.1.3.6.1.4.1.5528.31
·
1 row entry
·
36 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk expPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NETBOTZ-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NETBOTZ-MIB::expPortTable'
A list of expansion port entries.
An expansion port entry for a single port
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
expPort-module-idmandatory
The module ID of the sensor module installed. Blank string indicates that no module is installed.
|
RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.5528.31.1.1 |
|
expPort-module-typemandatory
The type of sensor module installed. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
|
RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.5528.31.1.2 |
|
expPort-labelmandatory
The label for the expansion port. Ports default to the label 'Extn', for port n.
|
RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.5528.31.1.3 |
|
expPort-ampsmandatory
The reading of the amperage probe, in milliamps.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.20 |
|
expPort-total-amp-secondsmandatory
The accumulated total of amp-seconds on the AmpDetect.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.21 |
|
expPort-total-amp-seconds-since-timemandatory
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the curre… |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.22 |
|
expPort-amps-enabledmandatory
Amperage probe alarm enabled(1) or disabled(0).
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.23 |
|
expPort-amps-minmandatory
The amperage probe minimum, from 0 to 30000 milliamps.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.24 |
|
expPort-amps-maxmandatory
The amperage probe maximum, from 0 to 30000 milliamps.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.25 |
|
expPort-amps-uV-per-10mAmandatory
The scaling factor used for the amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.26 |
|
expPort-amps-max-rangemandatory
The maximum RMS milliamps measureable by the AmpDetect.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.27 |
|
expPort-ext-tempmandatory
The reading of the external temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.40 |
|
expPort-ext-temp-enabledmandatory
External temperature probe alarm enabled(1) or disabled(0).
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.41 |
|
expPort-ext-temp-minmandatory
The external temperature probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.42 |
|
expPort-ext-temp-maxmandatory
The external temperature probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.43 |
|
expPort-ext-temp-uV-per-degreeCmandatory
The scaling factor used for the external temperature probe to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.44 |
|
expPort-ext-temp-uV-at-0-degreeCmandatory
The offset used for the external temperature probe of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.45 |
|
expPort-ext-temp-min-rangemandatory
The minimum temperature measureable by the temperature sensor, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.46 |
|
expPort-ext-temp-max-rangemandatory
The maximum temperature measureable by the temperature sensor, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.47 |
|
expPort-ext-drymandatory
The current value of the external dry contact sensor: 0=Open, 1=Closed, -1=N/A
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.60 |
|
expPort-ext-dry-alarm-valuemandatory
The value to generate alarms on for the external dry contact sensor: 0=Open, 1=Closed
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.61 |
|
expPort-ext-dry-enabledmandatory
External dry contact sensor alarm enabled(1) or disabled(0).
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.62 |
|
expPort-ext-dry-labelmandatory
The sensor name/label for the dry contact sensor
|
RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.5528.31.1.63 |
|
expPort-ext-dry-open-labelmandatory
The sensor name/label for the open(0) state for the dry contact sensor
|
RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.5528.31.1.64 |
|
expPort-ext-dry-closed-labelmandatory
The sensor name/label for the closed(0) state for the dry contact sensor
|
RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.5528.31.1.65 |
|
expPort-ext-dry-open-to-close-millismandatory
The minimum number of milliseconds that the dry contact sensor
must read closed before the state is changed from open to closed. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.66 |
|
expPort-ext-dry-close-to-open-millismandatory
The minimum number of milliseconds that the dry contact sensor
must read openbefore the state is changed from closed to open. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.67 |
|
expPort-ext-dry-responsemandatory
The type of alert response for the dry contact sensor: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera. |
RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.5528.31.1.68 |
|
expPort-ext-humimandatory
The reading of the external humidity probe, in percent.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.80 |
|
expPort-ext-humi-enabledmandatory
External humidity probe alarm enabled(1) or disabled(0).
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.81 |
|
expPort-ext-humi-minmandatory
The external humidity probe minimum, in percent.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.82 |
|
expPort-ext-humi-maxmandatory
The external humidity probe maximum, in percent.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.83 |
|
expPort-ext-humi-uV-per-percentmandatory
The scaling factor used for the external humidity probe to convert microvolts measured from the
humidity sensor into percent. Needs to be set based on the type of humidity sensor module installed. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.84 |
|
expPort-ext-humi-uV-at-0-percentmandatory
The offset used for the external humidity probe of microvolts measured from the
humidity sensor at zero percent. Needs to be set based on the type of humidity sensor module installed. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.85 |
|
expPort-ext-humi-min-rangemandatory
The minimum humidity measureable by the humidity sensor, in percent.
Needs to be set based on the type of humidity sensor module installed. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.86 |
|
expPort-ext-humi-max-rangemandatory
The maximum humidity measureable by the humidity sensor, in percent.
Needs to be set based on the type of humidity sensor module installed. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.87 |