expPort-ext-dry-response
NETBOTZ-MIB ·
.1.3.6.1.4.1.5528.31.1.68
Object
The type of alert response for the dry contact sensor: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
Context
- MIB
- NETBOTZ-MIB
- OID
.1.3.6.1.4.1.5528.31.1.68- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- expPortEntry
- Table
- expPortTable
- Siblings
- 35
Syntax
RFC1213-MIBDisplayString
- Source
- RFC1213-MIBDisplayString
- Base type
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| expPort-module-id mandatory The module ID of the sensor module installed. Blank string indicates that no module is installed. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.5528.31.1.1 |
| expPort-module-type mandatory The type of sensor module installed. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.5528.31.1.2 |
| expPort-amps mandatory The reading of the amperage probe, in milliamps. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.20 |
| expPort-total-amp-seconds mandatory The accumulated total of amp-seconds on the AmpDetect. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.21 |
| expPort-total-amp-seconds-since-time mandatory The UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect.
Writing a value to this attribute resets the accumulated total amp… | column | Integer32 | .1.3.6.1.4.1.5528.31.1.22 |
| expPort-amps-enabled mandatory Amperage probe alarm enabled(1) or disabled(0). | column | Integer32 | .1.3.6.1.4.1.5528.31.1.23 |
| expPort-amps-min mandatory The amperage probe minimum, from 0 to 30000 milliamps. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.24 |
| expPort-amps-max mandatory The amperage probe maximum, from 0 to 30000 milliamps. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.25 |
| expPort-amps-uV-per-10mA mandatory The scaling factor used for the amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detec… | column | Integer32 | .1.3.6.1.4.1.5528.31.1.26 |
| expPort-amps-max-range mandatory The maximum RMS milliamps measureable by the AmpDetect. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.27 |
| expPort-label mandatory The label for the expansion port. Ports default to the label 'Extn', for port n. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.5528.31.1.3 |
| expPort-ext-temp mandatory The reading of the external temperature probe, in degrees F or degrees C (depends on netBotz-ismetric). | column | Integer32 | .1.3.6.1.4.1.5528.31.1.40 |
| expPort-ext-temp-enabled mandatory External temperature probe alarm enabled(1) or disabled(0). | column | Integer32 | .1.3.6.1.4.1.5528.31.1.41 |
| expPort-ext-temp-min mandatory The external temperature probe minimum, in degrees F or degrees C (depends on netBotz-ismetric). | column | Integer32 | .1.3.6.1.4.1.5528.31.1.42 |
| expPort-ext-temp-max mandatory The external temperature probe maximum, in degrees F or degrees C (depends on netBotz-ismetric). | column | Integer32 | .1.3.6.1.4.1.5528.31.1.43 |
| expPort-ext-temp-uV-per-degreeC mandatory The scaling factor used for the external temperature probe to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of tempera… | column | Integer32 | .1.3.6.1.4.1.5528.31.1.44 |
| expPort-ext-temp-uV-at-0-degreeC mandatory The offset used for the external temperature probe of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor m… | column | Integer32 | .1.3.6.1.4.1.5528.31.1.45 |
| expPort-ext-temp-min-range mandatory The minimum temperature measureable by the temperature sensor, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.46 |
| expPort-ext-temp-max-range mandatory The maximum temperature measureable by the temperature sensor, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.47 |
| expPort-ext-dry mandatory The current value of the external dry contact sensor: 0=Open, 1=Closed, -1=N/A | column | Integer32 | .1.3.6.1.4.1.5528.31.1.60 |
| expPort-ext-dry-alarm-value mandatory The value to generate alarms on for the external dry contact sensor: 0=Open, 1=Closed | column | Integer32 | .1.3.6.1.4.1.5528.31.1.61 |
| expPort-ext-dry-enabled mandatory External dry contact sensor alarm enabled(1) or disabled(0). | column | Integer32 | .1.3.6.1.4.1.5528.31.1.62 |
| expPort-ext-dry-label mandatory The sensor name/label for the dry contact sensor | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.5528.31.1.63 |
| expPort-ext-dry-open-label mandatory The sensor name/label for the open(0) state for the dry contact sensor | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.5528.31.1.64 |
| expPort-ext-dry-closed-label mandatory The sensor name/label for the closed(0) state for the dry contact sensor | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.5528.31.1.65 |
| expPort-ext-dry-open-to-close-millis mandatory The minimum number of milliseconds that the dry contact sensor
must read closed before the state is changed from open to closed. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.66 |
| expPort-ext-dry-close-to-open-millis mandatory The minimum number of milliseconds that the dry contact sensor
must read openbefore the state is changed from closed to open. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.67 |
| expPort-ext-humi mandatory The reading of the external humidity probe, in percent. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.80 |
| expPort-ext-humi-enabled mandatory External humidity probe alarm enabled(1) or disabled(0). | column | Integer32 | .1.3.6.1.4.1.5528.31.1.81 |
| expPort-ext-humi-min mandatory The external humidity probe minimum, in percent. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.82 |
| expPort-ext-humi-max mandatory The external humidity probe maximum, in percent. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.83 |
| expPort-ext-humi-uV-per-percent mandatory The scaling factor used for the external humidity probe to convert microvolts measured from the
humidity sensor into percent. Needs to be set based on the type of humidity sensor… | column | Integer32 | .1.3.6.1.4.1.5528.31.1.84 |
| expPort-ext-humi-uV-at-0-percent mandatory The offset used for the external humidity probe of microvolts measured from the
humidity sensor at zero percent. Needs to be set based on the type of humidity sensor module insta… | column | Integer32 | .1.3.6.1.4.1.5528.31.1.85 |
| expPort-ext-humi-min-range mandatory The minimum humidity measureable by the humidity sensor, in percent.
Needs to be set based on the type of humidity sensor module installed. | column | Integer32 | .1.3.6.1.4.1.5528.31.1.86 |
| expPort-ext-humi-max-range mandatory The maximum humidity measureable by the humidity sensor, in percent.