tlpAtsConfigVoltageRangeOldEntry
TRIPPLITE-PRODUCTS ·
.1.3.6.1.4.1.850.1.1.3.4.5.2.1
Object
row
obsolete
An entry containing voltage range configuration options for a particular ats.
Context
- MIB
- TRIPPLITE-PRODUCTS
- OID
.1.3.6.1.4.1.850.1.1.3.4.5.2.1- Type
- row
- Status
- obsolete
- Parent
- tlpAtsConfigVoltageRangeOldTable
- Table
- tlpAtsConfigVoltageRangeOldTable
- Children
- 10
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| tlpAtsConfigHighVoltageTransferOld obsolete The maximum line voltage allowed before the unit disconnects the
AC input connection. The maximum value allowed is dictated by
tlpAtsInputHighTransferVoltageUpperBound (inclusivel… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.2.1.1 |
| tlpAtsConfigLowVoltageTransferOld obsolete The minimum line voltage allowed before the unit disconnects the
AC input connection. The maximum value allowed is dictated by
tlpAtsConfigLowVoltageResetOld. The minimum value al… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.2.1.10 |
| tlpAtsConfigHighVoltageResetOld obsolete If a unit is disconnected due to over-voltage, the line voltage has to
fall below this value before the unit re-connects the AC input connection.
The maximum value allowed is dict… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.2.1.2 |
| tlpAtsConfigSource1TransferResetOld obsolete If input source 1 voltage level is above this value, a unit connected to
source 2 will transition to source 1 (if it is the preferred source). The
maximum value allowed is dictate… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.2.1.3 |
| tlpAtsConfigSource1BrownoutSetOld obsolete This value dictates the voltage level below which source 1 goes into a
brown out condition. The maximum value allowed is dictated by
tlpAtsConfigSource1TransferResetOld. The minim… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.2.1.4 |
| tlpAtsConfigSource1TransferSetOld obsolete If input source 1 voltage level falls below this value, a unit connected to
source 1 will transition to source 2 (if it is in fair condition as denoted
by tlpAtsConfigSource2Trans… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.2.1.5 |
| tlpAtsConfigSource2TransferResetOld obsolete If input source 2 voltage level is above this value, a unit connected to
source 1 will transition to source 2 (if it is the preferred source). The
maximum value allowed is dictate… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.2.1.6 |
| tlpAtsConfigSource2BrownoutSetOld obsolete This value dictates the voltage level below which source 2 goes into a
brown out condition. The maximum value allowed is dictated by
tlpAtsConfigSource2TransferResetOld. The minim… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.2.1.7 |
| tlpAtsConfigSource2TransferSetOld obsolete If input source 2 voltage level falls below this value, a unit connected to
source 2 will transition to source 1 (if it is in fair condition as denoted
by tlpAtsConfigSource1Trans… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.2.1.8 |
| tlpAtsConfigLowVoltageResetOld obsolete If a unit is disconnected due to under-voltage or is not powered up yet, the
line voltage has to rise above this value before the unit gets connected to
the AC input connection. T… | column | 0.1 Volts SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.3.4.5.2.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| tlpDeviceIndex The table row index for the device. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.850.1.1.1.2.1.1 |