NETBOTZ-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
1
Rows
1
Columns
36

expPortTable

table mandatory
.1.3.6.1.4.1.5528.31 · 1 row entry · 36 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk expPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'NETBOTZ-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'NETBOTZ-MIB::expPortTable'
A list of expansion port entries.
expPortEntry row .1.3.6.1.4.1.5528.31.1
An expansion port entry for a single port
Indexes
No indexes recorded
Column Syntax OID
The module ID of the sensor module installed. Blank string indicates that no module is installed.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.5528.31.1.1
The type of sensor module installed. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.5528.31.1.2
expPort-labelmandatory
The label for the expansion port. Ports default to the label 'Extn', for port n.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.5528.31.1.3
expPort-ampsmandatory
The reading of the amperage probe, in milliamps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.20
The accumulated total of amp-seconds on the AmpDetect.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.21
The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the curre…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.22
Amperage probe alarm enabled(1) or disabled(0).
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.23
The amperage probe minimum, from 0 to 30000 milliamps.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.24
The amperage probe maximum, from 0 to 30000 milliamps.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.25
The scaling factor used for the amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.26
The maximum RMS milliamps measureable by the AmpDetect.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.27
The reading of the external temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.40
External temperature probe alarm enabled(1) or disabled(0).
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.41
The external temperature probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.42
The external temperature probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.43
The scaling factor used for the external temperature probe to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.44
The offset used for the external temperature probe of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.45
The minimum temperature measureable by the temperature sensor, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.46
The maximum temperature measureable by the temperature sensor, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.47
The current value of the external dry contact sensor: 0=Open, 1=Closed, -1=N/A
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.60
The value to generate alarms on for the external dry contact sensor: 0=Open, 1=Closed
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.61
External dry contact sensor alarm enabled(1) or disabled(0).
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.62
The sensor name/label for the dry contact sensor
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.5528.31.1.63
The sensor name/label for the open(0) state for the dry contact sensor
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.5528.31.1.64
The sensor name/label for the closed(0) state for the dry contact sensor
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.5528.31.1.65
The minimum number of milliseconds that the dry contact sensor
must read closed before the state is changed from open to closed.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.66
The minimum number of milliseconds that the dry contact sensor
must read openbefore the state is changed from closed to open.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.67
The type of alert response for the dry contact sensor: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.5528.31.1.68
The reading of the external humidity probe, in percent.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.80
External humidity probe alarm enabled(1) or disabled(0).
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.81
The external humidity probe minimum, in percent.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.82
The external humidity probe maximum, in percent.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.83
The scaling factor used for the external humidity probe to convert microvolts measured from the
humidity sensor into percent. Needs to be set based on the type of humidity sensor module installed.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.84
The offset used for the external humidity probe of microvolts measured from the
humidity sensor at zero percent. Needs to be set based on the type of humidity sensor module installed.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.85
The minimum humidity measureable by the humidity sensor, in percent.
Needs to be set based on the type of humidity sensor module installed.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.86
The maximum humidity measureable by the humidity sensor, in percent.
Needs to be set based on the type of humidity sensor module installed.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5528.31.1.87