5 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 5 has returned to acceptable limits. |
netBotz-prd-bot-ext-humi5-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.33.0.6 | NetBotz External Humidity 5 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-humi5-sensor-replugged | .1.3.6.1.4.1.5528.30.100.33.0.7 | NetBotz External Humidity 5 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-humi6-low-trap | .1.3.6.1.4.1.5528.30.100.34.0.1 | NetBotz External Humidity 6 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 6 has been exceeded. |
netBotz-prd-bot-ext-humi6-high-trap | .1.3.6.1.4.1.5528.30.100.34.0.2 | NetBotz External Humidity 6 High Trap. This trap indicates that the upper
limit for external humidity probe on port 6 has been exceeded. |
netBotz-prd-bot-ext-humi6-trap-clear | .1.3.6.1.4.1.5528.30.100.34.0.3 | NetBotz External Humidity 6 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 6 has returned to acceptable limits. |
netBotz-prd-bot-ext-humi6-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.34.0.6 | NetBotz External Humidity 6 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-humi6-sensor-replugged | .1.3.6.1.4.1.5528.30.100.34.0.7 | NetBotz External Humidity 6 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-ext-humi7-low-trap | .1.3.6.1.4.1.5528.30.100.35.0.1 | NetBotz External Humidity 7 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 7 has been exceeded. |
netBotz-prd-bot-ext-humi7-high-trap | .1.3.6.1.4.1.5528.30.100.35.0.2 | NetBotz External Humidity 7 High Trap. This trap indicates that the upper
limit for external humidity probe on port 7 has been exceeded. |
netBotz-prd-bot-ext-humi7-trap-clear | .1.3.6.1.4.1.5528.30.100.35.0.3 | NetBotz External Humidity 7 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 7 has returned to acceptable limits. |
netBotz-prd-bot-ext-humi7-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.35.0.6 | NetBotz External Humidity 7 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. |
netBotz-prd-bot-ext-humi7-sensor-replugged | .1.3.6.1.4.1.5528.30.100.35.0.7 | NetBotz External Humidity 7 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. |
netBotz-prd-bot-audio-high-trap | .1.3.6.1.4.1.5528.30.100.4.0.2 | NetBotz Audio High Trap. This trap indicates that the upper
limit for audio has been exceeded. |
netBotz-prd-bot-audio-trap-clear | .1.3.6.1.4.1.5528.30.100.4.0.3 | NetBotz Audio Cleared Trap. The trap has been cleared because
the audio value has returned to acceptable limits. |
netBotz-prd-bot-door-trap-tripped | .1.3.6.1.4.1.5528.30.100.5.0.2 | NetBotz Door Sensor Tripped Trap. This trap indicates that the door sensor
has been triggered (i.e. opened, if the thresdhold has been set to trip on open, closed if otherwise). |
netBotz-prd-bot-door-trap-clear | .1.3.6.1.4.1.5528.30.100.5.0.3 | NetBotz Door Cleared Trap. The trap has been cleared because
the door sensor has returned to normal (i.e. been closed, if the threshold has been set to trip on open). |
netBotz-prd-bot-amp1-low-trap | .1.3.6.1.4.1.5528.30.100.6.0.1 | NetBotz Amp1 Low Trap. This trap indicates that the lower
limit for the first amp detect has been exceeded. |
netBotz-prd-bot-amp1-high-trap | .1.3.6.1.4.1.5528.30.100.6.0.2 | NetBotz Amp1 High Trap. This trap indicates that the upper
limit for the first amp detect has been exceeded. |
netBotz-prd-bot-amp1-trap-clear | .1.3.6.1.4.1.5528.30.100.6.0.3 | NetBotz Amp1 Cleared Trap. The trap has been cleared because
the first amp detect value has returned to acceptable limits. |
netBotz-prd-bot-amp1-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.6.0.6 | NetBotz Amp 1 Sensor Unplugged Trap. The sensor for the first AmpDetect is unplugged or malfunctioning. |
netBotz-prd-bot-amp1-sensor-replugged | .1.3.6.1.4.1.5528.30.100.6.0.7 | NetBotz Amp 1 Sensor Replugged Trap. The sensor for the first AmpDetect was unplugged, but has been reconnected. |
netBotz-prd-bot-amp2-low-trap | .1.3.6.1.4.1.5528.30.100.7.0.1 | NetBotz Amp2 Low Trap. This trap indicates that the lower
limit for the second amp detect has been exceeded. |
netBotz-prd-bot-amp2-high-trap | .1.3.6.1.4.1.5528.30.100.7.0.2 | NetBotz Amp2 High Trap. This trap indicates that the upper
limit for the second amp detect has been exceeded. |
netBotz-prd-bot-amp2-trap-clear | .1.3.6.1.4.1.5528.30.100.7.0.3 | NetBotz Amp2 Cleared Trap. The trap has been cleared because
the second amp detect value has returned to acceptable limits. |
netBotz-prd-bot-amp2-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.7.0.6 | NetBotz Amp 2 Sensor Unplugged Trap. The sensor for the second AmpDetect is unplugged or malfunctioning. |
netBotz-prd-bot-amp2-sensor-replugged | .1.3.6.1.4.1.5528.30.100.7.0.7 | NetBotz Amp 2 Sensor Replugged Trap. The sensor for the second AmpDetect was unplugged, but has been reconnected. |
netBotz-prd-bot-amp3-low-trap | .1.3.6.1.4.1.5528.30.100.8.0.1 | NetBotz Amp3 Low Trap. This trap indicates that the lower
limit for the third amp detect has been exceeded. |
netBotz-prd-bot-amp3-high-trap | .1.3.6.1.4.1.5528.30.100.8.0.2 | NetBotz Amp3 High Trap. This trap indicates that the upper
limit for the third amp detect has been exceeded. |
netBotz-prd-bot-amp3-trap-clear | .1.3.6.1.4.1.5528.30.100.8.0.3 | NetBotz Amp3 Cleared Trap. The trap has been cleared because
the third amp detect value has returned to acceptable limits. |
netBotz-prd-bot-amp3-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.8.0.6 | NetBotz Amp 3 Sensor Unplugged Trap. The sensor for the third AmpDetect is unplugged or malfunctioning. |
netBotz-prd-bot-amp3-sensor-replugged | .1.3.6.1.4.1.5528.30.100.8.0.7 | NetBotz Amp 3 Sensor Replugged Trap. The sensor for the third AmpDetect was unplugged, but has been reconnected. |
netBotz-prd-bot-amp4-low-trap | .1.3.6.1.4.1.5528.30.100.9.0.1 | NetBotz Amp4 Low Trap. This trap indicates that the lower
limit for the fourth amp detect has been exceeded. |
netBotz-prd-bot-amp4-high-trap | .1.3.6.1.4.1.5528.30.100.9.0.2 | NetBotz Amp4 High Trap. This trap indicates that the upper
limit for the fourth amp detect has been exceeded. |
netBotz-prd-bot-amp4-trap-clear | .1.3.6.1.4.1.5528.30.100.9.0.3 | NetBotz Amp4 Cleared Trap. The trap has been cleared because
the fourth amp detect value has returned to acceptable limits. |
netBotz-prd-bot-amp4-sensor-unplugged | .1.3.6.1.4.1.5528.30.100.9.0.6 | NetBotz Amp 4 Sensor Unplugged Trap. The sensor for the fourth AmpDetect is unplugged or malfunctioning. |
netBotz-prd-bot-amp4-sensor-replugged | .1.3.6.1.4.1.5528.30.100.9.0.7 | NetBotz Amp 4 Sensor Replugged Trap. The sensor for the fourth AmpDetect was unplugged, but has been reconnected. |
netBotz-prd-crl-ping-offline-trap | .1.3.6.1.4.1.5528.30.20.5528.1.3.0.4 | NetBotz Ping Trap. This trap indicates that replies to a set of pings were not received from a monitored IP address. |
netBotz-prd-crl-ping-online-trap | .1.3.6.1.4.1.5528.30.20.5528.1.3.0.5 | NetBotz Ping Trap. This trap indicates that replies to a set of pings were received from a monitored IP address after
a period when no replies had been received. |
netBotz-prd-crl-uptime-online-trap | .1.3.6.1.4.1.5528.30.20.5528.1.8.0.5 | NetBotz Uptime Trap. This trap indicates that a device restart has been detected due to the uptime of the device
being reported as less than the previously reported reading. |
netBotz-prd-crl-snmp-offline-trap | .1.3.6.1.4.1.5528.30.20.5528.1.9.0.4 | NetBotz SNMP Offline Trap. This trap indicates that an SNMP request was
not possible on an IP address. |
netBotz-prd-crl-snmp-online-trap | .1.3.6.1.4.1.5528.30.20.5528.1.9.0.5 | NetBotz SNMP Online Trap. This trap indicates that an SNMP request succeeded
on an IP address where it had previously failed. |
netBotz-prd-crl-opstatus-mismatch-trap | .1.3.6.1.4.1.5528.30.20.5528.2.6.0.1 | NetBotz Interface Status Mismatch Trap. This trap indicates that the operational
status of a device interface does not match the administrative status. |
netBotz-prd-crl-opstatus-match-trap | .1.3.6.1.4.1.5528.30.20.5528.2.6.0.2 | NetBotz Interface Status Match Trap. This trap indicates that the operational
status of a device interface now matches the administrative status. This trap indicates
a transition from a state in which the administrative and operational status did not match. |
netBotz-prd-crl-opstatus-offline-trap | .1.3.6.1.4.1.5528.30.20.5528.2.6.0.4 | NetBotz Interface Offline Trap. This trap indicates that an interface on a device
did not respond to an SNMP query on the ifAdminStatus or ifOperStatus objects. |
netBotz-device-crawlers-value-low-alert-trap | .1.3.6.1.4.1.5528.60.5528.2.0.1 | NetBotz Device Crawlers Value Low Trap. This trap indicates that the lower limit on a monitored value has been exceeded. |
netBotz-device-crawlers-value-high-alert-trap | .1.3.6.1.4.1.5528.60.5528.2.0.2 | NetBotz Device Crawlers Value High Trap. This trap indicates that the upper limit on a monitored value has been exceeded. |
netBotz-device-crawlers-clear-alert-trap | .1.3.6.1.4.1.5528.60.5528.2.0.3 | NetBotz Device Crawlers Clear Trap. This trap indicates that the previous alert condition has been cleared. |
netBotz-device-crawlers-offline-alert-trap | .1.3.6.1.4.1.5528.60.5528.2.0.4 | NetBotz Device Crawlers Offline Trap. This trap indicates that a monitored target could not be contacted. |
netBotz-device-crawlers-online-alert-trap | .1.3.6.1.4.1.5528.60.5528.2.0.5 | NetBotz Device Crawlers Online Trap. This trap indicates that a monitored target that previously could not be contacted has now been contacted successfully. |
netBotz-device-crawlers-ifopstatus-alert-trap | .1.3.6.1.4.1.5528.60.5528.2.0.8 | NetBotz Device Crawlers Interface Operational Status Trap. This trap indicates that one or more of a monitored target's network interfaces operational status is not equal to the desired status. |
netBotz-branch-checker-target-error-trap | .1.3.6.1.4.1.5528.60.5528.3.0.12 | NetBotz Branch Target Error Trap. This trap indicates that a monitored target could be contacted, but not withing the timeout period specified. |
netBotz-branch-checker-clear-alert-trap | .1.3.6.1.4.1.5528.60.5528.3.0.3 | NetBotz Branch Checker Clear Trap. This trap indicates that the previous alert condition has been cleared. |
netBotz-branch-checker-offline-alert-trap | .1.3.6.1.4.1.5528.60.5528.3.0.4 | NetBotz Branch Checker Offline Trap. This trap indicates that a monitored target could not be contacted. |
netBotz-branch-checker-online-alert-trap | .1.3.6.1.4.1.5528.60.5528.3.0.5 | NetBotz Branch Checker Online Trap. This trap indicates that a monitored target that previously could not be contacted has now been contacted successfully. |