tlpUpsConfigFaultAction

TRIPPLITE-PRODUCTS · .1.3.6.1.4.1.850.1.1.3.1.5.1.1.16

Object

column r/w Enumeration
Determines the action to take if the output needs to be shut down due to a
fault condition, limited by the type of fault incurred. When configured for
bypass(0), the ups will go to bypass on a fault condition. When configured
for standby(1), the ups will go to standby mode on a fault condition. Either
configuration will be valid as long as AC input is within normal line voltage
and frequency limits when the fault condition occurs. If the line is outside
these limits, the ups will turn off. If this value is not supported by the ups,
then this value will always return ERROR_NO_SUCH_NAME.