NETBOTZ-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
1
Rows
1
Columns
36
.1.3.6.1.4.1.5528.31
·
1 row entry
·
36 columns
A list of expansion port entries.
An expansion port entry for a single port
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
expPort-module-id
mandatory
The module ID of the sensor module installed. Blank string indicates that no module is installed.
|
RFC1213-MIBDisplayStringr/w Textual Convention: RFC1213-MIBDisplayString OctetString |
.1.3.6.1.4.1.5528.31.1.1 |
|
expPort-module-type
mandatory
The type of sensor module installed. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
|
RFC1213-MIBDisplayStringr/w Textual Convention: RFC1213-MIBDisplayString OctetString |
.1.3.6.1.4.1.5528.31.1.2 |
|
expPort-label
mandatory
The label for the expansion port. Ports default to the label 'Extn', for port n.
|
RFC1213-MIBDisplayStringr/w Textual Convention: RFC1213-MIBDisplayString OctetString |
.1.3.6.1.4.1.5528.31.1.3 |
|
expPort-amps
mandatory
The reading of the amperage probe, in milliamps.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.20 |
|
expPort-total-amp-seconds
mandatory
The accumulated total of amp-seconds on the AmpDetect.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.21 |
|
expPort-total-amp-seconds-since-time
mandatory
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the curre… |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.22 |
|
expPort-amps-enabled
mandatory
Amperage probe alarm enabled(1) or disabled(0).
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.23 |
|
expPort-amps-min
mandatory
The amperage probe minimum, from 0 to 30000 milliamps.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.24 |
|
expPort-amps-max
mandatory
The amperage probe maximum, from 0 to 30000 milliamps.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.25 |
|
expPort-amps-uV-per-10mA
mandatory
The scaling factor used for the amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.26 |
|
expPort-amps-max-range
mandatory
The maximum RMS milliamps measureable by the AmpDetect.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.27 |
|
expPort-ext-temp
mandatory
The reading of the external temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.40 |
|
expPort-ext-temp-enabled
mandatory
External temperature probe alarm enabled(1) or disabled(0).
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.41 |
|
expPort-ext-temp-min
mandatory
The external temperature probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.42 |
|
expPort-ext-temp-max
mandatory
The external temperature probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.43 |
|
expPort-ext-temp-uV-per-degreeC
mandatory
The scaling factor used for the external temperature probe to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.44 |
|
expPort-ext-temp-uV-at-0-degreeC
mandatory
The offset used for the external temperature probe of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.45 |
|
expPort-ext-temp-min-range
mandatory
The minimum temperature measureable by the temperature sensor, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.46 |
|
expPort-ext-temp-max-range
mandatory
The maximum temperature measureable by the temperature sensor, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.47 |
|
expPort-ext-dry
mandatory
The current value of the external dry contact sensor: 0=Open, 1=Closed, -1=N/A
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.60 |
|
expPort-ext-dry-alarm-value
mandatory
The value to generate alarms on for the external dry contact sensor: 0=Open, 1=Closed
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.61 |
|
expPort-ext-dry-enabled
mandatory
External dry contact sensor alarm enabled(1) or disabled(0).
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.62 |
|
expPort-ext-dry-label
mandatory
The sensor name/label for the dry contact sensor
|
RFC1213-MIBDisplayStringr/w Textual Convention: RFC1213-MIBDisplayString OctetString |
.1.3.6.1.4.1.5528.31.1.63 |
|
expPort-ext-dry-open-label
mandatory
The sensor name/label for the open(0) state for the dry contact sensor
|
RFC1213-MIBDisplayStringr/w Textual Convention: RFC1213-MIBDisplayString OctetString |
.1.3.6.1.4.1.5528.31.1.64 |
|
expPort-ext-dry-closed-label
mandatory
The sensor name/label for the closed(0) state for the dry contact sensor
|
RFC1213-MIBDisplayStringr/w Textual Convention: RFC1213-MIBDisplayString OctetString |
.1.3.6.1.4.1.5528.31.1.65 |
|
expPort-ext-dry-open-to-close-millis
mandatory
The minimum number of milliseconds that the dry contact sensor
must read closed before the state is changed from open to closed. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.66 |
|
expPort-ext-dry-close-to-open-millis
mandatory
The minimum number of milliseconds that the dry contact sensor
must read openbefore the state is changed from closed to open. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.67 |
|
expPort-ext-dry-response
mandatory
The type of alert response for the dry contact sensor: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera. |
RFC1213-MIBDisplayStringr/w Textual Convention: RFC1213-MIBDisplayString OctetString |
.1.3.6.1.4.1.5528.31.1.68 |
|
expPort-ext-humi
mandatory
The reading of the external humidity probe, in percent.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.80 |
|
expPort-ext-humi-enabled
mandatory
External humidity probe alarm enabled(1) or disabled(0).
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.81 |
|
expPort-ext-humi-min
mandatory
The external humidity probe minimum, in percent.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.82 |
|
expPort-ext-humi-max
mandatory
The external humidity probe maximum, in percent.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.83 |
|
expPort-ext-humi-uV-per-percent
mandatory
The scaling factor used for the external humidity probe to convert microvolts measured from the
humidity sensor into percent. Needs to be set based on the type of humidity sensor module installed. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.84 |
|
expPort-ext-humi-uV-at-0-percent
mandatory
The offset used for the external humidity probe of microvolts measured from the
humidity sensor at zero percent. Needs to be set based on the type of humidity sensor module installed. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.85 |
|
expPort-ext-humi-min-range
mandatory
The minimum humidity measureable by the humidity sensor, in percent.
Needs to be set based on the type of humidity sensor module installed. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.86 |
|
expPort-ext-humi-max-range
mandatory
The maximum humidity measureable by the humidity sensor, in percent.
Needs to be set based on the type of humidity sensor module installed. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5528.31.1.87 |